Column bases in shear and normal force
Nol Gresnigt
Delft University of Technology, Civil Engineering and Geosciences, the Netherlands
Arie Romeijn
Delft University of Technology, Civil Engineering and Geosciences, the Netherlands
František Wald
Czech Technical University, Prague, Czech Republic
Martin Steenhuis †
Eindhoven University of Technology, Faculty of Architecture, Building and Planning,
the Netherlands
Connections of steel columns to concrete foundations may be loaded by combinations of
normal force, bending moment and shear force. Shear force will primarily be transmitted by
friction between the base plate and the grout layer to the concrete foundation. If the
compression force is small, or if tension force is present, as may occur in slender high rise
structures like towers and masts, the friction will be small or absent. Then, the anchor bolts
will be loaded by shear force and bending moment.
At the Stevin Laboratory of Delft University of Technology, experimental and theoretical
research has been carried out on column bases loaded by combinations of shear force and
tension force.
In the paper, the main results of this research programme are summarised. The test results are
presented and the analytical model that was developed to describe the load deformation
behaviour.
A comparison is made with the design rules as given by the Comité Euro-International du
Béton (CEB, 1994 and 1996). Based on the research, design rules for this load case were
proposed to the drafting panel for the revision of Eurocode 3 from ENV to EN status (Part 1.8:
Design of Joints).
Key words: Base plates, shear and tension, Eurocode 3, analytical model, tests
HERON Vol. 53 (2008) No. 1/2
1
Introduction
Horizontal shear force in column bases may be resisted by (see Figure 1):
(a)
friction between the base plate, grout and concrete footing,
(b)
shear and bending of the anchor bolts,
(c)
a special shear key, for example a block of I-stub or T-section or steel pad welded
onto the bottom of the base plate,
(d)
(a)
direct contact, e.g. achieved by recessing the base plate into the concrete footing.
(b)
(c)
(d)
Figure 1: Column bases loaded by horizontal shear force
In most cases, the shear force can be resisted through friction between the base plate and
the grout. The friction depends on the compressive load and on the coefficient of friction.
Pre-stressing the anchor bolts will increase the shear force transfer by friction.
Sometimes, for instance in slender buildings, it may happen that due to horizontal forces
(wind loading) columns are loaded in tension. In such cases, the horizontal shear force
usually cannot be transmitted through friction. If no other provisions are installed (e.g.
shear studs), the anchor bolts will have to transmit these shear forces.
Because the grout does not have sufficient strength to resist bearing stresses between the
bolt and the grout, considerable bending of the anchor bolts may occur, as is indicated in
Figure 2. The main failure modes are rupture of the anchor bolts (local curvature of the bolt
exceeds the ductility of the bolt material), crumbling of the grout, failure (splitting) of the
concrete footing and pull-out of the anchor bolt.
Due to the horizontal displacement, not only shear and bending in the bolts will occur, but
also the tensile force in the bolts will be increased due to second order effects. The
horizontal component of the increasing tensile force gives an extra contribution to the
shear resistance and stiffness. The increasing vertical component gives an extra
contribution to the transfer of load by friction and increases resistance and stiffness as well.
These factors explain the shape of the load deformation diagram as given in Figure 2. The
increase of the load continues till fracture occurs in one of the components of the
connection. If the connection is well designed and executed, such fracture will occur at
88
very large deformation (much larger than acceptable in serviceability and ultimate limit
state).
Fv
Fh
Fh
δh
δh
0
Figure 2: Column base loaded by shear and tension force
The thickness of the grout layer has an important influence on the horizontal deformations.
In the tests carried out by the Stevin Laboratory (Stevin, 1989), the deformations at rupture
of the anchor bolts were between about 15 and 30 mm, whilst grout layers had a thickness
of 15, 30 and 60 mm. The deformations have to be taken into account in the check of the
serviceability limit state. Because of the rather large deformations that may occur, this
check may govern the design. The size of the holes may have a considerable influence on
the horizontal deformations, especially when oversized holes are applied. In such cases it
may be useful to apply larger washers under the nuts, to be welded onto the base plate
after erection, or to fill the hole by a two component resin. For the application of such resin,
reference is made to the ECCS recommendations (1994) and EN 1993-1-8 (2006).
In the Stevin Laboratory (Stevin, 1989), a model for the load deformation behaviour of base
plates loaded by combinations of normal force and shear has been developed, see section 2.
Section 4 gives an overview of the tests carried out in Delft. For the design of fasteners, the
CEB has published a Design Guide (CEB, 1996). The CEB model (the CEB design rules for
"fixtures") has been compared with the Stevin Laboratory model and the tests. It appears
that the CEB model gives very conservative results, especially when large tensile forces are
present and / or the thickness of the grout layer is large. The main reason is that the CEB
model does not take account of the positive influence of the grout layer (COST, 1999). In
section 3 a summary of the CEB model is presented. In section 5 the test results are
compared with the Stevin Laboratory model and the CEB model. Section 6 gives a
summary of the design rules proposed for part 1.8 of EN 1993.
89
It is noted that in steel construction, usually only the steel part of the base plate connection
is considered. In the CEB Design Guide much attention is paid to the concrete part. It is
recommended to the steel designer to acquire knowledge about the requirements to the
reinforced concrete. For detailed design guidance and the various failure modes that may
occur in the concrete, reference is made to the CEB Design Guide (CEB, 1996).
For an interesting test series on anchor bolts, reference is made to the work of Nakashima
(1998). He studied the mechanical properties of steel column base anchor bolts, particularly
those parts of such anchor bolts which are exposed, i.e., not embedded in concrete footings.
He studied the anchor bolts which are often subjected to combined stresses which are
caused by tension, shear and in addition bending moments. Special attention is paid to the
influence of the thread and other factors on the deformation capacity.
2
The Stevin Laboratory model
In most cases the shear force can be transmitted via friction between the base plate and the
grout. The friction capacity depends on the normal force (compression) between the base
plate and the grout and the friction coefficient. At increasing horizontal displacement the
shear force increases till it reaches the friction capacity. At that point the friction resistance
stays constant with increasing displacements, while the load transfer through the anchor
bolts increases further. Because the grout does not have sufficient strength to resist the
bearing stresses between the bolts and the grout, considerable bending of the anchor bolts
may occur, as is indicated in Figures 2 and 3.
The test specimen shows
the bending deformation
of the anchor bolts, the
crumbling of the grout
and the final cracking of
the concrete.
Figure 3: Test specimen
loaded by shear force and
tensile force (Stevin, 1989)
90
2.1
Derivation of the analytical model
In Figure 4, the deformations and some important measures are indicated. Figure 5 shows
the schematisation of the deformations and the forces, which are taken into account in the
analytical model. In the derivations, the following symbols are used:
Ab, s
=
tensile stress area of the anchor bolt
Ft
=
applied tensile force
Fh
=
applied shear force (horizontal force)
Fw
=
friction force between base plate and grout
Nb
=
normal force in the grout
Fa
=
normal force in the anchor bolt
db
=
diameter of the anchor bolt
δa
=
elongation of the anchor bolt
δb
=
compression of the grout layer
δh
=
horizontal displacement of the base plate
v
=
actual thickness of the grout layer
vr
=
thickness of the grout layer in the analytical model: vr = v + 0.5d b
( vr = A as in the CEB model, see section 3)
Figure 4: Deformation and some measurements of
the anchor bolts
Figure 5: Schematisation of the deformations
and forces in the analytical model
Due to the horizontal displacement of the base plate, bending of the bolts will occur and
the tensile force in the bolts (Fa) will increase. This causes an increase of the compression
91
force between the base plate and the grout, resulting in a larger friction force (Fw) between
the grout and the base plate, see equations (2) and (3).
At rather small horizontal deformations (δh), the tensile force Fa in the bolt reaches the yield
force Fyb = As ⋅ f yb . This means that the bending moments in the anchor bolts rapidly
decrease and the horizontal component Fah of Fa (Figure 5) rapidly increases. Because of the
high tensile force in the bolts, the bending moment capacity in the bolts will be small.
Therefore, in the analytical model the bending moments in the bolts are not taken into
account. The bearing stresses of the grout-bolt contact are not taken into account either,
because they are small compared to other forces. For the horizontal equilibrium it follows:
Fh = Fa
δh
vr + δ a
+ Fw
vr − δ b
− Ft )
vr + δ a
Fw = f w ( Fa
(1)
(2)
In these equations fw is the coefficient of friction between the grout and the base plate.
For the deformation it follows:
2
2
δ 2h = ( v r + δ a ) - ( v r - δ b )
(3)
Because δ 2h is small compared with δ h this can be simplified to:
2
δ h = 2 vr ( δ a + δb )
(4)
For the "elastic" part of the behaviour, δa and δb can be written as:
δa =
Fa vr
E Ab, s
(5)
δb =
( F a - F t ) vr
E grout A grout
(6)
Because Egrout Agrout is much greater than EAb,s , δb will be small compared with δa. Therefore
δb is not taken into account further. From the geometry it follows:
v r + δ a = δ h2 + v r2
(7)
For (1), (2) and (4) can be written with (7):
Fh = Fa
δh
δ h2
+ v r2
+ Fw
⎛
⎞
vr
Fw = f w ⎜ F a
- Ft ⎟
⎜
⎟
2
2
δ h + vr
⎝
⎠
92
(8)
(9)
δh = 2 v r δ a
(10)
For every δh the elongation δa can be calculated via (10), then with (5) the force Fa and with
(8) and (9) the horizontal force Fh. The above equations are valid for Fa ≤ Fa,y where
Fa , y = As ⋅ f y ,b
(11)
For Fa = Fa,y it follows with (8), (9) and (11):
Fh =
f y ,b Ab, s
(δh + f wvr ) − f w Ft
δ h2 + v r2
(12)
with
2 f y ,b
δ h = vr
(13)
E
For the design value of the coefficient of friction fw,d the following values are proposed:
•
sand-cement mortar: fw,d = 0,20
•
special grout (e.g. Pagel IV): fw,d = 0,30
2.2
Comparison with one of the tests
To demonstrate the analytical model, one of the test results is calculated, namely DT6 in
(Stevin, 1989), see Figure 6. In this test, a tensile force Ft = 141 kN was kept constant in the
column, while the horizontal force Fh was increased. Figure 7 gives the test result together
with the result of the analytical model. With equations (13) and (12) it follows:
δ h = vr
Fh =
2 f y ,b
E
f y ,b Ab, s
δ h2
+ vr2
= 40
2 ⋅ 861
= 3,6 mm
210 000
(δ h + f wvr ) − f w Ft =
861 ⋅ 245
3,62 + 402
(3,6 + 0,20 ⋅ 40) ⋅ 2 − 0,20 ⋅ 141 = 94 kN
A linear relationship is assumed until the value of δh equals δh according to equation (13)
and Fa equals As fy,b. This part of the load deformation curve is called the elastic stage, see
Figure 7. For larger values of δh the load deformation curve is called the plastic stage. E.g.
for δh = 15 mm, it follows with equation (12): Fh = 227 - 28 = 199 kN.
In the test, failure occurred in the anchor bolts (rupture) at the edge of the base plate, due
to local high bending strains. The value Fv.Rd = 105 kN in Figure 7 is explained in the next
section.
93
•
2 anchor bolts M20, grade 8.8
•
Fu,b = 1076 N/mm2 (measured
tensile strength of the bolt
material)
•
fy;b = 861 N/mm2 (assumed as
0,8 fu,b)
•
εu,b = 12% (measured rupture
strain of the bolt material)
•
As = 245 mm2
•
grout = sand-cement mortar
•
v = 30 mm
•
vr = 30 + 0,5 ⋅ 20 = 40 mm
Figure 6: Set-up of test DT6
Figure 7: Comparison of the analytical model with result of test DT6
2.3
Ultimate design strength
The ultimate strength is a function of the strength of the various parts in the column base
and the ductility of the anchor bolts. A greater ductility allows a greater horizontal
displacement and thus a greater Fah (Figure 5) and consequently a greater Fh .
94
It can also be noted that δh should be limited, both at serviceability and at ultimate limit
state.
To predict the ultimate strength (if governed by the anchor bolt), a relation is needed
between the local strain in the bolt and the horizontal deformation. Furthermore, the strain
capacity (ductility) of the various anchor materials must be known.
In the tests, it appeared, as could be expected, that 4.6 grade anchor bolts were much more
ductile than the 8.8 grade bolts. A difference in ductility can also be found in the
requirements in the relevant product standards.
It is not easy to establish a reliable model to determine the strains in the anchor bolts and
to find reliable data for the bending strain capacity of various anchor bolt materials.
Therefore, a simplified method is proposed for the shear resistance of 4.6 and 8.8 grade
anchor bolts. This simplified method is adopted in the Dutch Standard (NEN 6770, 1990):
4.6 anchors:
Fv.Rd =
8.8 anchors:
Fv.Rd =
0,375 f u ,b ⋅ Ab, s
γMb
0,25 f u ,b ⋅ Ab, s
γMb
(14)
(15)
with γMb = 1,25.
Differences in ductility cause differences in ultimate strength, see Fig 7. This is the reason
for the different factors in (14) and (15). Note that the resistance functions (14) and (15) are
similar to the "normal" Eurocode 3 functions for bolts loaded in shear:
4.6 and 8.8 bolts: Fv. Rd =
0 ,60 fu ,b ⋅ Ab, s
γMb
(16)
After checking the design resistance, the horizontal displacements should be checked for
the serviceability limit state and for the ultimate limit state.
3
The CEB Design Guide model
In the CEB Design Guide (CEB, 1996), the load transfer from a fixture (e.g. base plate) into
the concrete is covered. The CEB Design Guide covers many types of anchors and possible
failure modes of the concrete. The design of the fixture (e.g. the base plate) must be
performed according to the appropriate code of practice. In case of steel fixtures, a steel
construction code is used.
95
Background information can be found in a separate CEB state of the art report: "Fastenings
to concrete and masonry structures" (CEB, 1994). It reviews the behaviour of fastenings in
concrete and masonry for the entire range of loading types (including monotonic,
sustained, fatigue, seismic and impact loading), as well as the influence of environmental
effects, based on experimental results.
For the transfer of shear forces, two methods are considered, namely:
•
Friction between the fixture (e.g. base plate) and the grout or concrete,
•
Shear/bending of the anchors.
3.1
Friction between base plate and grout/concrete
In section 4.1 of the CEB Guide it is stated that when a bending moment and/or a
compression force is acting on a fixture, a friction force may develop, which for simplicity
may conservatively be neglected in the design of the anchorage. If it is to be taken into
account, then the design value of this friction force VRd,f may be taken as:
VRD , f = VRk , f / γ Mf = µ ⋅ CSd / γ Mf
(17)
with
VRk,f
=
characteristic shear force
VRd,f
=
design shear force
µ
=
coefficient of friction
CSd
=
compression force under the fixture due to design actions
γMf
=
1,5 (ultimate limit state)
γMf
=
1,3 (limit state of fatigue)
γMf
=
1,0 (serviceability 1imit state)
In general, the coefficient of friction between a fixture and concrete may be taken as µ = 0,4.
The friction force VRd,f should be neglected if the thickness of grout beneath the fixture is
thicker than 3 mm (e.g. in case of levelling nuts) and for anchorages close to an edge.
In conclusion, it can be stated that for "normal column bases", according to the CEB Guide,
load transfer through friction should be neglected because in normal steel constructions
the thickness of the grout is always more than 3 mm.
3.2
Shear/bending of anchor bolts
For the resistance of anchor bolts, two cases are considered, namely (b) and (c):
(b)
96
Shear loads without lever arm
Shear loads acting on anchors may be assumed to act without a lever arm if both of
the following conditions are fulfilled.
(1)
The fixture must be made of metal and in the area of the anchorage be
fixed directly to the concrete without an intermediate layer or with a
levelling layer of mortar with a thickness ≤ 3 mm.
(2)
(c)
The fixture must be adjacent to the anchor over its entire thickness.
Shear loads with lever arm
If the conditions (1) and (2) of the preceding section (b) are not fulfilled, the length A
of the lever arm is calculated according to equation (18):
A = a3 + e1
(18)
with
el
=
distance between shear load and concrete surface
a3
=
0,5 d for post-installed and cast-in-place anchors (Figure 8)
a3
=
0 if a washer and a nut are directly clamped to the concrete surface
d
=
nominal diameter of the anchor bolt or thread diameter (Figure 8)
The design moment acting on the anchor is calculated according to equation (19):
M Sd = VSd ⋅
A
αM
(19)
The value of αM depends on the degree of restraint at the side of the fixture. No
restraint (αM = 1,0) should be assumed if the fixture can rotate freely. Full restraint
(αM = 2,0) may be assumed only if the fixture cannot rotate (see Figure 8b) and the
hole is smaller than 1,2d.
Figure 8: Examples of fastenings (a) without and (b) with full restrain of the anchor at the side of
the fixture (Figure 27 in the CEB Design Guide)
97
3.3
Plastic analysis
In section 4.2.2 of the CEB Guide it is stated that in a plastic analysis it is assumed that
significant redistribution of anchor tension and shear forces will occur in a group of anchor
bolts. Therefore, plastic analysis is acceptable only when the failure is governed by ductile
steel failure of the anchors. To ensure this failure mode, the CEB Guide gives several
conditions that should be met:
(1)
The arrangement of the anchors. It is assumed that base plates meet these
conditions.
(2)
The ultimate strength of a fastening as governed by concrete failure, should exceed
its strength as governed by steel failure (equation (20)):
Rd , c ≥ 1.25 Rd , s ⋅ fuk / f yk
(20)
with
Rd,c =
design concrete capacity of the fastening (concrete cone, splitting or pull
out failure (tension loading) or concrete pry-out or edge failure (shear
loading),
Rd,s =
design steel capacity of the fastening,
fuk
=
the characteristic ultimate tensile strength (nominal value),
fyk
=
the characteristic yield strength or proof strength respectively (nominal
value).
Equation (20) should be checked for tension, shear and combined tension and shear
forces.
(3)
The nominal steel strength of the anchors should not exceed fuk = 800 MPa. The ratio
of nominal steel yield strength to nominal ultimate strength should not exceed fyk /
fuk = 0,8, while the rupture elongation (measured over a length equal to 5d) should
be at least 12%.
(4)
Anchors that incorporate a reduced section (e.g. a threaded part) should satisfy the
following conditions:
(a)
For anchors loaded in tension, the tensile strength Nuk of the reduced section
should either be greater than 1.1 times the yield strength Nyk of the
unreduced section, or the stressed length of the reduced section should be ≥
5d (d = anchor diameter outside the reduced section).
(b)
For anchors loaded in shear or which are to redistribute shear forces, the
beginning of the reduced section should either be ≥ 5d below the concrete
98
surface or in the case of threaded anchors the threaded part should extend ≥
2d into the concrete.
(c)
For anchors loaded in combined tension and shear, the conditions (a) and (b)
above should be met.
(5)
The steel fixture should be embedded in the concrete or fastened to the concrete
without an intermediate layer or with a layer of mortar with a thickness ≤ 3 mm.
The diameter of the clearance hole in the fixture should be ≤ 1,2d (the bolt is
(6)
assumed to bear against the fixture).
From the above equations, especially equation (20), it follows that according to the CEB
Design Guide plastic design is only allowed for base plates without grout layer or with a
grout layer not thicker than 3 mm. For usual base plate construction this means that
according to the CEB Design Guide, plastic design is not allowed.
In equation (20) the relation between the required design concrete capacity of the fastening
and the design steel capacity of the fastening is given. It appears that for e.g. 8.8 anchors it
gives:
Rd ,c ≥ 1,56 Rd , s
(21)
In the Stevin Laboratory design model it is assumed that measures are taken to ensure that
failure of the concrete will not occur before failure of the base plate or anchor. The above
requirements seem adequate to ensure this prerequisite.
Resistance functions for the shear load
3.4
In section 9.3.1 of the CEB Design Guide (1994), the following required verifications are
given in the case of shear loading (elastic design approach):
•
Steel failure, shear load without lever arm (VRd,s)
•
Steel failure, shear load with lever arm (VRd,sm)
•
Concrete pry-out failure (VRd,cp)
•
Concrete edge failure (VRd,c)
For the design values VRd,s and VRd,sm the following equations are given:
VRd,s =
VRk.s
γ Ms
VRd,sm =
VRk.sm
γ Ms
with
VRk,s = k 2 ⋅ As ⋅ f yk
with
VRk.sm =
α M ⋅ M Rk,s
A
(22)
(23)
with
k2
=
0,6
(24)
99
As
=
M Rk , s
=
0
M Rk
,s
=
N Rd , s
=
N Rk , s / γ Ms
(27)
N Rk , s
=
As ⋅ f y , k
(28)
γ Ms
=
1,20 if f uk ≤ 800 MPa and f yk / f uk ≤ 0,8
(29)
γ Ms
=
1,50 if f uk ≥ 800 MPa or f yk / f uk ≥ 0,8
(30)
N Sd
=
applied normal force
αM
=
factor depending on the support conditions, see Figure 8
A
=
length of lever arm
stressed cross-section of the anchor in the shear plane
0
M Rk
, s (1 − N Sd / N Rd , s )
(25)
0
characteristic bending resistance of individual anchor M Rk
, s = 1,5 WeA f uk
(26)
Type of grout:
•
Special grout Pagel IV
•
Sand - cement mortar 2:1
• No grout
Thickness of grout:
•
15 mm
•
30 mm
• 60 mm
Anchor bolt:
•
M20 - 4.6
• M20 – 8.8
Anchoring length:
•
250 mm with a bend at the
end of the bar
• 600 mm with anchor plate
Concrete reinforcement:
Figure 9: Test specimens; in the tests with 4.6 grade anchor bolts,
four bolts were applied and in the tests with 8.8 grade
anchors two bolts
100
•
with reinforcement
•
without reinforcement
Table 1: Summary of test results and comparison with design values according to the proposed
kN
Test / design value
kN
Design value Fv.Rd **)
mm
shear force Fh
MPa
Failure mode *)
Tensile force Ft
Ultimate stress
fub
MPa
grout v
Yield stress
fyb
Class
number
Test
Thickness of the
Anchors
Measured ultimate
resistance functions (Stevin, 1989)
kN
D7
4
4.6
290
423
30
0
310
Rupture
124
2,50
D8
4
4.6
290
423
30
0
310
Rupture
124
2,50
D9
4
4.6
290
423
30
0
260
Rupture
124
2,10
D10
2
8.8
-
1196
30
0
300
Rupture
117
2,56
D11
4
4.6
283
423
30
0
234
Rupture
124
1,89
D12
2
8.8
-
1176
60
0
295
Rupture
115
2,57
----
----
----
----
----
----
----
----
----
----
----
DT1
4
4.6
290
423
30
182
170
Cracking
124
1,37
DT2
4
4.6
290
423
30
121
250
Cracking
124
2,06
DT3
4
4.6
290
423
30
121
240
Rupture
124
1,94
DT4
4
4.6
290
423
30
121
240
Rupture
124
1,94
DT5
2
8.8
-
1152
30
141
178
Rupture
113
1,57
DT6
2
8.8
-
1076
30
141
200
Rupture
105
1,90
DT7
2
8.8
-
1070
30
141
190
Rupture
105
1,81
DT8
2
8.8
-
1045
60
141
230
Rupture
102
2,25
DT9
4
4.6
290
423
60
121
180
Pull-out
124
1,45
DT10
2
8.8
-
1049
60
141
228
Rupture
102
2,23
DT11
4
4.6
290
423
15
121
270
Cracking
124
2,17
DT12
2
8.8
-
1176
15
141
255
Rupture
115
2,21
DT13
4
4.6
280
414
60
121
320
Rupture
122
2,62
DT14
4
4.6
283
411
60
121
305
Cracking
121
2,52
DT15
2
8.8
-
1089
30
200
200
Cracking
107
1,87
DT16
4
4.6
309
443
30
200
255
Rupture
130
1,96
*)
**)
Cracking
= cracking of the concrete after large deformation of the anchor, e.g. for
test DT2 compare Figure 2.
Rupture
= rupture of the anchor
Pull-out
= pull-out of the anchor
These values were calculated with the measured material properties and dimensions.
101
4
Test Results and Comparison with the Models
Test programme
4.1
The main dimensions of the test specimens are given in Figure 9, as well as the parameters
in the test programme. See also Figures 3 and 6. More information on the test set-up is
given in the Stevin Laboratory report (1989). In the test programme (Stevin, 1989), three
test series were carried out:
•
Test series 1 (6 tests D1 – D6), with only shear force. Due to insufficient strength of the
concrete, premature splitting of the concrete occurred. These test results are omitted.
•
Test series 2 (6 tests D7 – D12), with only shear force. In these specimens, more
reinforcement bars were applied in the concrete.
•
Test series 3 (16 tests DT1 – DT16), with a combination of tensile force and shear force.
4.2
Test results and comparison with the Stevin Laboratory model
In Table 1 a summary is given of the main test results and a comparison with the proposed
resistance functions.
4.3
Comparison with the CEB model
The results of the comparison for all tests are given in Table 2. The application of the CEB
model for one of the tests (DT5) is demonstrated below.
Bolts M20, grade 8.8
fub, measured =
1152 MPa
take f yk
=
0,8 · 1152 = 922 MPa
take γ Ms
=
1,20 (for 8.8 bolts)
As
=
π ⋅ d s2 / 4 = 245 mm2 giving ds = 17,66 mm
N Rk , s
=
As ⋅ f yk = 245 ⋅ 922 ⋅ 10 −3 = 226 kN
N Rd , s
=
N Rk , s / γ Ms = 226 / 1,20 = 188 kN
N Sd
=
141 / 2 = 70,5 kN
WeA
=
0
M Rk
,s
=
102
π ⋅ d s3
32
=
π ⋅ 17,663
32
= 541 mm3
1.5 WeA ⋅ f yk = 1,5 ⋅ 541 ⋅ 922 = 748 ⋅ 103 Nmm
M Rk , s
=
0
3
3
M Rk
, s (1 − N Sd / N Rd , s ) = 748 ⋅ 10 (1 − 70,5 / 188) = 468 ⋅ 10 Nmm
VRk , s
=
k 2 ⋅ As ⋅ f yk = 0.6 ⋅ 245 ⋅ 922 ⋅ 10 −3 = 136 kN
VRk , sm
=
α M ⋅ M Rk , s
A
=
2 ⋅ 468 ⋅ 103 − 3
10 = 23,4 kN ≤ VRk , s = 136 kN
30 + 20 / 2
For the test with 2 bolts it follows 2· 23,4 = 46,8 kN ~ 47 kN, see Table 2.
Test / Stevin**)
Length A
Test / CEB
MRk,s*)
VRk,sm group*)
M0Rk,s*)
Nsd / NRd,s
Test
Nsd per bolt
NRd,s per bolt*)
Table 2: Comparison of test results with design values - CEB model and Stevin Laboratory model
Nm
Nm
mm
kN
0.77
235
54
40
11
15.6
1.4
0.51
235
115
40
23
10.9
2.0
30.25
0.51
235
115
40
23
10.4
1.9
30.25
0.51
235
115
40
23
10.4
1.9
188
70.50
0.37
748
468
40
47
3.8
1.6
176
70.50
0.40
699
418
40
42
4.8
1.9
DT7
175
70.50
0.40
695
414
40
41
4.6
1.8
DT8
171
70.50
0.41
678
398
70
23
10.1
2.3
DT9
59
30.25
0.51
235
115
70
13
13.7
1.5
DT10
171
70.50
0.41
681
401
70
23
10.0
2.2
DT11
59
30.25
0.51
235
115
25
37
7.3
2.2
DT12
192
70.50
0.37
763
483
25
77
3.3
2.2
DT13
57
30.25
0.53
227
107
70
12
26.2
2.6
DT14
58
30.25
0.52
230
109
70
13
24.4
2.5
DT15
178
100.00
0.56
707
310
40
31
6.5
1.9
DT16
63
50.00
0.79
251
52
40
10
24.5
2.0
kN
kN
DT1
59
45.50
DT2
59
30.25
DT3
59
DT4
59
DT5
DT6
*)
Calculated with the measured material properties and dimensions as given in table 1.
**)
The Stevin Laboratory values are taken from table 1.
103
5
Proposal for Design Rules
On request of the Eurocode 3 Project Team for prEN 1993-1-8 Design of Joints, based on the
Stevin Laboratory model, the following design rules were proposed by the authors.
Resistance to shear forces
5.1
In a column base the design shear resistance Fv.Rd may be derived as follows:
Fv.Rd = F f .Rd + nFvb.Rd
(31)
where:
Ff.Rd
is the design friction resistance between base plate and grout layer:
F f . Rd = C f .d ⋅ N c.Sd
Cf.d
(32)
is the coefficient of friction between base plate and grout layer. The following
values may be used:
Nc.Sd
•
for sand-cement mortar Cf,d = 0,20
(33a)
•
for special grout Cf,d = 0,30
(33b)
is the design value of the normal compressive force in the column. If the normal
force in the column is a tensile force Ff.Rd = 0.
Drafting note: Also, the preload in the anchor bolts contributes to the friction resistance.
However, because of its uncertainty (e.g. relaxation and interaction with the column
normal force), it was decided to neglect this action.
n
is the number of anchor bolts in the base plate
Fvb.Rd
is the smallest of F1.vb.Rd and F2.vb.Rd
F1.vb.Rd
is the bearing resistance for the anchor bolt - base plate
F2.vb.Rd
is the shear resistance of the anchor bolt
F 2.vb.Rd =
α b f ub As
γ Mb
As
is the tensile stress area of the bolt or of the anchor bolt
αb
is a coefficient depending on the yield strength fyb the anchor bolt:
α b = 0,44 − 0,0003 f yb
fyb
(34)
(35)
is the nominal yield strength the anchor bolt, where: 235 N/mm2 ≤ fyb ≤ 640
N/mm2
fub
is the nominal ultimate strength the anchor bolt, where: 400 N/mm2 ≤ fub ≤ 800
N/mm2
γ Mb
104
is the partial safety factor:
γ Mb = 1,25
(36)
Deformations
5.2
In a column base the design shear deformations may be derived as follows:
•
If N c.Sd ≤ F f .Rd the shear deformation δv = 0.
•
If N c.Sd > F f .Rd the shear deformation δv is the largest of δv1 and δv2.
δ v1 = Fv.Sd
δ v*
(37)
Fv*
⎧⎪
⎛
N c.Sd
Fv.Sd
− C fd ⎜1 −
⎜
⋅
⋅
⋅
n
f
A
n
f yb ⋅ As
⎪⎩
yb
s
⎝
δ v 2 = vr ⎨
⎞⎫⎪
⎟⎬
⎟⎪
⎠⎭
(38)
where
δ v* = vr
2 f yb
(39)
Ea
⎛δ*
⎞
Fv* = n ⋅ f yb ⋅ As ⎜⎜ v + C f .d ⎟⎟ − C f .d N c.Sd
⎝ vr
⎠
(40)
with
NC.Sd
is the design value of the normal force in the column (positive value if the normal
force is tensile and negative value if the normal force is compression)
Ea
is the elastic modulus of steel
vr
is the design value of the thickness of the grout layer:
vr = v + 0,5db
v
(41)
is the actual thickness of the grout layer.
Remark: The hole clearance may contribute considerably to the horizontal displacements.
The hole clearance is not included in the above equations. Displacements due to the hole
clearances may be prevented by measures to prevent the bolts moving in the holes, e.g. by
filling the hole clearances with a two component epoxy.
5.3
Prerequisites
In the above equations, it is a prerequisite that:
•
The grout layer is of adequate quality. See the applicable reference standard.
105
•
The design strength of the anchor – concrete connection is greater than the design
rupture strength of the anchor.
•
Other failure modes, like splitting of the concrete and pull out of the anchor, are
prevented by adequate design and execution of the anchor in the concrete block.
Reference is made to
-
EN 1992, Eurocode 2.
-
CEB, 1994. Fastenings to concrete and masonry structures, state of the art report.
Comité Euro-International du Béton. Thomas Telford Publishing, London, ISBN:
0 7277 1937 8.
-
CEB, 1996. Design of fastenings in concrete, Design Guide. Comité EuroInternational du Béton. Thomas Telford Publishing, London, ISBN: 0 7277 2558 0.
5.4
Application of the equations for the deformation
The equations in section 5.2 are somewhat simplified compared to those given in the
section 2, where the Stevin Laboratory model is explained. For the example calculation in
section 2.2 (test DT6), it follows:
•
For Fv.Sd = 94,0 kN: δv1 = 3,60 mm, δv2= 3,59 mm; the displacement δv is the largest of
δv1 and δv2; in this case, δv = δv1= δv2= 3,6 mm.
•
For Fv.Sd = 130,0 kN: δv1 = 4,97 mm, δv2= 7,0 mm; the displacement δv is the largest of
δv1 and δv2; in this case, δv = δv2= 7,0 mm.
These values are in agreement with those in section 2.2.
6
Conclusions
6.1
•
On the behaviour of column bases loaded in shear and tension
The shear strength of anchor bolts is considerably lower than the shear strength of
bolts in bolted connections between steel plates.
•
The ductility of the anchor bolts is an important factor for the strength. The lower
ductility of 8.8 grade bolts compared to 4.6 grade bolts is reflected in the lower
coefficient in the resistance function.
•
The influence of a tensile force Ft in the column can be neglected for the
determination of the shear resistance.
•
The shear resistance is almost independent of the thickness of the grout layer.
•
The deformations are greatly dependent on the thickness of the grout layer.
•
A "better" grout, e.g. "Pagel IV" gives lower deformations.
106
•
In the design, not only the shear resistance should be checked, but also the
deformations at serviceability and ultimate limit state.
•
6.2
•
Also other failure modes, like splitting of the concrete block, etc., should be checked.
On the models
The Stevin Laboratory model gives results that are consistent with test results. It also
gives rules to determine the deformation.
•
The CEB model gives very conservative results, especially when a large tensile force is
present and / or the thickness of the grout layer is large. The main reason is that the
CEB model does not take account of the positive influence of the grout layer. The CEB
model does not give rules to determine the deformation.
Acknowledgement
Within the framework of the European Project COST C1 (Semi-rigid behaviour of civil
engineering structural connections) and the Technical Committee 10 of ECCS (European
Convention for Constructional Steelwork) an ad-hoc working group prepared a
background document on design of column bases for Eurocode 3. Members of this group
are: D. Brown, SCI London; A.M. Gresnigt, TU Delft; J.P. Jaspart, University of Liège; Z.
Sokol, CTU in Prague; J.W.B. Stark, TU Delft; C.M. Steenhuis, TU Eindhoven; J.C. Taylor,
SCI London; F. Wald, CTU in Prague (convener of the group), K. Weynand, RTWH
Aachen.
107
References
CEB, 1994. Fastenings to concrete and masonry structures, state of the art report. Comité
Euro-International du Béton. Thomas Telford Publishing, London, ISBN: 0 7277 1937 8.
CEB, 1996. Design of fastenings in concrete, Design Guide. Comité Euro-International du
Béton. Thomas Telford Publishing, London, ISBN: 0 7277 2558 0.
COST, 1999. Column Bases in Steel Building Frames, COST C1- EU, Brussels, Luxembourg.
ECCS, 1994. European recommendations for bolted connections with injection bolts. ECCS
publication No. 79, Brussels.
EN 1993-1-8, 2006. Eurocode 3: Design of Steel Structures, Part 1.8: Design of joints, CEN,
Brussels.
NEN 6770, 1990. Staalconstructies TGB 1990, Basiseisen en basisrekenregels voor
overwegend statisch belaste constructies (TGB 1990 Steel Structures, Basic
requirements and basic rules for calculation of predominantly statically loaded
structures), NEN, Delft.
Stevin, 1989. Bouwman, L.P., Gresnigt A.M., Romeijn, A. Onderzoek naar de bevestiging
van stalen voetplaten aan funderingen van beton. (Research into the connection of steel
base plates to concrete foundations), TU-Delft Stevin Laboratory report 25.6.89.05/c6,
Delft.
Nakashima, Shigetoshi, (1998). Mechanical Characteristics of Exposed Portions of Anchor
Bolts in Steel Column Bases under Combined Tension and Shear. Journal of
Constructional Steel Research, 1998, 46:1-3, Paper No. 277.
108