Reactive Power Compensation Technologies:
State-of-the-Art Review
JUAN DIXON, SENIOR MEMBER, IEEE, LUIS MORÁN, FELLOW, IEEE,
JOSÉ RODRÍGUEZ, SENIOR MEMBER, IEEE, AND RICARDO DOMKE
Invited Paper
This paper presents an overview of the state of the art in reactive
power compensation technologies. The principles of operation, design characteristics and application examples of Var compensators
implemented with thyristors and self-commutated converters are
presented. Static Var generators are used to improve voltage regulation, stability, and power factor in ac transmission and distribution
systems. Examples obtained from relevant applications describing
the use of reactive power compensators implemented with new static
Var technologies are also described.
Keywords—Reactive power, static Var compensators (SVCs).
I. INTRODUCTION
Var compensation is defined as the management of
reactive power to improve the performance of ac power
systems. The concept of Var compensation embraces a wide
and diverse field of both system and customer problems,
especially related with power quality issues, since most
power quality problems can be attenuated or solved with
an adequate control of reactive power [1]. In general, the
problem of reactive power compensation is viewed from
two aspects: load compensation and voltage support. In load
compensation the objectives are to increase the value of
the system power factor, to balance the real power drawn
from the ac supply, to compensate voltage regulation, and to
eliminate current harmonic components produced by large
Manuscript received August 15, 2005; revised October 6, 2005. This work
was supported in part by Fondecyt (the Chilean Research Council) under
Project 1050067 and in part by the Universidad Federico Santa Maria.
J. Dixon is with the Electrical Engineering Department, Pontificia Universidad Católica de Chile, Santiago 690441, Chile (e-mail:
[email protected].
cl).
L. Morán and R. Domke are with the Electrical Engineering Department,
Universidad de Concepción, Concepción, Chile (e-mail:
[email protected]).
J. Rodríguez is with the Electronic Engineering Department, Universidad
Federico Sta. María, Valparaíso, Chile (e-mail:
[email protected]).
Digital Object Identifier 10.1109/JPROC.2005.859937
and fluctuating nonlinear industrial loads [2], [3]. Voltage
support is generally required to reduce voltage fluctuation
at a given terminal of a transmission line. Reactive power
compensation in transmission systems also improves the
stability of the ac system by increasing the maximum active
power that can be transmitted. It also helps to maintain a
substantially flat voltage profile at all levels of power transmission, it improves high-voltage dc (HVDC) conversion
terminal performance, increases transmission efficiency,
controls steady-state and temporary overvoltages [4], and
can avoid disastrous blackouts [5], [6].
Series and shunt Var compensation are used to modify
the natural electrical characteristics of ac power systems. Series compensation modifies the transmission or distribution
system parameters, while shunt compensation changes the
equivalent impedance of the load [1], [7]. In both cases, the
reactive power that flows through the system can be effectively controlled improving the performance of the overall
ac power system.
Traditionally, rotating synchronous condensers and fixed
or mechanically switched capacitors or inductors have
been used for reactive power compensation. However, in
recent years, static Var compensators (SVCs) employing
thyristor-switched capacitors (TSCs) and thyristor-controlled reactors (TCRs) to provide or absorb the required
reactive power have been developed [7]–[9]. Also, the use of
self-commutated pulsewidth modulation (PWM) converters
with an appropriate control scheme permits the implementation of static compensators capable of generating or
absorbing reactive current components with a time response
faster than the fundamental power network cycle [10]–[12].
Based on the use of reliable high-speed power electronics,
powerful analytical tools, advanced control and microcomputer technologies, flexible ac transmission systems
(FACTS) have been developed and represent a new concept
for the operation of power transmission systems [13], [14].
In these systems, the use of SVCs with fast response times
0018-9219/$20.00 © 2005 IEEE
2144
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
play an important role, allowing to increase the amount of
apparent power transfer through an existing line, close to its
thermal capacity, without compromising its stability limits.
These opportunities arise through the ability of special SVCs
to adjust the interrelated parameters that govern the operation of transmission systems, including shunt impedance,
current, voltage, phase angle and the damping of oscillations
[15].
This paper presents an overview of the state of the art
of static Var technologies. Static compensators implemented with thyristors and self-commutated converters
are described. Their principles of operation, compensation
characteristics and performance are presented and analyzed.
A comparison of different Var generator compensation characteristics, is also presented. New static compensators such
as unified power flow controllers (UPFCs) and dynamic
voltage restorers (DVRs), required to compensate modern
power distribution systems, are also presented and described
[28].
II. REACTIVE POWER COMPENSATION PRINCIPLES
In a linear circuit, the reactive power is defined as the
ac component of the instantaneous power, with a frequency
equal to 100/120 Hz in a 50- or 60-Hz system. The reactive
power generated by the ac power source is stored in a capacitor or a reactor during a quarter of a cycle, and in the next
quarter cycle is sent back to the power source. In other words,
the reactive power oscillates between the ac source and the
capacitor or reactor, and also between them, at a frequency
equals to two times the rated value (50 or 60 Hz). For this
reason it can be compensated using Var generators, avoiding
its circulation between the load (inductive or capacitive) and
the source, and therefore improving voltage stability of the
power system. Reactive power compensation can be implemented with Var generators connected in parallel or in series.
The principles of both shunt and series reactive power
compensation alternatives are described below.
Fig. 1. Principles of shunt compensation in a radial ac system. (a) Without
reactive compensation. (b) Shunt compensation with a current source.
the reactive current component from the source is reduced or
almost eliminated.
If the load needs leading compensation, then an inductor
would be required. Also, a current source or a voltage source
can be used for inductive shunt compensation. The main
advantage of using voltage- or current-source Var generators (instead of inductors or capacitors) is that the reactive
power generated is independent of the voltage at the point
of connection.
A. Shunt Compensation
B. Series Compensation
Fig. 1 shows the principles and theoretical effects of shunt
reactive power compensation in a basic ac system, which
comprises a source , a power line, and a typical inductive load. Fig. 1(a) shows the system without compensation
and its associated phasor diagram. In the phasor diagram,
the phase angle of the current has been related to the load
is in phase with
side, which means that the active current
the load voltage . Since the load is assumed inductive, it
requires reactive power for proper operation and hence, the
source must supply it, increasing the current from the generator and through power lines. If reactive power is supplied
near the load, the line current can be reduced or minimized,
reducing power losses and improving voltage regulation at
the load terminals. This can be done in three ways: 1) with
a capacitor; 2) with a voltage source; or 3) with a current
source. In Fig. 1(b), a current-source device is being used to
.
compensate the reactive component of the load current
As a result, the system voltage regulation is improved and
Var compensation can also be of the series type. Typical
series compensation systems use capacitors to decrease the
equivalent reactance of a power line at rated frequency. The
connection of a series capacitor generates reactive power
that, in a self-regulated manner, balances a fraction of the
line’s transfer reactance. The result is improved functionality
of the power transmission system through:
1) increased angular stability of the power corridor;
2) improved voltage stability of the corridor;
3) optimized power sharing between parallel circuits.
Like shunt compensation, series compensation may also
be implemented with current- or voltage-source devices, as
shown in Fig. 2. Fig. 2(a) shows the same power system of
Fig. 1(a), also with the reference angle in , and Fig. 2(b)
shows the results obtained with the series compensation
through a voltage source, which has been adjusted again
to have unity power factor operation at . However, the
compensation strategy is different when compared with
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2145
throughput fault current, even at a severe nearby fault. The
primary overvoltage protection typically involves nonlinear
metal–oxide varistors, a spark gap, and a fast bypass switch.
Secondary protection is achieved with ground mounted electronics acting on signals from optical current transducers in
the high-voltage circuit.
Independent of the source type or system configuration,
different requirements have to be taken into consideration
for a successful operation of Var generators. Some of these
requirements are simplicity, controllability, dynamics, cost,
reliability, and harmonic distortion. The following sections
describe different solutions used for Var generation with
their associated principles of operation and compensation
characteristics.
III. TRADITIONAL VAR GENERATORS
Fig. 2. Principles of series compensation. a) The same system of Fig. 1(a)
without compensation. b) Series compensation with a voltage source.
In general, Var generators are classified depending on the
technology used in their implementation and the way they
are connected to the power system (shunt or series). Rotating
and static generators were commonly used to compensate
reactive power. In the last decade, a large number of different static Var generators using power electronic technologies have been proposed and developed [7]. There are two
approaches to the realization of power electronics based Var
compensators: the one that employs thyristor-switched capacitors and reactors with tap-changing transformers, and the
other that uses self-commutated static converters. A brief description of the most commonly used shunt and series compensators is presented below.
A. Fixed or Mechanically Switched Capacitors
Fig. 3.
Series capacitor compensator and associated protection system.
has been
shunt compensation. In this case, voltage
added between the line and the load to change the angle
of , which is now the voltage at the load side. With the
appropriate magnitude adjustment of
, unity power
factor can again be reached at . As can be seen from the
generates a voltage with
phasor diagram of Fig. 2(b),
opposite direction to the voltage drop in the line inductance
because it lags the current .
As was already mentioned, series compensation with
capacitors is the most common strategy. Series capacitors
are installed in series with a transmission line as shown in
Fig. 3, which means that all the equipment must be installed
on a platform that is fully insulated for the system voltage
(both the terminals are at the line voltage). On this platform,
the main capacitor is located together with overvoltage
protection circuits. The overvoltage protection is a key
design factor as the capacitor bank has to withstand the
2146
Shunt capacitors were first employed for power factor
correction in 1914 [16]. The leading current drawn by the
shunt capacitors compensates the lagging current drawn
by the load. The selection of shunt capacitors depends on
many factors, the most important of which is the amount
of lagging reactive power taken by the load. In the case of
widely fluctuating loads, the reactive power also varies over
a wide range. Thus, a fixed capacitor bank may often lead to
either over-compensation or under-compensation. Variable
Var compensation is achieved using switched capacitors
[17]. Depending on the total Var requirement, capacitor
banks are switched into or switched out of the system. The
smoothness of control is solely dependent on the number
of capacitors switching units used. The switching is usually
accomplished using relays and circuit breakers. However,
these methods based on mechanical switches and relays
have the disadvantage of being sluggish and unreliable. Also
they generate high inrush currents, and require frequent
maintenance [16].
B. Synchronous Condensers
Synchronous condensers have played a major role in
voltage and reactive power control for more than 50 years.
Functionally, a synchronous condenser is simply a synchronous machine connected to the power system. After the
unit is synchronized, the field current is adjusted to either
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
if the thyristor is turned on at the instant when the capacitor
voltage and the network voltage have the same value. Static
compensators of the TSC type have the following properties:
stepwise control, average delay of one half a cycle (maximum one cycle), and no generation of harmonics, since current transient component can be attenuated effectively [16],
[17].
The current that flows through the capacitor at a given time
is defined by the following expression:
(1)
Fig. 4.
TSC configuration.
generate or absorb reactive power as required by the ac
system. The machine can provide continuous reactive power
control when used with the proper automatic exciter circuit.
Synchronous condensers have been used at both distribution
and transmission voltage levels to improve stability and
to maintain voltages within desired limits under varying
load conditions and contingency situations. However, synchronous condensers are rarely used today because they
require substantial foundations and a significant amount of
starting and protective equipment. They also contribute to
the short-circuit current, and they cannot be controlled fast
enough to compensate for rapid load changes. Moreover,
their losses are much higher than those associated with
static compensators, and the cost is much higher compared
with static compensators. Their advantage lies in their high
temporary overload capability [1].
C. Thyristorized Var Compensators
As in the case of the synchronous condenser, the aim of
achieving fine control over the entire Var range, has been fulfilled with the development of static compensators but with
the advantage of faster response times [6], [7]. SVCs consist of standard reactive power shunt elements (reactors and
capacitors) which are controlled to provide rapid and variable reactive power. They can be grouped into two basic categories, the TSC and the TCR.
1) TSCs: Fig. 4 shows the basic scheme of a static compensator of the TSC type. First introduced by ASEA in 1971
[16], the shunt capacitor bank is split up into appropriately
small steps, which are individually switched in and out using
bidirectional thyristor switches. Each single-phase branch
consists of two major parts, the capacitor and the thyristor
and
. In addition, there is a minor comswitches
ponent, the inductor , whose purpose is to limit the rate of
rise of the current through the thyristors and to prevent res).
onance with the network (normally 6% with respect to
The capacitor may be switched with a minimum of transients
where
and
are the compensator capacitive and inthe source maximum instantaneous
ductive reactance,
the voltage phase-shift angle at which the cavoltage,
the system resonant frequency
pacitor is connected, and
,
capacitor voltage at
.
This expression has been obtained assuming that the
system equivalent resistance is negligible as compared
with the system reactance. This assumption is valid in
high-voltage transmission lines. If the capacitor is connected
at the moment that the source voltage is maximum and
is equal to the source voltage peak value
the current transient component is zero.
Despite the attractive theoretical simplicity of the switched
capacitor scheme, its popularity has been hindered by a
number of practical disadvantages: the Var compensation
is not continuous, each capacitor bank requires a separate
thyristor switch and therefore the construction is not economical, the steady state voltage across the nonconducting
thyristor switch is twice the peak supply voltage, and the
thyristor must be rated for or protected by external means
against line voltage transients and fault currents.
An attractive solution to the disadvantages of using TSCs
is to replace one of the thyristor switches by a diode. In this
case, inrush currents are eliminated when thyristors are fired
at the right time, and a more continuous reactive power control can be achieved if the rated power of each capacitor bank
is selected following a binary combination, as described in
[13] and [18]. This configuration is shown in Fig. 5. In this
is used to prevent any inrush curfigure, the inductor
rent produced by a firing pulse out of time.
To connect each branch, a firing pulse is applied at the
thyristor gate, but only when the voltage supply reaches its
maximum negative value. In this way, a soft connection is
obtained (1). The current will increase starting from zero
without distortion, following a sinusoidal waveform, and
after the cycle is completed, the capacitor voltage will have
, and the thyristor automatically will block.
the voltage
In this form of operation, both connection and disconnection
of the branch will be soft, and without distortion. If the firing
are properly adjusted, neither
pulses and the voltage
harmonics nor inrush currents are generated, since two
important conditions are achieved: 1) dv/dt at
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2147
Fig. 5. Binary thyristor-diode-switched capacitor configuration.
Fig. 6. Experimental compensating phase current of the thyristor-diode
switched capacitor. (a) Current through B1. (b) Current through B2. (c) Current through B3. (d) Current through B4. (e) Total system compensating current.
Fig. 7. TCR configuration.
is zero and 2) anode-to-cathode thyristor voltage is equal
, is the source
to zero. Assuming that
the initial capacitor voltage, and
the
voltage,
thyristor anode-to-cathode voltage, the right connection of
the branch will be when
, that is
(2)
since
Fig. 8. Simulated voltage and current waveforms in a TCR for different
thyristor phase-shift angles, .
(3)
then
At
pacitor
when
.
, the thyristor is switched on, and the cabegins to discharge. At this point,
, and hence
for
will be
. The compensating capacitor current starting at
will be
(4)
Equation (4) shows that the current starts from zero as a
sinusoidal waveform without distortion and/or inrush component. If the above switching conditions are satisfied, the
inductor may be minimized or even eliminated.
2148
The experimental oscillograms of Fig. 6 shows how
the binary connection of many branches allows an almost
continuous compensating current variation. These experimental current waveforms were obtained in a 5-kVAr
laboratory prototype. The advantages of this topology are
that many compensation levels can be implemented with few
branches allowing continuous variations without distortion.
Moreover, the topology is simpler and more economical as
compared with TSCs. The main drawback is that it has a
time delay of one complete cycle compared with the half
cycle of TSCs.
2) TCR: Fig. 7 shows the scheme of a static compensator
of the TCR type. In most cases, the compensator also includes a fixed capacitor and a filter for low order harmonics,
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
Fig. 9. FC-TCR configuration. (a) Six-pulse topology. (b) Twelve-pulse topology.
which is not show in this figure. Each of the three phase
branches includes an inductor , and the thyristor switches
and
. Reactors may be both switched and phaseangle controlled [20]–[22].
When phase-angle control is used, a continuous range of
reactive power consumption is obtained. It results, however,
in the generation of odd harmonic current components during
the control process. Full conduction is achieved with a gating
angle of 90 . Partial conduction is obtained with gating angles between 90 and 180 , as shown in Fig. 8. By increasing
the thyristor gating angle, the fundamental component of the
current reactor is reduced. This is equivalent to increase the
inductance, reducing the reactive power absorbed by the reactor. However, it should be pointed out that the change in
the reactor current may only take place at discrete points of
time, which means that adjustments cannot be made more
frequently than once per half-cycle. Static compensators of
the TCR type are characterized by the ability to perform
continuous control, maximum delay of one half-cycle, and
practically no transients. The principal disadvantages of this
configuration are the generation of low-frequency harmonic
current components, and higher losses when working in the
inductive region (i.e., absorbing reactive power) [20].
The relation between the fundamental component of the
reactor current, and the phase-shift angle is given by (5)
(5)
In a single-phase unit, with balanced phase-shift angles,
only odd harmonic components are presented in the current
of the reactor. The amplitude of each harmonic component
is defined by (6)
(6)
In order to eliminate low-frequency current harmonics
(third, fifth, seventh), delta configurations (for zero sequence
Fig. 10.
Voltage-reactive power characteristic of a FC-TCR.
harmonics) and passive filters may be used, as shown in
Fig. 9(a). Twelve pulse configurations are also used as shown
in Fig. 9(b). In this case passive filters are not required, since
the fifth and seventh current harmonics are eliminated by the
phase-shift introduced by the transformer.
3) Var Compensation Characteristics: One of the main
characteristics of SVCs is that the amount of reactive power
interchanged with the system depends on the applied voltage,
as shown in Fig. 10. This figure displays the steady state Q-V
characteristics of a combination of fixed capacitor-TCR (FCTCR) compensator. This characteristic shows the amount of
reactive power generated or absorbed by the FC-TCR, as a
function of the applied voltage. At rated voltage, the FC-TCR
presents a linear characteristic, which is limited by the rated
power of the capacitor and reactor respectively. Beyond these
limits, the
characteristic is not linear [1], [7], which
is one of the principal disadvantages of this type of Var compensator.
4) Combined TSC and TCR: Irrespective of the reactive
power control range required, any static compensator can be
built up from one or both of the above mentioned schemes
(i.e., TSC and TCR), as shown in Fig. 11. In those cases
where the system with switched capacitors is used, the reactive power is divided into a suitable number of steps and
the variation will therefore take place stepwise. Continuous
control may be obtained with the addition of a TCR. If it is
required to absorb reactive power, the entire capacitor bank
is disconnected and the equalizing reactor becomes responsible for the absorption. By coordinating the control between
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2149
Fig. 13.
Fig. 11.
Power circuit topology of a TCSC.
Combined TSC and TCR configuration.
Fig. 14. A Var compensator topology implemented with a current-source
converter.
Fig. 12. Steady-state voltage-reactive power characteristic of a combined
TSC-TCR compensator.
the reactor and the capacitor steps, it is possible to obtain
fully stepless control. Static compensators of the combined
TSC and TCR type are characterized by a continuous control, practically no transients, low generation of harmonics
(because the controlled reactor rating is small compared to
the total reactive power), and flexibility in control and operation. An obvious disadvantage of the TSC-TCR as compared
with TCR and TSC type compensators is the higher cost. A
smaller TCR rating results in some savings, but these savings
are more than absorbed by the cost of the capacitor switches
and the more complex control system [16].
The V-Q characteristic of this compensator is shown in
Fig. 12.
To reduce transient phenomena and harmonics distortion,
and to improve the dynamics of the compensator, some
researchers have applied self-commutation to TSC and
TCR. Some examples of this can be found in [21] and [22].
However, best results have been obtained using self-commutated compensators based on conventional two-level and
three-level inverters. They are analyzed in Section IV.
5) Thyristor-Controlled Series Compensation: Fig. 13
shows a single line diagram of a thyristor-controlled series compensator (TCSC). The TCSC provides a proven
technology that addresses specific dynamic problems in
transmission systems. TCSCs are an excellent tool to
2150
Fig. 15.
A Var compensator topology implemented with a VSC.
introduce if increased damping is required when interconnecting large electrical systems. Additionally, they can
overcome the problem of subsynchronous resonance (SSR),
a phenomenon that involves an interaction between large
thermal generating units and series compensated transmission systems.
There are two bearing principles of the TCSC concept.
First, the TCSC provides electromechanical damping between large electrical systems by changing the reactance of
a specific interconnecting power line, i.e., the TCSC will
provide a variable capacitive reactance. Second, the TCSC
shall change its apparent impedance (as seen by the line current) for subsynchronous frequencies such that a prospective
SSR is avoided. Both these objectives are achieved with the
TCSC using control algorithms that operate concurrently.
The controls will function on the thyristor circuit (in parallel
to the main capacitor bank) such that controlled charges are
added to the main capacitor, making it a variable capacitor
at fundamental frequency but a “virtual inductor” at subsynchronous frequencies.
For power oscillation damping, the TCSC scheme introduces a component of modulation of the effective reactance
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
Fig. 16. Simulated current and voltage waveforms of a voltage-source self-commutated shunt Var compensator. (a) Compensator topology. (b) Simulated current and voltage waveforms for leading compensation (
). (c) Simulated current and voltage waveforms for lagging compensation (
).
V
V
>V
V
<
of the power transmission corridor. By suitable system control, this modulation of the reactance is made to counteract
the oscillations of the active power transfer, in order to damp
these out.
IV. SELF-COMMUTATED VAR COMPENSATORS
The application of self-commutated (also know as forcecommutated) converters as a means of compensating reactive power has demonstrated to be an effective solution. This
technology has been used to implement more sophisticated
compensator equipment such as static synchronous compensators (STATCOMs), UPFCs, and DVRs [15], [19].
A. Principles of Operation
With the remarkable progress of gate commutated
semiconductor devices, attention has been focused on
self-commutated Var compensators capable of generating
or absorbing reactive power without requiring large banks
of capacitors or reactors. Several approaches are possible
including current-source and voltage-source converters
(VSCs). The current-source approach shown in Fig. 14 uses
a reactor supplied with a regulated dc current, while the
Fig. 17. Simulated compensator output voltage waveform for different
modulation index (amplitude of the voltage fundamental component).
voltage-source inverter, displayed in Fig. 15, uses a capacitor
with a regulated dc voltage.
The principal advantages of self-commutated Var compensators are the significant reduction of size and the
potential reduction in cost achieved from the elimination of
a large number of passive components and lower relative
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2151
Fig. 18.
A shunt Var compensator implemented with a three-level NPC inverter.
capacity requirement for the semiconductor switches [19],
[23]. Because of their smaller size, self-commutated Var
compensators are well suited for applications where space
is a premium.
Self-commutated compensators are used to stabilize transmission systems, improve voltage regulation, correct power
factor, and also correct load imbalances [19], [23]. Moreover,
they can be used for the implementation of shunt and series
compensators. Fig. 16 shows a shunt Var compensator, implemented with a boost-type VSC. Neglecting the internal
power losses of the overall converter, the control of the reactive power is done by adjusting the amplitude of the funda, which can be
mental component of the output voltage
modified with the PWM pattern as shown in Fig. 17. When
is larger than the voltage
, the Var compenis
sator generates reactive power [Fig. 16(b)] and when
, the compensator absorbs reactive power
smaller than
[Fig. 16(c)]. Its principle of operation is similar to the synchronous machine. The compensation current can be leading
or lagging, depending of the relative amplitudes of
and
. The capacitor voltage
, connected to the dc
link of the converter, is kept constant and equal to a referwith a special feedback control loop, which
ence value
and
.
controls the phase-shift angle between
The amplitude of the compensator output voltage
can be controlled by changing the switching pattern modu2152
lation index (Fig. 17) or by changing the amplitude of the
. Faster time response is achieved by
converter dc voltage
changing the switching pattern modulation index instead of
. The converter dc voltage
is changed by adjusting the
small amount of active power absorbed by the converter and
defined by (7)
(7)
is the converter linked reactor, and is the phasewhere
and
.
shift angle between voltages
One of the major problems that must be solved to use selfcommutated converters in high-voltage systems is the limited capacity of the controlled semiconductors [insulated gate
bipolar transistors (IGBTs) and integrated gate commutated
thyristors (IGCTs)] available in the market. Actual semiconductors can handle a few thousands of amperes and 6–10-kV
reverse voltage blocking capabilities, which is clearly not
enough for high-voltage applications. This problem can be
overcome by using more sophisticated converters topologies,
as described below.
B. Multilevel Compensators
Multilevel converters are being investigated and some
topologies are used today as SVCs. The main advantages
of multilevel converters are less harmonic generation and
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
higher voltage capability because of serial connection of
bridges or semiconductors. The most popular arrangement today is the three-level neutral-point clamped (NPC)
topology.
1) Three-Level Compensators: Fig. 18 shows a shunt Var
compensator implemented with a three-level NPC converter.
Three-level converters [24] are becoming the standard
topology for medium voltage converter applications, such
as machine drives and active front-end rectifiers. The advantage of three-level converters is that they can reduce the
generated harmonic content, since they produce a voltage
waveform with more levels than the conventional two-level
topology. Another advantage is that they can reduce the
semiconductor’s voltage rating and the associated switching
frequency. Three-level converters consist of 12 self-commutated semiconductors such as IGBTs or IGCTs, each of them
shunted by a reverse parallel connected power diode, and six
diode branches connected between the midpoint of the dc
link bus and the midpoint of each pair of switches as shown
in Fig. 18. By connecting the dc source sequentially to the
output terminals, the converter can produce a set of PWM
signals in which the frequency, amplitude, and phase of the
ac voltage can be modified with adequate control signals.
2) Multilevel Converters With Carriers Shifted: Another
exciting technology that has been successfully proven uses
basic “H” bridges as shown in Fig. 19, connected to line
through power transformers. These transformers are connected in parallel at the converter side, and in series at the line
side [25]. The system uses sinusoidal pulsewidth modulation
(SPWM) with triangular carriers shifted and depending on
the number of converters connected in the chain of bridges,
the voltage waveform becomes more and more sinusoidal.
Fig. 19(a) shows one phase of this topology implemented
with eight “H” bridges, and Fig. 19(b) shows the voltage
waveforms obtained as a function of number of “H” bridges.
An interesting result with this converter is that the ac
voltages become modulated by pulsewidth and by amplitude
(PWM and AM). This is because when the pulse modulation
changes, the steps of the amplitude also changes. The maximum number of steps of the resultant voltage is equal to
two times the number of converters plus the zero level. Then
four bridges will result in a nine-level converter per phase.
Fig. 20 shows the AM operation. When the voltage decreases, some steps disappear, and then the amplitude modulation becomes a discrete function.
3) Optimized Multilevel Converter: The number of levels
can increase rapidly with few converters when voltage scalation is applied. In a similar way of converter in Fig. 19(a),
the topology of Fig. 21(a) has a common dc link with voltage
isolation through output transformers, connected in series
at the line side. However, the voltages at the line side are
scaled in power of three. By using this strategy, the number
of voltage steps is maximized and few converters are required to obtain almost sinusoidal voltage waveforms. In the
example of Fig. 21, amplitude modulation with 81 levels
of voltage is obtained using only four “H” converters per
phase (four-stage inverter). In this way, Var compensators
with “harmonic-free” characteristics can be implemented.
Fig. 19. (a) Multilevel converter with eight “H” bridges and triangular carriers shifted (b) Voltage quality as a function of number of bridges.
Fig. 20.
Amplitude modulation in topology of Fig. 19(a).
It is important to remark that the bridge with the higher
voltage is being commutated at the line frequency, which
is a major advantage of this topology for high-power applications. Another interesting characteristic of this converter,
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2153
tion requires that the semiconductor must be able to block
high voltages in the kV range. High-voltage IGBTs required
to apply self-commutated converters in SVC reach now the
level of 6.5 kV, allowing for the construction of circuits with
a power of several MW. Also IGCTs are reaching now the
level of 6 kV. Perhaps the most important development in
semiconductors for SVC applications is the light-triggered
thyristor (LTT). This device is the most important for ultrahigh-power applications. Recently, LTT devices have been
developed with a capability of up to 13.5 kV and a current
of up to 6 kA. These new devices reduce the number of elements in series and in parallel, reducing consequently the
number of gate and protection circuits. With these elements,
it is possible to reduce cost and increase reactive power in
SVC installations of up to several hundreds of MVARs [27].
D. Comparison Between Thyristorized and
Self-Commutated Compensators
Fig. 21. (a) Four-stage, 81-level Var compensator, using “H” bridges
scaled in power of three. (b) Converter output using amplitude modulation.
compared with the multilevel strategy with carriers shifted,
is that only four “H” bridges per phase are required to get 81
levels of voltage. In the previous multilevel converter with
carriers shifted, 40 “H” bridges instead of four are required.
For high-power applications, probably a less complicated
three-stage (three “H” bridges per phase) is enough. In this
case, 27 levels or steps of voltage are obtained, which will
provide good enough voltage and current waveforms for
high-quality operation [26].
C. Semiconductor Devices Used for Self-Commutated Var
Compensators
Three are the most relevant devices for applications in
SVC: thyristors, IGBTs, and IGCTs. This field of applica2154
As compared with thyristor-controlled capacitor and reactor banks, self-commutated Var compensators have the following advantages.
1) They can provide both leading and lagging reactive
power, thus enabling a considerable saving in capacitors and reactors. This in turn reduces the possibility of
resonances at some critical operating conditions.
2) Since the time response of self-commutated converter
can be faster than the fundamental power network cycle,
reactive power can be controlled continuously and precisely.
3) High frequency modulation of self-commutated converter results in a low harmonic content of the supply
current, thus reducing the size of filter components.
4) They do not generate inrush current.
5) The dynamic performance under voltage variations and
transients is improved.
6) Self-commutated Var compensators are capable of generating 1 p.u. reactive current even when the line voltages are very low. This ability to support the power
system is better than that obtained with thyristor-controlled Var compensators because the current in shunt
capacitors and reactors is proportional to the voltage.
7) Self-commutated compensators with appropriate control can also act as active line harmonic filters, DVRs,
or UPFCs.
Table 1 summarizes the comparative merits of the main
types of Var compensators. The significant advantages of
self-commutated compensators make them an interesting alternative to improve compensation characteristics and also to
increase the performance of ac power systems.
Fig. 22 shows the voltage/current characteristic of a
self-commutated Var compensator compared with that of
thyristor-controlled SVC. This figure illustrates that the
self-commutated compensator offers better voltage support
and improved transient stability margin by providing more
reactive power at lower voltages. Because no large capacitors and reactors are used to generate reactive power, the
self-commutated compensator provides faster time response
and better stability to variations in system impedances.
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
Table 1
Comparison of Basic Types of Compensators
V. NEW VAR COMPENSATOR’S TECHNOLOGY
Based on power electronics converters and digital control
schemes, reactive power compensators implemented with
self-commutated converters have been developed to compensate not only reactive power, but also voltage regulation,
flicker, harmonics, real and reactive power, transmission line
impedance, and phase-shift angle. It is important to note,
that even though the final effect is to improve power system
performance, the control variable in all cases is basically
the reactive power. Using self-commutated converters, the
following high-performance power system controllers have
been implemented: the STATCOM, the static synchronous
series compensator (SSSC), the DVR, the UPFC, the interline power flow controller (IPFC), and the superconducting
magnetic energy storage (SMES). The principles of operation and power circuit topology of each one are described
below.
Fig. 22. Voltage–current characteristics of shunt Var compensators. (a)
Compensator implemented with self-commutated converter (STATCOM).
(b) Compensator implemented with back-to-back thyristors.
A. STATCOM
The STATCOM is based on a solid-state voltage source,
implemented with an inverter and connected in parallel to the
power system through a coupling reactor, in analogy with a
synchronous machine, generating balanced set of three sinusoidal voltages at the fundamental frequency, with controllable amplitude and phase-shift angle. This equipment,
however, has no inertia and no overload capability. Examples of these topologies are Figs. 16, 18 and 19 [19], [28].
Fig. 23.
SSSC.
B. SSSC
A VSC can also be used as a series compensator as shown
in Fig. 23. The SSSC injects a voltage in series to the line,
90 phase-shifted with the load current, operating as a controllable series capacitor. The basic difference, as compared
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2155
Fig. 24. DVR.
with the series capacitor, is that the voltage injected by an
SSSC is not related to the line current and can be independently controlled. [28].
C. DVR
A DVR, shown in Fig. 24, is a device connected in series
with the power system and is used to keep the load voltage
constant, independently of the source voltage fluctuations
[29]. When voltage sags or swells are present at the load
terminals, the DVR responds by injecting three ac voltages
in series with the incoming three-phase network voltages,
compensating for the difference between faulted and prefault voltages. Each phase of the injected voltages can be
controlled separately (i.e., their magnitude and angle). Active and reactive power required for generating these voltages are supplied by the VSC fed from a dc link, as shown
in Fig. 24 [28]–[30]. In order to be able to mitigate voltage
sag, the DVR must present a fast control response. The key
components of the DVR are:
• switchgear;
• booster transformer;
• harmonic filter;
• IGCT VSC;
• dc charging unit;
• control and protection system;
• energy source, that is, a storage capacitor bank.
When power supply conditions remain normal, the DVR
can operate in low-loss standby mode, with the converter side
of the booster transformer shorted. Since no VSC modulation
takes place, the DVR produces only conduction losses. Use
of IGCT technology minimizes these losses.
SSSCs and DVRs can be integrated to get a system capable
of controlling the power flow of a transmission line during
steady state conditions and providing dynamic voltage compensation and short-circuit current limitation during system
disturbances [30].
D. UPFC
The UPFC, shown in Fig. 25, consists of two switching
converters operated from a common dc link provided by a
2156
dc storage capacitor. One is connected in series with the
line, and the other in parallel [28], [32]. This arrangement
functions as an ideal ac to ac power converter in which
the real power can freely flow in either direction between
the ac terminals of the two inverters and each inverter
can independently generate (or absorb) reactive power at
its own ac output terminal. The series converter of the
UPFC injects via series transformer, an ac voltage with
controllable magnitude and phase angle in series with the
transmission line. The shunt converter supplies or absorbs
the real power demanded by the series converter through the
common dc link. The inverter connected in series provides
the main function of the UPFC by injecting an ac voltage
with controllable magnitude
and
phase angle
, at the power frequency, in
series with the line via a transformer. The transmission line
current flows through the series voltage source, resulting
in real and reactive power exchange between it and the ac
system. The real power exchanged at the ac terminal that
is the terminal of the coupling transformer is converted by
the inverter into dc power, which appears at the dc link
as positive or negative real power demand. The reactive
power exchanged at the ac terminal is generated internally
by the inverter.
The basic function of the inverter connected in parallel (inverter 1) is to supply or absorb the real power demanded by
the inverter connected in series to the ac system (inverter 2),
at the common dc link. Inverter 1 can also generate or absorb controllable reactive power, if it is desired, and thereby
it can provide independent shunt reactive compensation for
the line. It is important to note that whereas there is a closed
“direct” path for the real power negotiated by the action of series voltage injection through inverter 1 and back to the line,
the corresponding reactive power exchanged is supplied or
absorbed locally by inverter 2, and therefore it does not flow
through the line. Thus, inverter 1 can be operated at a unity
power factor or be controlled to have a reactive power exchange with the line independently of the reactive power exchanged by inverter 2. This means that there is no continuous
reactive power flow through the UPFC.
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
Fig. 25.
UPFC power circuit topology.
Fig. 26.
IPFC power circuit topology.
E. IPFC
An IPFC, shown in Fig. 26, consists of two series VSCs
whose dc capacitors are coupled, allowing active power to
circulate between different power lines [33]. When operating
below its rated capacity, the IPFC is in regulation mode, allowing the regulation of the P and Q flows on one line, and the
P flow on the other line. In addition, the net active power generation by the two coupled VSCs is zero, neglecting power
losses.
F. SMES
An SMES system, shown in Fig. 27, is a device for storing
and instantaneously discharging large quantities of power
[34], [35]. It stores energy in the magnetic field created by
the flow of dc current in a coil of superconducting material
that has been cryogenically cooled. These systems have been
in use for several years to improve industrial power quality
and to provide a premium-quality service for individual
customers vulnerable to voltage fluctuations. The SMES
recharges within minutes and can repeat the charge/discharge sequence thousands of times without any degradation
of the magnet. Recharge time can be accelerated to meet
specific requirements, depending on system capacity. It is
claimed that SMES is 97%–98% efficient and it is much
better at providing reactive power on demand. Fig. 28 shows
another SMES topology using three-level converters.
The first commercial application of SMES was in 1981
[36] along the 500-kV Pacific Intertie, which interconnects
California and the Northwest. The device’s purpose was to
demonstrate the feasibility of SMES to improve transmission
capacity by damping interarea modal oscillations. Since that
time, many studies have been performed and prototypes developed for installing SMES to enhance transmission line capacity and performance. A major cost driver for SMES is the
amount of stored energy. Previous studies have shown that
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2157
Fig. 27.
SMES implemented with a thyristor converter.
Fig. 29.
ST.
ings of the transformer. This connection allows for independent control of voltage magnitude and phase shift in each one
of the three phases.
Fig. 28.
SMES implemented with a three-level converter.
SMES can substantially increase transmission line capacity
when utilities apply relatively small amounts of stored energy and a large power rating (greater than 50 MW).
Another interesting application of SMES for frequency
stabilization is in combination with an SSSC [37].
G. Var Generation Using Coupling Transformers
The power industry is in constant search for the most economical way to transfer bulk power along a desired path. This
can only be achieved through the independent control of active and reactive power flow in a transmission line. Traditional solutions, such as shunt or series inductor/capacitors
and phase angle regulators, affect both the active and the reactive power flow in the transmission line simultaneously.
With the use of a UPFC, which is based on a VSC, the active and the reactive power flow in the line can also independently be regulated. However, a new concept using proven
transformer topologies is being investigated: the SEN transformer (ST) [38].
The ST, which is shown in Fig. 29, is a new family of controlled power flow transformers that meets the new requirements of independent active and reactive power flow control
in a transmission line. Using state-of-the-art power flow control techniques, the ST redirects the active and reactive power
from an overloaded line and offers effective power flow management. The main advantage of ST, compared with UPFC
is its low cost, but the drawback of this alternative is its low
dynamic response.
in Fig. 29, is a
The series compensation, show as
series connection of the three phases of the secondary wind2158
VI. VAR COMPENSATOR’S APPLICATIONS
The implementation of high-performance reactive power
compensators enable power grid owners to increase existing
transmission network capacity while maintaining or improving the operating margins necessary for grid stability.
As a result, more power can reach consumers with a minimum impact on the environment, after substantially shorter
project implementation times, and at lower investment
costs—all compared to the alternative of building new transmission lines or power generation facilities. Some of the
examples of high-performance reactive power controllers
that have been installed and are operating in power systems
are described below. Some of these projects have been
sponsored by the Electric Power Research Institute (EPRI),
based on a research program implemented to develop and
promote FACTS.
1) Series Compensation in a 400-kV Transmission System
in Sweden [24]: The 420-kV transmission system between
northern and central Sweden comprises eight lines with eight
series capacitors, having a total rating of 4800 MVAr. The
degree of compensation for the individual series capacitor
banks has been selected in such a way that the sharing of active load (real power) between the individual 420-kV lines,
which are of different designs, and the parallel connected
245-kV network became most favorable. In the optimum
point, minimum losses for the total network are obtained.
The reduction in losses, compared to the uncompensated
case, has alone paid for the series capacitor investment in
a few years. Another benefit of the series capacitors in the
Swedish 420-kV network is the ability to supply reactive
power and support the voltage during and after a large
disturbance. Fig. 3 showed a typical compensated line with
series capacitors.
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
Fig. 30.
SVC at the Forbes substation.
The selected degree of compensation is between 30% and
70% for the individual banks. With this compensation, stable
transmission of more than 7000 MW on eight parallel lines is
achieved. Without series compensation, five additional lines
would have been needed to transmit the same amount of
power. This, of course, would have been impermissible, not
only from an investment point of view, but also with respect
to the environmental impact, right of way problems, etc. The
operating experience has been very good. The overall failure
rate of capacitor units has been less than 0.1% per year. Other
faults have also been insignificant and caused no interruption
of service. A simple and reliable design of the protective and
supervising system has contributed to this.
2)
500-kV Winnipeg–Minnesota Interconnection
(Canada–USA) [24]: Northern States Power Co. (NSP)
of Minnesota is operating an SVC in its 500-kV power
transmission network between Winnipeg, MB, Canada, and
Minnesota. This device is located at Forbes substation in
Minnesota and is shown in Fig. 30. The purpose is to increase
the power interchange capability on existing transmission
lines. This solution was chosen instead of building a new line
as it was found superior with respect to increased advantage
utilization as well as reduced environmental impact. With
the SVC in operation, the power transmission capability was
increased in about 200 MW.
The system has a dynamic range of 450 MVAr inductive to
1000 MVAr capacitive at 500 kV, making it one of the largest
of its kind in the world. It consists of an SVC and two 500-kV,
300-MVAr mechanically switched capacitor banks (MSCs).
The large inductive capability of the SVC is required to control the overvoltage during loss of power from the incoming
HVDC at the northern end of the 500-kV line.
The SVC consists of two TSRs and three TSCs. Additionally, the SVC has been designed to withstand brief ( 200
ms) overvoltages up to 150% of rated voltage.
Without the SVC, power transmission capacity of the NSP
network would be severely limited, either due to excessive
voltage fluctuations following certain fault situations in the
underlying 345-kV system, or to severe overvoltages at loss
of feeding power from HVDC lines coming from Manitoba.
Fig. 31.
SVC at the Auas substation.
3) Namibia’s Long Transmission Lines Give Rise to Unusual Resonance; A New SVC has Solved the Problem [40]:
Namibia is located in southwestern Africa, between Angola,
Botswana, South Africa, and the Atlantic Ocean. While
construction of the new 400-kV line has brought reliable
power to Namibia, it was not without troubles. The line’s
length of 890 km, for instance, aggravated certain problems,
mainly voltage instability and near 50-Hz resonance, which
already existed in the NamPower system. To solve the
problem, several solutions were considered as an answer to
the resonance problem, including fixed and switched reactors, before deciding to install a FACTS device in the Auas
substation. Finally, preference was given to conventional,
proven SVC technology, which is shown in Fig. 31, provided
by three TCRs, a fourth, continuously energized TCR, and
two identical double-tuned filters, each rated at 40 MVAr.
The filters take care of harmonics and supply capacitive
reactive power during steady-state operation.
The SVC has a dynamic range of 330 MVAr (250 MVAr
inductive to 80 MVAr capacitive) and is installed primarily
to control the system voltage. High availability is essential
for the SVC system. If, for any reason, it should have to be
taken out of service, the 400-kV transmission system could
not be operated without risking dangerous overvoltages. As
a result, an availability figure of 99.7% was specified, and
this strongly influenced the design, quality, functionality, and
layout of its components and subsystems as well as of the
SVC scheme as a whole.
The required capacitive MVAr is provided by two
40-MVAr filter banks. Each filter is double-tuned to the
third/fifth harmonics and connected in an ungrounded configuration. The double-tuned design was chosen to ensure
sufficient filtering even in the case of one filter becoming
defective.
4) Channel Tunnel Rail Link [41]: Today, it is possible to
travel between London, U.K., and Paris, France, in just over
two hours, at a maximum speed of 300 km/h. The railway
power system is designed for power loads in the range of
10 MW. The traction feeding system is a modern 50-Hz,
2–25-kV supply incorporating an autotransformer scheme to
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2159
Fig. 32.
Var compensation system for the channel tunnel.
keep the voltage drop along the traction lines low. Power
step-down from the grid is direct, via transformers connected
between two phases. A major feature of this power system,
shown in Fig. 32, is the SVC support. The primary purpose
of Var is to balance the unsymmetrical load and to support
the railway voltage in the case of a feeder station trip—when
two sections have to be fed from one station. The second purpose of the SVCs is to ensure a low tariff for the active power
by maintaining unity power factor during normal operation.
Thirdly, the SVCs alleviate harmonic pollution by filtering
the harmonics from the traction load.
Harmonic compensation is important because strict limits
apply to the traction system’s contribution to the harmonic
level at the supergrid connection points. The SVCs for
voltage support only are connected on the traction side
of the interconnecting power transformers. The supergrid
transformers for the traction supply have two series-connected medium-voltage windings, each with its midpoint
grounded. This results in two voltages, 180 apart, between
the winding terminals and ground. The SVCs are connected
across these windings; consequently, there are identical
single-phase SVCs connected feeder to ground and catenary
to ground. The traction load of up to 120 MW is connected
between two phases. Without compensation, this would
result in an approximately 2% negative phase sequence
voltage. To counteract the unbalanced load, a load balancer
(an asymmetrically controlled SVC) has been installed in
the Sellindge substation. This has a three-phase connection
to the grid. The load balancer transfers active power between
the phases in order to create a balanced load (as seen by the
supergrid).
5) Static Compensator (STATCOM) “Voltage Controller” 100-MVAr STATCOM at Sullivan Substation
(TVA) in Northeastern Tennessee [42]: The Sullivan substation is supplied by a 500-kV bulk power network and by four
161-kV lines that are interconnected through a 1200-MVA
transformer bank. Seven distributors and one large industrial
customer are served from this substation. The STATCOM,
shown in Fig. 33, is implemented with a 48 pulse, two-level
2160
voltage-source inverter that combines 8 six pulse three-phase
inverter bridges, each with a nominal rating of 12.5 MVA.
The system also comprises a single step-down transformer
having a wye and delta secondary to couple the inverter to
the 161-kV transmission line and a central control system
with operator interface. The STATCOM system is housed
in one building that is a standard commercial design with
metal walls and roof and measured 27.4 15.2 m.
The STATCOM regulates the 161-kV bus voltage during
daily load increases to minimize the activation of the tap
changing mechanism on the transformer bank, which interconnects the two power systems. The use of this Var compensator to regulate the bus voltage has resulted in the reduction
of the use tap changer from about 250 times per month to
2–5 times per month. Tap changing mechanisms are prone
to failure, and the estimated cost of each failure is about $1
million. Without the STATCOM, the transmission company
would be compelled either to install a second transformer
bank or to construct a fifth 161-kV line into the area; both
are costly alternatives.
6) UPFC “All Transmission Parameters Controller”:
160-MVA Shunt and 160-MVA Series at Inez Substation
(AEP), Northeastern Virginia [42]: The Inez load area has
a power demand of approximately 2000 MW and is served
by long and heavily loaded 138-kV transmission lines. This
means that, during normal power delivery, there is a very
small voltage stability margin for system contingencies.
Single-contingency outages in the area will adversely affect
the underlying 138-kV system and, in certain cases, a second
contingency would be intolerable, resulting in a wide-area
blackout. A reliable power supply to the Inez area requires
effective voltage support and added real power supply facilities. System studies have identified a reinforcement plan
that includes, among other things, the following system
upgrades:
1) construction of a new double-circuit high-capacity
138-kV transmission line from Big Sandy to Inez substation;
2) installation of FACTS controller to provide dynamic
voltage support at the Inez substation and to ensure full
utilization of the new high-capacity transmission line.
The UPFC satisfies all these needs, providing independent
dynamic control of transmission voltage as well as real and
reactive power flow. The UPFC installation (see Fig. 34)
comprises two identical three-phase 48-pulse, 160-MVA
voltage-source inverters coupled to two sets of dc capacitor
banks. The two inverters are interfaced with the ac system
via two transformers, a set of magnetically coupled windings
configured to construct a 48-pulse sinusoidal waveshape.
With this arrangement, the following operation modes are
possible. Inverter 1 (connected in parallel) can operate as
a STATCOM, with either one of the two main shunt transformers, while inverter 2 (connected in series) operates as an
SSSC. Alternatively, inverter 2 can be connected to the spare
shunt transformer and operates as an additional STATCOM.
With the latter configuration, a formidable shunt reactive
capability of 320 MVA would be available, necessary for
voltage support at some transmission contingencies in the
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
Fig. 33.
100-MVAr STATCOM at Sullivan substation.
Fig. 34.
Inverter pole assembly of UPFC at Inez substation.
Inez area. The expected benefits of the installed UPFC are
the following.
1) Dynamic voltage support at the Inez substation to prevent voltage collapse under double transmission contingency conditions.
2) Flexible and independent control of real and reactive power flow on the new high-capacity (950-MVA
thermal rating) of the 138-kV transmission line.
3) Reduction of real power losses by more than 24 MW,
which is equivalent to a reduction of CO emissions by
about 85 000 tons per year.
4) More than 100 MW increase in the power transfer and
excellent voltage support at the Inez bus.
7) Convertible Static Compensator (CSC) in the New York
345-kV Transmission System [43]: The CSC, a versatile and
reconfigurable device based on FACTS technology, was designed, developed, tested, and commissioned in the New York
345-kV transmission system. The CSC, shown in Fig. 35,
consists of two 100-MVA VSCs which can be reconfigured
and operated as either a STATCOM, an SSSC, a UPFC, or
an IPFC. The CSC installation at the New York Power Authority’s (NYPA’s) Marcy 345-kV substation consists of a
200-MVA shunt transformer with two identical secondary
windings, and two 100-MVA series coupling transformers
for series devices in two 345-kV lines. The CSC provides
voltage control on the 345-kV Marcy bus, improved power
flow transfers, and superior power flow control on the two
345-kV lines leaving the Marcy substation: the Marcy–New
Scotland line and Marcy–Coopers Corner line.
Each voltage-source inverter of Fig. 33 has 12 three-level
NPC poles connected to a common dc bus. Inverter pole
outputs are connected to an intermediate transformer, which
synthesize the three-phase near-sinusoidal 48-pulse voltage
waveform that is coupled into the transmission system.
VII. CONCLUSION
An overview of the technological development of Var generators and compensators has been presented. Starting from
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2161
Fig. 35.
One-line diagram of 2
2 100-MVA CSC.
the principles of Var compensation, classical solutions using
phase-controlled semiconductors have been reviewed. The
introduction of self-commutated topologies based on IGBTs
and IGCTs semiconductors produced a dramatic improvement in the performance of Var compensators: they have a
faster dynamic behavior and they can control more variables.
The introduction of new self-commutated topologies at even
higher voltage levels will increase the impact of Var compensation in future applications.
Some relevant examples of projects have been described,
where it can be observed that modern Var compensators improve power systems performance, helping to increase reliability and the quality of power delivered to the customers.
These examples show that Var compensators will be used on
a much wider scale in the future as grid performance and
reliability becomes an even more important factor. Having
better grid controllability will allow utilities to reduce investment in the transmission lines themselves. The combination
of modern control with real-time information and information technologies will move them very close to their physical
limits. Besides, the development of faster and more powerful
semiconductor valves will increase the applicability of Var
generators to higher limits.
2162
REFERENCES
[1] T. J. Miller, Reactive Power Control in Electric Systems. New
York: Wiley, 1982.
[2] E. Wanner, R. Mathys, and M. Hausler, “Compensation systems
for industry,” Brown Boveri Rev., vol. 70, pp. 330–340, Sep./Oct.
1983.
[3] G. Bonnard, “The problems posed by electrical power supply to
industrial installations,” Proc. IEE Part B, vol. 132, pp. 335–340,
Nov. 1985.
[4] A. Hammad and B. Roesle, “New roles for static Var compensators in transmission systems,” Brown Boveri Rev., vol. 73, pp.
314–320, Jun. 1986.
[5] N. Grudinin and I. Roytelman, “Heading off emergencies in large
electric grids,” IEEE Spectr., vol. 34, no. 4, pp. 43–47, Apr. 1997.
[6] C. W. Taylor, “Improving grid behavior,” IEEE Spectr., vol. 36,
no. 6, pp. 40–45, Jun. 1999.
[7] Canadian Electrical Association, “Static compensators for reactive
power control,” 1984.
[8] L. Gyugyi, “Reactive power generation and control by thyristor
circuits,” IEEE Trans. Ind. Appl., vol. IA-15, no. 5, pp. 521–532,
Sep./Oct. 1979.
[9] L. Gyugyi, R. Otto, and T. Putman, “Principles and applications
of static, thyristor-controlled shunt compensators,” IEEE Trans.
Power App. Syst., vol. PAS-97, no. 5, pp. 1935–1945, Oct. 1980.
[10] Y. Sumi, Y. Harumoto, T. Hasegawa, M. Yano, K. Ikeda, and
T. Mansura, “New static Var control using force-commutated inverters,” IEEE Trans. Power App. Syst., vol. PAS-100, no. 9, pp.
4216–4223, Sep. 1981.
[11] C. Edwards, K. Mattern, E. Stacey, P. Nannery, and J. Gubernick, “Advanced static Var generator employing GTO thyristors,”
IEEE Trans. Power Del., vol. 3, no. 4, pp. 1622–1627, Oct. 1988.
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
[12] L. Walker, “Force-commutated reactive power compensator,”
IEEE Trans. Ind. Appl., vol. IA-22, no. 6, pp. 1091–1104,
Nov./Dec. 1986.
[13] K. E. Stahlkopf and M. R. Wilhelm, “Tighter controls for busier
systems,” IEEE Spectr., vol. 34, no. 4, pp. 48–52, Apr. 1997.
[14] R. Grünbaum, Å. Petersson, and B. Thorvaldsson, “FACTS, improving the performance of electrical grids,” ABB Rev., pp. 11–18,
Mar. 2003.
[15] N. Hingorani and L. Gyugyi, Understanding FACTS, Concepts
and Technology of Flexible ac Transmission Systems. New York:
IEEE Press, 2000.
[16] H. Frank and S. Ivner, “Thyristor-controlled shunt compensation
in power networks,” ASEA J., vol. 54, pp. 121–127, 1981.
[17] H. Frank and B. Landstrom, “Power factor correction with
thyristor-controlled capacitors,” ASEA J., vol. 45, no. 6, pp.
180–184, 1971.
[18] J. W. Dixon, Y. del Valle, M. Orchard, M. Ortúzar, L. Morán,
and C. Maffrand, “A full compensating system for general loads,
based on a combination of thyristor binary compensator, and a
PWM-IGBT active power filter,” IEEE Trans. Ind. Electron., vol.
50, no. 5, pp. 982–989, Oct. 2003.
[19] L. Morán, P. Ziogas, and G. Joos, “Analysis and design of a synchronous solid-state Var compensator,” IEEE Trans. Ind. Appl., vol.
IA-25, no. 4, pp. 598–608, Jul./Aug. 1989.
[20] S. Torseng, “Shunt-connected reactors and capacitors controlled
by thyristors,” IEE Proc. Part C, vol. 128, no. 6, pp. 366–373, Nov.
1981.
[21] A. K. Chakravorti and A. E. Emanuel, “A current regulated
switched capacitor static volt ampere reactive compensator,” IEEE
Trans. Ind. Appl., vol. 30, no. 4, pp. 986–997, Jul./Aug. 1994.
[22] H. Jin, G. Goós, and L. Lopes, “An efficient switched-reactorbased static var compensator,” IEEE Trans. Ind. Appl., vol. 30, no.
4, pp. 997–1005, Jul./Aug. 1994.
[23] J. W. Dixon, J. García, and L. Morán, “Control system for a threephase active power filter which simultaneously compensates power
factor and unbalanced loads,” IEEE Trans. Ind. Electron., vol. 42,
no. 6, pp. 636–641, Dec. 1995.
[24] R. Grünbaum, B. Halvarsson, and A. Wilk-wilczynski, “FACTS
and HVDC light for power system interconnections,” presented at
the Power Delivery Conf., Madrid, Spain, 1999.
[25] O. Gaupp, P. Zanini, P. Daehler, E. Baerlocher, R. Boeck, and J.
Werninger, “Bremen’s 100-MW static frequency link,” ABB Rev.,
vol. M420, no. 9, pp. 4–17, Oct. 1996.
[26] J. Dixon and L. Morán, “A clean four-quadrant sinusoidal power
rectifier, using multistage converters for subway applications,”
IEEE Trans. Ind. Electron., vol. 52, no. 3, pp. 653–661, Jun. 2005.
[27] L. Lorenz, “Power semiconductors: state of the art and future developments,” in Int. Power Electronics Conf., IPEC 2005 (Keynote
Speech) Niigata, Japan.
[28] R. Grünbaum, M. Noroozian, and B. Thorvaldsson,
“FACTS—powerful systems for flexible power transmission,”
ABB Rev., pp. 4–17, May 1999.
[29] N. H. Woodley, “Field experience with dynamic voltage restorer
systems,” presented at the IEEE Power Engineering Society Winter
Meeting 2000, Singapore.
[30] T. K. Saha and P. T. Nguyen, “Dynamic voltage restorer against
balanced and unbalanced voltage sags: modeling and simulation,”
presented at the IEEE Power Engineering Society General Meeting,
Denver, CO, 2004.
[31] H. Okayama, T. Fujii, S. Tamai, S. Jochi, M. Takeda, R.
Hellested, and G. Reed, “Application and development concepts
for a new transformer-less FACTS device: the Multimode Static
Series Compensator (MSSC),” presented at the Proc. IEEE PES
Conf. Expo, Dallas, TX, 2003.
[32] X. Wei, J. H. Chow, B. Fardanesh, and A.-A. Edris, “A common
modeling framework of voltage-sourced converters for load flow,
sensitivity, and dispatch analysis,” IEEE Trans. Power Syst., vol.
19, no. 2, pp. 934–941, May 2004.
[33] ——, “A dispatch strategy for an interline power flow controller
operating at rated capacity,” presented at the 2004 IEEE/PES Power
Systems Conf. Exposition (PSCE 2004), New York.
[34] C. A. Luongo, “Superconducting storage systems: An overview,”
IEEE Trans. Magn., vol. 32, no. 4, pp. 2214–2223, Jul. 1996.
[35] M. J. Superczynski, “Analysis of the Power Conditioning System
for a Superconducting Magnetic Energy Storage Unit,” M.S. thesis,
Virginia Polytechnic Inst. State Univ., Blacksburg, Aug. 2000.
[36] Electric Power Research Institute, “Reassessment of superconducting magnetic energy storage (SMES) transmission system
benefits,” Rep. 01 006 795, Mar. 2002.
[37] I. Ngamroo, “Robust frequency stabilization by coordinated superconducting magnetic energy storage with static synchronous series
compensator,” Int. J. Emerging Elec. Power Syst., vol. 3, no. 1, Aug.
2005.
[38] K. Sen, “Recent developments in electric power transmission technology” Apr. 15, 2003 [Online]. Available: http://wpweb2.tepper.
cmu.edu/ceic/SeminarPDFs/Sen_CEIC_Seminar_4_15_03.pdf
[39] A. Edris, “FACTS technology development: An update,” IEEE
Power Eng. Rev., vol. 20, no. 3, pp. 4–9, Mar. 2000.
[40] R. Grünbaum, M. Halonen, and S. Rudin, “Power factor, ABB
static var compensator stabilizes Namibian grid voltage,” ABB Rev.,
pp. 43–48, Feb. 2003.
[41] R. Grünbaum, Å. Petersson, and B. Thorvaldsson, “FACTS improving the performance of electrical grids,” ABB Rev. (Special Report on Power Technologies), pp. 13–18, 2003.
[42] A. Edris, “Facts technology development: an update,” IEEE Power
Engineering Rev., pp. 4–9, Mar. 2000.
[43] S. Bhattacharya, B. Fardenesh, B. Shperling, and S. Zelingher,
“Convertible static compensator: Voltage source converter based
FACTS application in the New York 345 kV transmission system,”
in Int. Power Electronics Conf. (IPEC 2005) 2005, pp. 2286–2294.
Juan Dixon (Senior Member, IEEE) was born in
Santiago, Chile. He received the Degree in electrical engineering from the Universidad de Chile,
Santiago, in 1977 and the Ms. Eng. and Ph.D.
degrees from McGill University, Montreal, QC,
Canada, in 1986 and 1988, respectively.
In 1976, he was working with the State Transportation Company in charge of trolleybus operation. In 1977 and 1978, he worked at the Chilean
Railways Company. Since 1979, he has been with
the Electrical Engineering Department, Pontificia
Universidad Catolica de Chile, Santiago, where he is currently Professor. He
has presented more than 70 works at international conferences and has published more than 30 papers related to power electronics in IEEE Transactions
and IEE Proceedings. His main areas of interests are in electric traction,
power converters, PWM rectifiers, active power filters, power factor compensators, and multilevel and multistage converters. He has done consulting
work related to trolleybuses, traction substations, machine drives, hybrid
electric vehicles, and electric railways. He has created an electric vehicle
laboratory, where he has built state-of-the-art vehicles using brushless-dc
machines with ultracapacitors and high specific energy batteries. Recently,
he has started with research in distributed generation and power generation
using renewable energy sources.
Luis Morán (Fellow, IEEE) was born in Concepción, Chile. He received the Degree in electrical
engineering from the University of Concepción,
Concepción, in 1982 and the Ph.D. degree from
Concordia University, Montreal, QC, Canada, in
1990.
Since 1990, he has been with the Electrical
Engineering Department, University of Concepción, where he is a Professor. He has written
and published more than 30 papers on active
power filters and static Var compensators in
IEEE Transactions. He has extensive consulting experience in the mining
industry, especially in the application of medium voltage ac drives, large
power cycloconverter drives for SAG mills, and power quality issues. His
main areas of interests are in ac drives, power quality, active power filters,
FACTS, and power protection systems.
Dr. Morán received the City of Concepción Medal of Honor for achievement in applied research in 1998. From 1997 until 2001 he was Associate
Editor of the IEEE TRANSACTIONS ON POWER ELECTRONICS. He is the principal author of the paper that received the IEEE Outstanding Paper Award
from the Industrial Electronics Society for the best paper published in the
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS during 1995 and was
a coauthor of the paper that was awarded in 2002 by the IAS Static Power
Converter Committee.
DIXON et al.: REACTIVE POWER COMPENSATION TECHNOLOGIES: STATE-OF-THE-ART REVIEW
Authorized licensed use limited to: UNIVERSIDADE DO PORTO. Downloaded on March 11,2010 at 12:50:29 EST from IEEE Xplore. Restrictions apply.
2163
José Rodríguez (Senior Member, IEEE)
received the Engineer degree in electrical engineering from the Universidad Técnica Federico
Santa Maria, Valparaíso, Chile, in 1977 and the
Dr.-Ing. degree in electrical engineering from
the University of Erlangen, Erlangen, Germany,
in 1985.
Since 1977, he has been with the Universidad
Técnica Federico Santa Maria, where he is
currently a Professor and Academic Vice-Rector.
During his sabbatical leave in 1996, he was
responsible for the mining division of Siemens Corporation in Chile. He
has several years’ consulting experience in the mining industry, especially
in the application of large drives such as cycloconverter-fed synchronous
motors for SAG mills, high-power conveyors, controlled drives for shovels,
and power quality issues. He has authored or coauthored more than 130
refereed journal and conference papers and contributed to one chapter in
the Power Electronics Handbook (Academic, 2001). His research interests
2164
are mainly in the areas of power electronics and electrical drives. In recent
years, his main research interests are in multilevel inverters and new
converter topologies.
Ricardo Domke was born in Concepción, Chile.
He received the Degree in electrical engineering
from the University of Concepción, Concepción,
in 2000. He is currently working toward the M.Sc.
degree from the University of Concepción.
He was Academic Collaborator in the Department of Electrical Engineering, University of
Concepción, during 2004. His interests include
reactive power compensation, active power
filters, ac drives, and power distribution systems.
PROCEEDINGS OF THE IEEE, VOL. 93, NO. 12, DECEMBER 2005