ARTICLE IN PRESS
Renewable Energy 33 (2008) 832–838
www.elsevier.com/locate/renene
Technical Note
Testing solar collectors as an energy source for a heat pump
A. Georgiev
Department of Mechanics, Technical University of Sofia, branch Plovdiv, P.O. Box 7, 4023 Plovdiv, Bulgaria
Available online 2 July 2007
Abstract
The article presents the experimental study of a heat pump possessing solar collectors as an energy source. A method to test the
combined work of collectors delivering heat to the evaporator of a heat pump was devised. The layout of the test facility is shown and
the system construction with the measurement equipment is described. The planning experiment to test the installation was chosen. The
_ c and the medium fluid evaporator temperature t̄ev were
medium fluid condenser temperature t̄c , the fluid condenser mass flow rate m
chosen as experiment factors to determine both objective functions—the coefficient of performance (COP) of the heat pump and the
efficiency of the system Zs. The reverberation of both objective functions is shown.
r 2007 Elsevier Ltd. All rights reserved.
Keywords: Heat pump; Flat plate solar collectors; Experimental design; Study
1. Introduction
Freeman [1] has studied some systems for residential
space and domestic hot water heating. These are the
conventional solar system, the conventional heat pump
system, the series system, in which the solar storage is used
as the source for the heat pump, the parallel system, in
which ambient air is used as the source for the heat pump,
and the dual source system, in which the storage or
ambient air is used as the source depending on which
source yields the lowest work input.
The systems for residential space were studied by several
authors. O’ Dell et al. [2] presented mathematical models
and experimental results of similar systems for residential
space in detail. Sakai et al. [3] showed the effects of different
system parameters change and delivered some test data.
Hatheway et al. [4] carried out detailed economic analysis of
different heat pumps for residential space using solar energy.
The most comprehensive study was done by General Electric
[5] and Bessler [6] et al. Cottingham [7] considered in brief the
mentioned systems—he described the system method of work
and gave some experimental data.
The heat pump systems using the solar energy for
residential space and domestic hot water heating were
Tel.: +359 32 649785; fax: +359 32 650270.
E-mail address:
[email protected]
0960-1481/$ - see front matter r 2007 Elsevier Ltd. All rights reserved.
doi:10.1016/j.renene.2007.05.002
studied, too. MacArthur et al. [8], Chandrashekar et al. [9],
Tleimat et al. [10] and Chaturvedy et al. [11] considered this
type of systems in detail giving an economic analysis as
well. Roeder et al. [12], Speiser et al. [13], Terrell [14] and
Ucar et al. [15] presented particular details of the overall
installation analysis.
The objective of the article is to explain the series heat
pump system in detail. A bench consisting of a heat pump
‘‘water–water’’ and flat plate solar collectors was constructed. Methods to investigate the given system were
devised [16]. It also discusses the investigation regime of the
system, the accuracy of the measured parameters and the
processing of the experimental data. A parameter investigation of the mentioned system heat pump ‘‘water–
water’’— solar collectors was undertaken. A planning
experiment was used to test the system and a description of
the main characterizing system parameters, the coefficient
of performance (COP) of the heat pump and the system
efficiency Zs is shown. An error analysis evaluating the
measured parameters was conducted, too.
2. Investigation methods of a system heat pump
‘‘water–water’’-solar collectors
The methods are concerned with operational schemes
where the additional energy source (AES) is situated after
the solar collectors and before the evaporator of the heat
ARTICLE IN PRESS
A. Georgiev / Renewable Energy 33 (2008) 832–838
A
c
COP
I
_
m
N
p
Q_
s
t
n
d
Z
j
area, m2
specific heat capacity, J/kg K
coefficient of performance
insolation, W/m2
mass flow rate, kg/s
electrical power, W
pressure, Pa
heat flux, W
collector tilt from horizontal surface, 1
temperature, 1C
velocity, m/s
declination, 1
efficiency
geographic latitude, 1
Subscripts
a
AES
c
col
ev
g
hp
i
o
s
w
pump. The layout of the test facility heat pump ‘‘water–
water’’-solar collectors is presented in Fig. 1 [16].
2.1. Theory
Some parameters are defined:
Efficiency Zcol of the solar collector—it is the ratio of the
heat flux extracted by the solar collector Q_ col and the solar
collector area Acol multiplied by the global solar insolation
in the plane of the solar collectors Icol:
Q_ col
.
Acol :I col
(1)
ambient
additional energy source
condenser
collector
evaporator
global
heat pump
inlet
outlet
system
wind
circuit Nc and of the pumps in the solar circuit Ncol)
Zs ¼
Zcol ¼
time, s; h; d
t
Nomenclature
833
Q_ col
Q_ col þ Q_ AES
.
þ Q_ AES þ N hp þ N c þ N col
(5)
2.2. Investigation procedure
All parameters are measured simultaneously every 3 min
during a period of 30 min. The measurements are made
under quasi-stationary conditions. The tested collector is
orientated towards the sun and tilted to the horizon at an
angle (j–d).
The heat flux Q_ col is defined as a function of the fluid mass
flow rate through the solar collectors and the evaporator
_ col , the fluid specific heat capacity in the solar collector
m
ccol and the inlet and outlet fluid collector temperatures
tcol,i,tcol,o:
_ col ccol ðtcol;o tcol;i Þ,
Q_ col ¼ m
(2)
COP of the heat pump—the ratio of the condenser heat
flux Q_ and the consumed electrical power Nhp:
c
COP ¼
Q_ c
.
N hp
(3)
The condenser heat flux is defined as a function of the fluid
_ c , the fluid specific
mass flow rate through the condenser m
heat capacity in the condenser cc and the inlet and outlet
fluid condenser temperatures tc,i, tc,o:
_ c cc ðtc;o tc;i Þ.
Q_ c ¼ m
(4)
Efficiency of the system heat pump–flat plate solar
collectors Zs is defined as the ratio of the gained heat flux
Q_ col plus the used power from an AES Q_ AES to the full inlet
power (Q_ col ,Q_ AES and the electrical powers of the heat
pump compressor Nhp, of the pumps in the condenser
Fig. 1. Layout of the test facility heat pump ‘‘water–water’’-flat plate solar
collectors with AES: 1—heat pump; 2—flat plate solar collectors; 3—
additional energy source (AES); 4—heat exchanger; 5–7—expanding
vessels; 8, 9—pumps; 10–12—flow meters; 13—sensor of the solarimeter;
14—sensor of the anemometer; 15–21—thermometers; 22–24—out-off
valves; 25—solarimeter; 26—anemometer; 27–30—wattmeters.
ARTICLE IN PRESS
834
A. Georgiev / Renewable Energy 33 (2008) 832–838
The following must be observed during a measuring
period of 30 min:
_ col and
The fluid mass flow rates through the collector m
_ c must be kept within precision of
the condenser m
75%;
The measured temperatures must be kept within
precision of 71 1C;
The intensity of the global insolation must be kept
within precision of 710%;
The collector construction error relating to the angle
tilted to the horizon must not exceed 721;
The change of the measured electrical powers must not
exceed 75%;
The change of the measured wind velocity must not
exceed 70,5 m/s (if nwo2 m/s, it is to be assumed that
nw ¼ 0 m/s).
2.3. Processing of the experimental data
The semi-integral inlet and outlet temperatures of the
collector, evaporator and condenser and the ambient
temperature are to be determined during a period of
30 min as follows:
!
10
Dtj
t1 þ t11 X
t̄ ¼
þ
tj
,
(6)
2
tg
j¼2
where t1 and t11 are the temperature values-obtained at the
first and the last measurement of the period of 30 min, 1C;
tj temperature value obtained at the j intermediate
measurement; C;
The semi-integral wind velocity is to be determined during
a period of 30 min analogically:
!
10
Dtj
vw;1 þ vw;11 X
þ
vw;j
.
(10)
v̄w ¼
2
tg
j¼2
The semi-integral electrical powers of the heat pump, of the
pumps and of the AES are to be determined during a
period of 30 min analogically:
!
10
Dtj
N 1 þ N 11 X
þ
.
(11)
Nj
N̄ ¼
tg
2
j¼2
2.4. Accuracy of the measured parameters
The directly measured parameters must be measured
with the following precision:
Intensity of the global solar insolation—72%;
Temperatures—72%;
Flow rate—72%;
Refrigerant pressures—72%;
Wind velocity—76%;
Electrical powers—75%.
The indirectly measured parameters must be measured
with the following precision:
Condenser heat flux of the heat pump—76%;
Solar collector heat flux—76%;
Collector efficiency—76%;
Heat pump coefficient of performance (COP)—76%;
System efficiency—76%.
Dtj ¼ 3 min time step between two consecutive
measurements;
tg ¼ 3 min time period of the measurement:
The semi-integral intensity of the global solar insolation on
the collector plane is to be determined during a period of
30 min analogically:
!
10
Dtj
I col;1 þ I col;11 X
þ
.
(7)
Ī col ¼
I col;j
tg
2
j¼2
The semi-integral fluid flow rates through the condenser,
evaporator and collector are to be determined during a
period of 30 min analogically:
!
10
_1 þm
_ 11 X
Dtj
m
¯_ ¼
_j
.
(8)
þ
m
m
tg
2
j¼2
The semi-integral refrigerant pressures of condensation and
evaporation are to be determined during a period of 30 min
analogically:
!
10
Dtj
p1 þ p11 X
p̄ ¼
þ
pj
.
(9)
2
tg
j¼2
3. System design
3.1. Construction
An experimental installation consisting of a heat pump
‘‘water–water’’ and two flat plate solar collectors (Figs. 2
and 3) was constructed. There are two main components—
the heat pump 1 and the solar collectors 2 (Fig. 1).
The flat plate solar collectors are of the type KWM
(Table 1). They are orientated to the South and tilted at an
angle s ¼ 301. The heat pump is of the type ‘‘water–water’’
(Table 2). It is constructed and produced at the ‘‘Institute
of Refrigerator Technique’’ in Sofia, Bulgaria. The
evaporator consists of a tube with a diameter +30 1.5
and a length of 2816 mm. It is shaped as a cylinder with a
diameter of +640 mm. Three small tubes with diameter
+10 1 are situated therein (Fig. 4). The heating fluid is
flowing through the small tubes and the refrigerant is
flowing between the small tubes and the big tube. The
condenser is shaped as a horizontal cylinder with a length
of 500 mm and a diameter of +108 mm, where a tube
serpentine is situated (Fig. 5). The cooling fluid flows
ARTICLE IN PRESS
A. Georgiev / Renewable Energy 33 (2008) 832–838
835
Table 2
Technical data of a heat pump with compressor of the type KK-6,6
Nominal compressor power
Refrigerant
Cooling power
Fig. 2. View of the heat pump and the measuring instruments in the test
installation.
1500 W
R22
4710 W
Fig. 4. Cross section of the evaporator.
Fig. 5. Cross section of the condenser.
Fig. 3. View of the solar collectors in the test installation.
Table 1
Technical data of flat plate solar collector KVM
Absorber plate length
Absorber plate width
Insulation thickness
Distance between absorber and glass
Collector number
1.9 m
0.92 m
0.05 m
0.025 m
2
through the serpentine and the refrigerant enters the upper
condenser part, condenses round the serpentine and flows
out through its lower part.
Two circuits are available in the installation. The working
fluid enters the solar collectors as part of the solar circuit,
leaves them and enters an electrical heat exchanger 3
(maximum power of 4000 W), which heats the fluid in the
solar circuit when the solar radiation is not enough. After that
the fluid flows through the evaporator and gets cooled by
means of the pumps 9 to the expanding vessel 5, mounted at
the height of 3.04 m. Next, it flows through the flow meters 11
and enters the solar collectors. The valves 24 are used to draw
out the fluid from the solar circuit.
Both pumps 9 have the following correspondent parameters: nominal power—70 and 100 W; volume flow rate—
300 and 300 l/h; head—20 and 30 kPa.
The fluid flows through the condenser and the heat
exchanger 4 in the second circuit and reaches the expanding
vessel 7 with raised temperature. Tap water (with a
temperature of about 12 1C) is mixed in this vessel with
the heated fluid in the condenser. The cooled water flows
by means of the pumps 8 to the expanding vessel 6 and
enters the condenser through the flow meters 10 and 12.
The valve 23 regulates the flow rate in the condenser
circuit.
The two pumps 8 have the following respective
parameters: nominal power—70 and 100 W; volume flow
rate—420 and 420 l/h; head—20 and 30 kPa.
All tubes between the installation parts are well
insulated and covered with aluminium folio. The visible
parts of the thermometers are insulated with aluminium
folio, too.
ARTICLE IN PRESS
836
A. Georgiev / Renewable Energy 33 (2008) 832–838
3.2. Measurement equipment
The list of the measured parameters is presented below.
The inlet and outlet fluid collector temperatures, the inlet
and outlet fluid evaporator temperature and the inlet and
outlet fluid condenser temperatures are measured with the
corresponding precise mercury thermometers 18, 16, 20, 21, 17
and 19. The thermometers have the following properties—type
TGL, range 0–100 1C, absolute measurement error 0.1 1C.
The ambient temperature is measured in a small house
with a precise mercury thermometer 15. It has the
following properties—type TGL, range 0–50 1C, absolute
measurement error 0.1 1C.
The wind velocity is measured by means of the
anemometer 14, 26, which possesses the following properties—type N188, range 1.5–30 m/s, absolute measurement
error 0.5 m/s.
The intensity of the global solar insolation in the plane of
the solar collectors is measured by means of the integrating
solarimeter 13, 25. It has the following properties—type IS2-85, range 0.05–1.2 kW/m2, summary error of the
apparatus 72%.
The electrical power of the heat pump, of the heaters and
of the pumps of the solar and condenser circuits is
measured by means of the correspondent wattmeters 29,
27, 28 and 30, which possesses the following properties—
range 0–3600 W, precision class 0.5.
The refrigerant pressure in the condenser and the
evaporator is measured by laboratory manometers with
the following properties—type MZM, range 0–25 kg/cm2,
precision class 0.4.
The fluid flow rate in the solar circuit is measured by the
flow meters 11, which have the following properties—type
SW 16,1, range 0.5–3 l/min, and precision class 2.5.
The fluid flow rate in the condenser circuit is measured
by the flow meters 10 and 12, which possess the following
properties—type GG, range 30–250 l/h, and precision
class 2.
The equipment was calibrated prior to the test.
4. Parameter investigation of a system heat pump–solar
collectors
An experiment was conducted on the installation
consisting of heat pump and solar collectors (Fig. 1). The
methods described in Chapter 2 and an experimental
design were used during the investigation.
4.1. Choice of experimental design
It was decided to test the installation using a planning
experiment. The number of the measured parameters is 15.
One of them, the fluid flow rate through the solar collectors
and the evaporator was kept constant (4.7 l/min). Three
parameters were chosen as experiment factors:
the medium
condenser fluid temperature t̄c ¼ tc;i þ tc;o =2, the fluid
_ c and the medium evaporator
condenser mass flow rate m
fluid temperature t̄ev ¼ tev;i þ tev;o =2. They respond to the
following basic conditions:
The measurement of the factors is of high enough
precision;
The factors are essential;
All factors can be regulated directly during the experiment;
Every factor has quantitative value and can be
controlled in its whole change interval;
The realization of all possible combinations of the factor
values in their variation region limits is possible.
Preliminary tests were done with the aim to specify the
technical realization of the factor values combinations. The
following variation limits of the basic factors during
the experiment were chosen:
t̄c 2 ½25; 35 C;
_ c 2 ½0:077; 0:111 kg=s;
m
t̄ev 2 ½15; 25 C.
The experiment is conducted at three factor levels (lower,
basic and upper) as follows:
t̄c 2 f25; 30; 35g C;
_ c 2 f0:077; 0:094; 0:111g kg=s;
m
t̄ev 2 f15; 20; 25g C.
The change steps of the factors are 5 1C for the
temperatures and 0.017 kg/s for the mass flow rate.
Two parameters were chosen as objective functions—
first the COP of the heat pump and second the whole
efficiency of the system Zs. The experimental values of COP
and Zs are calculated according to Eqs. (3) and (5)
respectively. The heat specific coefficients cc and ccol are
determined as tabular values based on the average
temperatures and pressures of the water.
The COP of the heat pump as objective function meets
the basic requirements. It describes the amount of heat
delivered to the consumer at a specific input electrical
energy of the compressor.
The common view of the mathematical model describing
the COP is as follows:
_ c þ c3 t̄ev þ c12 t̄c m
_ c þ c13 t̄c t̄ev
COP ¼ co þ c1 t̄c þ c2 m
_ 2c þ c33 t̄2ev .
_ c t̄ev þ c11 t̄2c þ c22 m
þ c23 m
ð12Þ
The coefficients c0,c1yc33 are obtained after statistical
data processing. Two coefficients fall off after the evaluation of the coefficient significance. The final view of
Eq. (12) is as follows:
_c
COP ¼ 3:391957 0; 37132t̄c þ 0:09989m
þ 0:31236t̄ev þ 0:045987t̄c t̄ev 0:0200939t̄2c
_ 2c 0:1117061t̄2ev .
0:003156m
The verification proves the model adequacy.
ð13Þ
ARTICLE IN PRESS
A. Georgiev / Renewable Energy 33 (2008) 832–838
Fig. 7. Reverberation of the efficiency Zs.
Fig. 6. COP reverberation.
Fig. 6 shows the COP reverberation, which was obtained
from Eq. (13). The areas built present the COP as a
_ c and t̄ev . Every area is built at
function of three factors t̄c , m
_ c –m
_ c ¼ 0.077 kg/s, m
_ c ¼ 0.094 kg/s
a constant flow rate m
_ c ¼ 0.111 kg/s. The values of the factors t̄c and t̄ev
and m
situated on the two axes of the coordinate system and the
values of COP are situated on the third axis.
The system efficiency Zs was chosen as an objective
function in the second case because of its richest value of
the investigated system. The basic factors influencing Zs
and COP are the same and are in the same variation limits.
Zs responds to the basic requirements.
The mathematical model describing Zs has the following
common view:
ð14Þ
The coefficients d0,d1yd33 are obtained on the basis of
the same tests after statistical data processing. The
evaluation of the coefficient significance is made analogically. The model looks in the following way after rejecting
the insignificant coefficients:
_c
Zs ¼ 0:66945 0:02716t̄c þ 0:01723m
þ 0:03869t̄ev þ 0:011375t̄c t̄ev
_ c t̄ev 0:00165t̄2c
0:0094m
_ 2c 0:0162t̄2ev .
0:0045m
on the two axes of the coordinate system and the values of
Zs are situated on the third axis.
4.2. Error analysis
Three types of errors exist, which can be made during an
experiment—systematic, occasional and dynamic errors.
There is a lack of systematic errors because all the
measuring instruments were calibrated recently before
starting the measurements. Dynamic errors during the
experiment are not present for the following reasons:
_ c þ d 3 t̄ev þ d 12 t̄c m
_ c þ d 13 t̄c t̄ev
Zs ¼ d 0 þ d 1 t̄c þ d 2 m
_ 2c þ d 33 t̄2ev .
_ c t̄ev þ d 11 t̄2c þ d 22 m
þ d 23 m
837
ð15Þ
The verification proves the model adequacy.
Fig. 7 shows the Zs reverberation, which was obtained
from Eq. (15). The areas built present the Zs as function of
_ c and t̄ev . Every area is built at a constant
three factors t̄c , m
_ c –m
_ c ¼ 0.077 kg/s, m
_ c ¼ 0.094 kg/s and m
_c ¼
value of m
0.111 kg/s. The values of the factors t̄c and t̄ev are situated
The measuring equipment is used within the acceptable
working condition limits of the instruments;
The installation operates for more than an hour before
starting the reading.
The occasional errors are evaluated by means of the
regression analysis. Two linear models are created (one for
the COP and another one for the efficiency of the system
Zs) as a function of 15 factors (inlet condenser temperature,
tc,i; ; outlet condenser temperature, tc,o ; inlet evaporator
temperature, tev,i ; outlet evaporator temperature, tev,o ;
inlet collector temperature, tcol,i ; outlet collector temperature, tcol,o; global solar insolation in the plane of the solar
collectors, Icol; ambient temperature, ta; flow rate through
_ col ; flow rate through the condenser
the collector loop, m
_ c ; refrigerant pressure in the condenser, pc;
loop, m
refrigerant pressure in the evaporator, pev; electrical power
of the heat pump, Nhp; electrical power of the pumps in the
condenser loop, Nc and electrical power of the pumps in
the collector loop, Ncol) [17]. The relative error of the
measuring instruments is presented in Table 3.
The coefficient of multiple correlation R and the
^ P̄ and Z̄ Z̄^ are
maximum absolute error COP C̄ Ō
s
s
ARTICLE IN PRESS
A. Georgiev / Renewable Energy 33 (2008) 832–838
838
Table 3
Relative error of measured parameters
Parameter
Relative
error (%)
Inlet condenser temperature tc,I
Outlet condenser temperature tc,o
Inlet evaporator temperature tev,I
Outlet evaporator temperature tev,o
Inlet collector temperature tcol,I
Outlet collector temperature tcol,o
Global solar insolation in the plane of the solar collectors
Icol
Ambient temperature ta
_ col
Flow rate through the collector loop m
_c
Flow rate through the condenser loop m
Refrigerant pressure in the condenser pc
Refrigerant pressure in the evaporator pev
Electrical power of the heat pump Nhp
Electrical power of the pumps in the condenser loop Nc
Electrical power of the pumps in the collector loop Ncol
1.9
0.9
2.0
1.9
1.5
1.2
2.0
2.0
1.1
0.25
0.9
0.9
1.0
2.3
2.1
used as adequacy criterion of the model evaluation. The
following values are obtained for both parameters:
n
o
R ¼ 0.981 and max COP C̄ Ō^ P̄ ¼ 0:036 for
i i
COP;
n
o
R ¼ 0.989 and max Z̄s Z̄^ s i ¼ 0:0055 for Zs.
i
5. Conclusions
A system heat pump–flat plate solar collectors was
investigated experimentally. A planning experiment was
used during the tests for the evaluation of the COP and of
the system efficiency Zs. The following conclusions can be
drawn:
COP and Zs are higher at lower condenser temperature
t̄c ;
_ c leads to
The increase of the mass condenser flow rate m
an increase of COP and Zs;
COP and Zs are higher at higher temperature t̄ev ;
The same approach can be used by similar heat pump
systems for describing different thermal parameters.
The presented experiment is a part of the work, which
aims at the theoretical and experimental investigation of a
series heat pump system. The publication of further results
is foreseen.
References
[1] Freeman TL, Mitchell JW, Audit TE. Performance of combined
solar–heat pump systems. Solar Energy 1979;22(2):125–35.
[2] O’ Dell MP, Mitchell JW, Beckman WA. Design method and
performance of heat pumps with refrigerant-filled solar collectors.
Trans ASME, J Sol Energy Eng 1984;106(2):159–64.
[3] Sakai I, Takagi M, Terakawa K, Ohue J. Solar space heating and
cooling with bi-heat source heat pump and hot water supply system.
Solar Energy 1976;18(6):525–32.
[4] Hatheway FM, Converse AO. Economic comparison of solarassisted heat pumps. Solar Energy 1981;27(6):561–9.
[5] Solar-assisted heat pump for the heating and cooling of buildings. Six
month technical report, 6.11.1978-05.05.1979. General electric
company corporate research and development. Schenectady: New
York 12301; May 1979.
[6] Bessler WF, Hwang BC. Solar assisted heat pumps for residential use.
ASHRAE J 1980;22(9):59–63.
[7] Cottingham JG. Heat pump design: Cost-effectiveness in the
collection, storage and distribution of solar energy. ASHRAE J
1979(4):35–8.
[8] MacArthur JW, Palm WJ, Lessmann RC. Performance analysis and
cost optimization of a solar-assisted heat pump system. Solar Energy
1978;21(1):1–9.
[9] Chandrashekar M, Le NT, Sullivan HF, Hollands KGT. A
comparative study of solar assisted heat pump systems for Canadian
locations. Solar Energy 1982;28(3):217–26.
[10] Tleimat BW, Howe ED. A solar-assisted heat pump system for
heating and cooling residences. Solar Energy 1978;21(1):45–54.
[11] Chaturvedy SK, Murphy LM. Energy conservation potential of large
capacity Solar-assisted heat pumps for low temperature IPH
applications. Trans ASME, J Sol Energy Eng 1985;107(4):286–92.
[12] Roeder DJ, Reid RL. A TRNSYS/GROCS simulation of the TECH
House I ground-coupled series solar-assisted heat pump system.
Trans ASME, J Sol Energy Eng 1983;105(4):446–53.
[13] Speiser K, Diamond E. The energy house. ASHRAE J 1975(11):68–71.
[14] Terrell RE. Performance and analysis of a ‘‘series’’ heat pumpassisted solar heated residence in Madison, Wisconsin. Solar Energy
1979;23(5):451–3.
[15] Ucar M, Mittur S. Weather sensitivity analysis of solar-assisted heat
pump systems. Trans ASME, J Sol Energy Eng 1984;106(2):182–6.
[16] Georgiev A, Kartelov Y. Methods for investigation of a system heat
pump ‘‘water–water’’—water solar collectors. Thermo techniques for
the mode of life 2004;12:15–8.
[17] Bozhanov E, Vuchkov I. Statistical methods for modeling and
optimization of multifactor objects. Sofia: Tehnika; 1983.