Physical Security in
Mission Critical
Facilities
By Suzanne Niles
White Paper #82
Revision 1
Executive Summary
Physical security — controlling personnel access to facilities — is critical to achieving data
center availability goals. As new technologies such as biometric identification and remote
management of security data become more widely available, traditional card-and-guard
security is being supplanted by security systems that can provide positive identification and
tracking of human activity in and around the data center. Before investing in equipment, IT
managers must carefully evaluate their specific security needs and determine the most
appropriate and cost-effective security measures for their facility. This paper presents an
overview of the principles of personnel identification and describes the basic elements and
procedures used in security systems.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
2
Introduction
People: A Risk to be Managed
When data center security is mentioned, the first thing likely to come to mind is protection from sabotage,
espionage, or data theft. While the need is obvious for protection against intruders and the intentional harm
they could cause, the hazards from ordinary activity of personnel working in the data center present a greater
day-to-day risk in most facilities.
People are essential to the operation of a data center, yet studies consistently show that people are directly
responsible for 60% of data center downtime through accidents and mistakes — improper procedures,
mislabeled equipment, things dropped or spilled, mistyped commands, and other unforeseen mishaps large and
small. With human error an unavoidable consequence of human presence, minimizing and controlling
personnel access to facilities is a critical element of risk management even when concern about malicious
activity is slight.
Identification technology is changing as fast as the facilities, information, and communication it protects. With
the constant appearance of new equipment and techniques, it's
easy to forget that the age-old problem this technology is trying
to solve is neither technical nor complicated: keeping
unauthorized or ill-intentioned people out of places where they
don't belong. And while the first step, mapping out the secure
areas of the facility and defining access rules, may produce a
Network-Critical Physical Infrastructure
Physical security is part of Network-Critical
Physical Infrastructure (NCPI) because it plays a
direct role in maximizing system availability
(“uptime”). It does this by reducing downtime
from accidents or sabotage due to the presence
of unnecessary or malicious people.
layered and complex blueprint, it isn’t intuitively difficult — IT
managers generally know who should be allowed where. The
Other NCPI elements are power, cooling, racks,
cabling, and fire suppression.
challenge lies in the second step: deciding how best to apply
less-than-perfect technologies to implement the plan.
Who Are You, and Why Are You Here?
While emerging security technologies may appear exotic and inscrutable — fingerprint and hand scans, eye
scans, smart cards, facial geometry — the underlying security objective, unchanged since people first started
having things to protect, is uncomplicated and familiar to all of us: getting a reliable answer to the question "Who
are you, and why are you here?"
The first question — "Who are you?" — causes most of the trouble in designing automated security systems.
Current technologies all attempt to assess identity one way or another, with varying levels of certainty — at
correspondingly varying cost. For example, a swipe card is inexpensive and provides uncertain identity (you
can't be sure who's using the card); an iris scanner is very expensive and provides very certain identity. Finding
an acceptable compromise between certainty and expense lies at the heart of security system design.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
3
The answer to the second question, "Why are you here?" — in other words, what is your business at this access
point — might be implicit once identity has been established (“It’s Alice Wilson, our cabling specialist, she works
on the cables — let her in”), or it can be implemented in a variety of ways: A person's "who" and "why" can be
combined — in the information on a swipe-card’s magnetic strip, for example; a person's identity could call up
information in a computer file listing allowable access; or there could be different access methods for various
parts of the facility, designed to allow access for different purposes. Sometimes "Why are you here?" is the only
question, and "Who are you?" doesn't really matter — as for repair or cleaning personnel.
Combining Expertise to Find the Solution
IT managers know the "who and why" of security for their installation, but they may not be conversant in the
details of current methodologies or the techniques for applying them — nor should they need to be. They know
their budget constraints, and they know the risks inherent in various types of security breach at their facility.
The security system consultant, on the other hand, doesn't know the particulars of the facility, but knows the
capabilities, drawbacks, and cost of current methodologies. He or she also has experience in the design of
other security systems, and so can help clarify, refine, or simplify the "who and why" requirements by asking the
right questions.
With their combined expertise, a system can be designed that balances access requirements, acceptable risk,
available methods, and budget constraints.
Defining the Problem
Secure Areas: What Needs Protecting?
The first step in mapping out a security plan is just that — drawing a map of the physical facility and identifying
the areas and entry points that need different rules of access, or levels of security.
These areas might have concentric boundaries:
Site perimeter
Building perimeter
Computer area
Computer rooms
Equipment racks
Or side-by-side boundaries:
Visitor areas
“Physical security” can also mean…
Physical security can also refer to protection
from catastrophic damage (fire, flood, earthquake, bombing) or utility malfunction (power
loss, HVAC failure).
Here it refers only to protection from on-site
human intrusion.
Offices
Utility rooms
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
4
Concentric areas can have different or increasingly stringent access methods, providing added protection called
depth of security. With depth of security, an inner area is protected both by its own access methods and by
those of the areas that enclose it. In addition, any breach of an outer area can be met with another access
challenge at a perimeter further in.
Figure 1 – Security Map Showing “Depth of Security”
Data
vault Mech.
Offices
room
Employee parking
Deliveries
and service
Deliv.
Rack
Room
Data center
BUILDING
Employee
car entrance
Common
areas
Foot entrance
for visitors
GROUNDS
Fence
Vistor Parking
"Depth of Security"
Concentric areas to
protect data center
= Access point
Darker = More Secure
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
5
Rack-Level Security At the innermost “depth of security” layer — further in than the data room itself — is the
rack. Rack locks are not in common use (yet), but if used they serve as the last defense against unauthorized
access to critical equipment. It would be unusual for everyone in a room full of racks to have the need to access
every rack; rack locks can ensure that only server people have access to servers, only telecommunications
people have access to telecommunications gear, and so on. “Manageable” rack locks that can be remotely
configured to allow access only when needed — to specific people at specific times — reduce the risk of an
accident, sabotage, or unauthorized installation of additional gear that could cause a potentially damaging rise in
power consumption and rack temperature.
Infrastructure Security It is important to include in the security map not only areas containing the functional IT
equipment of the facility, but also areas containing elements of the physical infrastructure which, if
compromised, could result in downtime. For example, HVAC equipment could be accidentally or deliberately
shut down, generator starting batteries could be stolen, or a system management console could be fooled into
thinking the fire sprinklers should be activated.
Access Criteria: Who is Allowed Where?
A person’s authority for access to a secure area can be based on different things. Besides the usual ones —
identity and purpose, the first two listed below — there may be additional categories requiring special treatment,
such as “need to know.”
Personal identity Certain individuals who are known to the facility need access to the areas relevant to their
position. For example, the security director will have access to most of the facility but not to client data stored at
the installation. The head of computer operations might have access to computer rooms and operating
systems, but not the mechanical rooms that house power and HVAC facilities. The CEO of the company might
have access to the offices of the security director and IT staff and the
public areas, but not the computer rooms or mechanical rooms.
Reason to be there A utility repair person, regardless of whether it’s
Joe Smith or Mary Jones, might have access only to mechanical
rooms and public areas. The cleaning crew, whose roster could
change from day to day, might have access to common areas but
nowhere else. A network switch expert might have access only to
Separate the issues
Don't let the details of identification
technologies intrude upon the initial
mapping out of security requirements.
First define the areas and the access
criteria for your facility, then attack the
cost/effectiveness/risk analysis, consider
compromises, and figure out the best
implementation of technology.
racks with switching equipment, and not racks with servers or storage
devices. At a web server facility, a client’s system maintenance personnel might have access only to a “client
access room” where there are connections to their personal server for administrative purposes.
Need to know Access to extremely sensitive areas can be granted to specific people for a specific purpose —
that is, if they “need to know,” and only for as long as they have that need.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
6
Applying the Technology
Methods of Identification: Reliability vs. Cost
Methods of identifying people fall into three general categories of increasing reliability — and increasing
equipment cost:
•
•
•
What you have
What you know
Who you are
What you have
Least reliable (can be shared or stolen)
What you have is something you wear or carry — a key, a card, or a small object (a token) that can be
worn or attached to a key ring. It can be as “dumb” as an old fashioned metal key or as “smart” as a
card having an onboard processor that exchanges information with a reader (a smart card). It can be a
card with a magnetic strip of information about you (such as the familiar ATM card); it can be a card or
token having a transmitter and/or receiver that communicates with the reader from a short distance (a
proximity card or proximity token — Mobil Speedpass® is an example).
What you have is the least reliable form of identification, since there is no guarantee it is being used by
the correct person — it can be shared, stolen, or lost and found.
What you know
More reliable (can’t be stolen, but can be shared or written down)
What you know is a password, code, or procedure for something such as opening a coded lock,
verification at a card reader, or keyboard access to a computer. A password/code presents a security
dilemma: if it’s easy to remember, it will likely be easy to guess; if it’s hard to remember, it will likely be
hard to guess — but it will also likely be written down, reducing its security.
What you know is more reliable than What you have, but passwords and codes can still be shared, and
if written down they carry the risk of discovery.
Who you are
Most reliable (based on something physically unique to you)
Who you are refers to identification by recognition of unique physical characteristics — this is the
natural way people identify one another with nearly total certainty. When accomplished (or attempted)
by technological means, it’s called biometrics. Biometric scanning techniques have been developed
for a number of human features that lend themselves to quantitative scrutiny and analysis:
Fingerprint
Hand (shape of fingers and thickness of hand)
Iris (pattern of colors)
Face (relative position of eyes, nose, and mouth)
Retina (pattern of blood vessels)
Handwriting (dynamics of the pen as it moves)
Voice
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
7
Figure 2 – What You have, What You Know, Who You Are
PIN
ID #
SSN #
Physical traits
Passwords
and PINs
Keys, cards, tokens
Reliability
(Is it you?)
What You
Have
What You
Know
Who You
Are
Biometric devices are generally very reliable, if recognition is achieved — that is, if the device thinks it
recognizes you, then it almost certainly is you. The main source of unreliability for biometrics is not incorrect
recognition or spoofing by an imposter, but the possibility that a legitimate user may fail to be recognized (“false
rejection”).
Combining Methods to Increase Reliability
Why is it so complicated?
A typical security scheme uses methods of increasing reliability — and
expense — in progressing from the outermost (least sensitive) areas to
the innermost (most sensitive) areas. For example, entry into the
building might require a combination of swipe card plus PIN; entry to
the computer room might require a keypad code plus a biometric.
Combining methods at an entry point increases reliability at that point;
using different methods for each level significantly increases security at
inner levels, since each is secured by its own methods plus those of
The reason security system design
seems so complicated is this: We do
not have the technology to quickly,
easily, and cheaply determine a
person’s identity with certainty. What
we have is an assortment of methods
of varying effectiveness, convenience,
and expense, resulting in difficult
cost/effectiveness/risk analysis and the
necessity of combining technologies or
implementing concentric security perimeters for backup.
outer levels that must be entered first.
Security System Management
Some access control devices — card readers and biometric scanners, for example — can capture the data from
access events, such as the identity of people who pass through and their time of entry. If network-enabled,
these devices can provide this information to a remote management system for monitoring and logging (who’s
coming and going), device control (configuring a lock to allow access to certain people at certain times), and
alarm (notification of repeated unsuccessful attempts or device failure).
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
8
Access Control Devices
Cards and Tokens: “What You Have”
Several types of cards and tokens are currently being used for access control, from simple to sophisticated,
offering a range of performance on various dimensions:
•
•
Ability to be reprogrammed
•
Type of interaction with card reader: swipe, insert, flat contact, no contact (“proximity”)
•
Amount of data carried
•
Cost of cards
•
Resistance to counterfeiting
•
Convenience: physical form and how carried/worn
•
Computational ability
Cost of reader
Regardless of how secure and reliable they may be due to their technology, the security provided by these
physical “things” is limited by the fact that there is no guarantee the correct person is using them. It is therefore
common to combine them with one or more additional methods of confirming identity, such as a password or
even a biometric.
The magnetic stripe card is the most common type of card, with a simple magnetic strip of identifying data.
When the card is swiped in a reader the information is read and looked up in a database. This system is
inexpensive and convenient; its drawback is that it is relatively easy to duplicate the cards or to read the
information stored on them.
The barium ferrite card (also called a “magnetic spot card”) is similar to the magnetic stripe card but offers
more security without adding significant cost. It contains a thin sheet of magnetic material with round spots
arranged in a pattern. Rather than scanning or swiping, the card is simply touched to the reader.
The Weigand card is a variation of the magnetic stripe card. A series of specially treated wires with a unique
magnetic signature is embedded in the card. When the card is swiped through the reader, a sensing coil
detects the signature and converts it to a string of bits. The advantage of this complex card design is that the
cards cannot be duplicated; the disadvantage is they cannot be reprogrammed either. With this technology the
card need not be in direct contact with the reader; the head of the reader can therefore be encapsulated,
making it suitable for outdoor installation. Unlike readers for proximity cards and magnetic-stripe cards,
Weigand readers are not affected by radio frequency interference (RFI) or electromagnetic fields (EMF). The
robustness of the reader combined with the difficulty in duplicating the card makes the Weigand system
extremely secure (within the limits of a “what you have” method), but also more expensive.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
9
The bar-code card carries a bar code, which is read when the card is swiped in the reader. This system is very
low-cost, but easy to fool — an ordinary copy machine can duplicate a bar code well enough to fool a bar-code
reader. Bar-code cards are good for minimum-security requirements, especially those requiring a large number
of readers throughout the facility or a large volume of traffic traversing a given access point. This is not so
much a security system as it is an inexpensive access monitoring method. (It has been said that bar-code
access only serves to “keep out the honest people.”)
The infrared shadow card improves upon the poor security of the bar-code card by placing the bar code
between layers of PVC plastic. The reader passes infrared light through the card, and the shadow of the bar
code is read by sensors on the other side.
The proximity card (sometimes called a “prox card”) is a step up in convenience from cards that must be
swiped or touched to the reader. As the name implies, the card only needs to be in "proximity" with the reader.
This is accomplished using RFID (radio frequency identification) technology, with power supplied to the card by
the card reader’s electromagnetic field. The most popular design works within a distance of about 10 cm. (four
inches) from the reader; another design — called a vicinity card —works up to about a meter (three feet) away.
The smart card, the most recent development in access control cards, is rapidly becoming the method of
choice for new installations. It is a card with a built-in silicon chip for onboard data storage and/or computation.
Data is exchanged with the reader either by touching the chip to the reader (contact smart card) or by interacting
with the reader from a distance, using the same technology as proximity and vicinity cards (contactless or
proximity smart card). The chip, which is about a half inch in diameter, doesn’t necessarily have to be on a card
— it can be attached to a photo ID, mounted on a key chain, or worn as a button or jewelry (such as the
iButton® token). The general term for objects that carry such a chip is smart media.
Smart cards offer a wide range of flexibility in access control. For example, the chip can be attached to older
types of cards to upgrade and integrate with pre-existing systems, or the cardholder’s fingerprint or iris scan can
be stored on the chip for biometric verification at the card reader — thereby elevating the level of identification
from “what you have” to “who you are.” Contactless smart cards having the “vicinity” range offer nearly ultimate
user convenience: half-second transaction time with the card never leaving the wallet.
Keypads and Coded Locks: “What You Know”
Keypads and coded locks are in wide use as a method of access control. They are reliable and very userfriendly, but their security is limited by the sharable and guessable nature of passwords. They have familiar
phone-like buttons where users punch in a code — if the code is unique to each user it’s called a personal
access code (PAC) or personal identification number (PIN). Keypad generally implies the ability to accept
multiple codes, one for each user; coded lock usually refers to a device having only one code that everyone
uses.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
10
The security level of keypads and coded locks can be increased by periodically changing codes, which requires
a system for informing users and disseminating new codes. Coded locks that don’t have their code changed will
need to have their keypad changed periodically if a detectable pattern of wear develops on the keys. As with
access cards, keypad security can be increased by adding a biometric to confirm user identity.
Biometrics: “Who You Are”
Why not use just a biometric?
Biometric technology is developing fast, getting better and cheaper. High
confidence affordable biometric verification — especially fingerprint
recognition — is entering the mainstream of security solutions. Many
vendors now supply a wide range of biometric devices, and when
combined with traditional “what you have” and “what you know” methods,
biometrics can complement existing security measures to become best
practice for access control.
Biometric identification is typically used not to recognize identity by
searching a database of users for a match, but rather to verify identity
Q: If an entry point uses card, PIN, plus
biometric, why not use just the biometric
alone if biometrics are so reliable?
A: Because (1) Biometric processing
time can be unacceptable if a large
database of user scans must be
searched instead of comparing to the
scan of single user, and (2) The risk of
biometric false rejection or acceptance
can be reduced if the scan is compared
to only one user in the database.
While biometric traits are nearly impossible to forge, there is still the risk of
incorrect matches by the technology.
that is first established by a “what you have” or “what you know” method
— for example, a card/PIN is first used, then a fingerprint scan verifies
the result. As performance and confidence in biometric technology increase, it may eventually become a standalone method of recognizing identity, eliminating the need to carry a card or remember a password.
There are two types of failures in biometric identification:
False rejection — Failure to recognize a legitimate user. While it could be argued that this
has the effect of keeping the protected area extra secure, it is an intolerable frustration to
legitimate users who are refused access because the scanner doesn’t recognize them.
False acceptance — Erroneous recognition, either by confusing one user with another, or by
accepting an imposter as a legitimate user.
Failure rates can be adjusted by changing the threshold (“how close is close
Figure 3 – Hand Scanner
enough”) for declaring a match, but decreasing one failure rate will increase the
other.
Considerations in choosing a biometric capability are equipment cost, failure rates
(both false rejection and false acceptance), and user acceptance, which means how
intrusive, inconvenient, or even dangerous the procedure is perceived to be. For
example, retinal scanners are generally considered to have low user acceptance
because the eye has to be 1-2 inches from the scanner with an LED directed into
the eye.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
11
Other Security System Elements
Security system design focuses on devices to identify and screen individuals at entry points — “access control”
— which is all you would need if there were 100% reliability of identification, total trustworthiness of the
intentions of people admitted, and the physical perfection of unbreakable walls, doors, windows, locks, and
ceilings. To cover for inevitable failings due to flaws or sabotage, security systems ordinarily incorporate
additional methods of protection, monitoring, and recovery.
Building Design
When building a new facility or renovating an old one, physical security can be addressed from the ground up by
incorporating architectural and construction features that discourage or thwart intrusion. Security considerations
in the structure and layout of a building generally relate to potential entry and escape routes, access to critical
infrastructure elements such as HVAC and wiring, and potential sources of concealment for intruders. See the
appendix for a list of some of these design considerations.
Piggybacking and Tailgating: Mantraps
A common and frustrating loophole in otherwise secure access control systems can be the ability of an
unauthorized person to follow through a checkpoint behind an authorized person (called piggybacking when
the authorized person is complicit — i.e., holds the door — or tailgating if the unauthorized person slips
through undetected). The traditional solution is an airlock-style arrangement called a mantrap having doors at
entry and exit, with room for only one person in the space between the doors. Mantraps can be designed with
access control for both entry and exit, or for exit only — in which case a failed attempt to exit the enclosure
causes the entry door to lock and an alert to be issued indicating that an intruder has been caught. A footstepdetecting floor can be added to confirm there is only one person passing through.
A new technology for solving this problem uses an overhead camera for optical tracking and tagging of
individuals as they pass, issuing an alert if it detects more than one person per authorized entry.
Camera Surveillance
Still cameras can be used for such things as recording license plates at vehicle entry points, or in conjunction
with footstep sensors to record people at critical locations.
Closed circuit TV (CCTV) cameras — hidden or visible — can provide interior or exterior monitoring, deterrence,
and post-incident review. Several types of camera views can be used — fixed, rotating, or remotely controlled.
Some things to consider when placing cameras:
•
•
Is it important that a person in camera view be easily identifiable?
•
Are you watching to see if assets are being removed?
•
Is it only necessary to determine if the room is occupied?
Is the camera simply to serve as a deterrent?
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
12
If CCTV signals are recorded, there must be procedures in place to address the following issues:
•
•
How will tapes be indexed and cataloged for easy retrieval?
•
Who will have access to the tapes?
•
Will the tapes be stored on site or off site?
•
What is the procedure for accessing tapes?
How long will the tapes be kept before being destroyed?
New technology is in development to automate a job traditionally done by security guards — watching TV
monitors — by software detection of changes (movement) in the image on the screen
Security Guards
Despite all the technological advancements in the field of physical security, experts agree that a quality staff of
protection officers tops the list of methods for backing up and supporting access control. Guards provide the
surveillance capability of all the human senses, plus the ability to respond with mobility and intelligence to
suspicious, unusual, or disastrous events.
The International Foundation for Protection Officers (IFPO) is a non-profit organization founded for the purpose
of facilitating standardized training and certification of protection officers. Their Security Supervisor Training
Manual is a reference guide for protection officers and their employers.
Sensors and Alarms
Everyone is familiar with traditional house and building alarm systems and their sensors — motion sensors, heat
sensors, contact (door-closed) sensors, and the like. Data center alarm systems might use additional kinds of
sensors as well — laser beam barriers, footstep sensors, touch sensors, vibration sensors. Data centers might
also have some areas where a silent alarm is preferred over an audible one in order to catch perpetrators “in the
act.”
If the sensors are network-enabled, they can be monitored and controlled remotely by a management system,
which could also include personnel movement data from access-control devices (see earlier section, Security
System Management.)
Visitors
Handling of visitors must be considered in any security system design. Typical solutions are to issue temporary
badges or cards for low-security areas, and to require escorting for high security areas. The presence of
mantraps (to prevent two people from passing an entry point with one authorization) would require a provision
for a temporary override or for issuance of visitor credentials to allow passage.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
13
The Human Element
Technology can’t do the job all by itself, particularly since we are calling upon it to perform what is essentially a
very human task: assessing the identity and intent of people. While people are a significant part of the security
problem, they are also part of the solution — the abilities and fallibilities of people uniquely qualify them to be
not only the weakest link, but also the strongest backup.
People: The Weakest Link
In addition to mistakes and accidents, there is inherent risk in the natural human tendency toward friendliness
and trust. A known person entering the facility could be a disgruntled employee or a turncoat; the temptation to
bend rules or skip procedures for a familiar face could have disastrous consequences; a significant category of
security breach is the “inside job.” Even strangers can have surprising success overcoming security — the
ability of a clever stranger to use ordinary guile and deceit to gain access is so well documented that it has a
name: social engineering. Anyone in an area where harm could be done must be well trained not only in
operational and security protocols, but also in resistance to creative social engineering techniques.
People: The Strongest Backup
Protection from a security breach often comes down to the recognition and interpretation of unexpected factors
— a skill in which technology is no match for alert people. Add an unwavering resistance to manipulation and
shortcuts, and human presence can be a priceless adjunct to technology.
Beyond an alert staff, the incomparable value of human eyes, ears, brains, and mobility also qualifies people for
consideration as a dedicated element in a security plan — the old-fashioned security guard. The presence of
guards at entry points and roving guards on the grounds and inside the building, while expensive, can save the
day when there is failure or hacking of technological security. The quick response of an alert guard when
something “isn’t right” may be the last defense against a potentially disastrous security breach.
In protecting against both accidental and deliberate harm, the human contribution is the same: constant
vigilance and strict adherence to protocols. Having kept out all but those essential to the operation of the
facility, the remaining staff — well trained, following well-designed practices and procedures — are the final
firewall of an effective physical security system.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
14
Choosing the Right Solution: Risk Tolerance vs. Cost
The right security system is a best-guess compromise that balances the risk and potential damage from people
being in the wrong place against the expense and nuisance of security measures to keep them out.
Potential Cost of a Security Breach
While each data center has its own unique characteristics and potential for loss, most will have something to
consider in these general categories:
Physical loss — Damage to rooms and equipment from accidents, sabotage, or outright theft.
IT productivity loss — Diversion of staff from primary duties while equipment is repaired or replaced, data is
reconstructed, or systems are cleared of problems.
Corporate productivity loss — Interruption of business due to downtime.
Information loss — Loss, corruption, or theft of data.
Loss of reputation and customer goodwill — Consequences from serious or repeated security breaches: loss
of business, drop in stock value, lawsuits.
Considerations in Security System Design
Security system design can be a complicated equation with many variables. While specific strategies for
security system design are beyond the scope of this paper, any design will likely consider these issues:
Cost of equipment — Budget constraints ordinarily limit the extensive use of high-confidence
identification equipment. The usual approach is to deploy a range of techniques appropriate to various
security levels.
Combining of technologies — The reliability of identification at any level
can be increased by combining lower-cost technologies, with the innermost
level enjoying the combined protection of all the outer concentric
perimeters that contain it.
User acceptance — (The “nuisance” factor.) Ease of use and reliability of
identification are important in preventing the system from becoming a
source of frustration and a temptation for subversion.
You can’t buy your way out
Even if expense were of no
concern, blanketing the facility
with highest security would, in
most cases, be unacceptably intrusive and inconvenient. Each
area to be protected must be
realistically assessed for security
needs based on what’s in it and
who needs access.
Scalability — Can the design be implemented incrementally as necessity,
funding, and confidence in the technology increase?
Backwards compatibility — Is the new design compatible with elements of an older system already in
place? Keeping all or part of an existing system can significantly reduce deployment cost.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
15
Figure 4 – Balancing potential loss against known cost of security
Loss from damage
or theft
Initial cost of security
equipment
Data loss
or corruption
Damage to reputation
or customer goodwill
Productivity loss
during downtime
POTENTIAL LOSS
from people being in
the wrong place
Maintenance of
security equipment
Day-to-day inconvenience of
security protocols
KNOWN COST
of keeping people out
Conclusion
As data centers and web hosting sites proliferate, the need for physical security at the facility is every bit as
great as the need for cybersecurity of networks. Intruders who falsify their identity or intentions can cause
enormous damage, from physically disabling critical equipment to launching a software attack at an unsecured
keyboard. Even the ordinary mistakes of well-intentioned staff pose a significant daily threat to operations, and
can be minimized by restricting access to only the most essential personnel.
Technologies are in place, and getting less expensive, to implement broad range solutions based on the
identification principles of What you have, What you know, and Who you are. By combining an assessment
of risk tolerance with an analysis of access requirements and available technologies, an effective security
system can be designed to provide a realistic balance of protection and cost.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
16
About the Author
Suzanne Niles is a white paper author at APC’s Engineering Design Center in Billerica, Massachusetts. She
studied mathematics at Wellesley College before receiving a Bachelor’s degree in computer science from MIT,
with a thesis on handwritten character recognition. Suzanne has been documenting and explaining to diverse
audiences for over 25 years, in a variety of media from software manuals to photography and children’s songs.
Prior to joining APC in 2004, she was book editor for The Village Group, where she edited Wes Kussmaul’s new
book, Quiet Enjoyment, about security and identity in the Internet age.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
17
Appendix
Security Considerations in Building Design
When building a new facility or renovating an old one, physical security can be addressed from the ground up by
incorporating architectural and construction features that discourage or thwart intrusion. Security considerations
in the structure and layout of a building generally relate to potential entry and escape routes, access to critical
infrastructure elements such as HVAC and wiring, and potential sources of concealment for intruders.
For security considerations in site selection, see APC White Paper #81, “Site Selection for Mission Critical
Facilities.”
•
•
Position the data center door in such a way that only traffic intended for the data center is near the door.
Use steel doors and frames, with solid doors instead of hollow-core. Make sure that hinges cannot be
removed from the outside.
•
Data center walls should use materials sturdier than the typical sheet rock used for interior walls.
Sensors can be imbedded in the walls to detect tampering.
•
•
•
The room used for the data center should not abut any outside walls.
Allow long and clear lines of sight for any security stations or cameras within the data center.
Make use of barriers to obstruct views of the entrances and other areas of concern from the outside
world. This prevents visual inspection by people who wish to study the building layout or its security
measures.
•
Be aware of the placement of ventilation ducts, service hatches, vents, service elevators and other
possible openings that could be used to gain access. Tamper-proof grills should be installed on all such
openings that exceed 12 inches in width, to prevent human entry.
•
Avoid creating spaces that can be used to hide people or things. For example, the space beneath raised
floors could be a hiding place. Make sure that potential hiding places are secured and not easily noticed
by someone walking through the facility.
•
Install locks and door alarms to all roof access points so that security is notified immediately upon
attempted access. Avoid points of entry on the roof whenever possible.
•
Take note of all external plumbing, wiring, HVAC, etc., and provide appropriate protection. If left in plain
site or unprotected, these infrastructure components can be used to sabotage the facility without having
to disable security measures.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
18
•
Eliminate access to internal runs of wire, plumbing and ventilation ducts inside the facility. You may have
a data center thoroughly secured, but if a person walking down a corridor can gain access to a run of
power cabling or data cabling, the data center is compromised.
•
Consider the placement of the data center within the building when retrofitting an existing facility or
constructing a new data center within an existing structure. Avoid vulnerable locations or man-made
risks. For example, avoid placing a data center underneath or adjacent to kitchen facilities,
manufacturing areas with large machinery, parking lots, or any area with frequent traffic or vehicular
access. Anything from kitchen fires to car bombs to traffic accidents can pose a threat.
•
•
Protect the central security monitoring station by enclosing it with bulletproof glass.
If the data center is housed in its own building, keep the exterior of the building plain. Do not use
identifying marks such as company names or logos that would imply that a data center lies within.
•
Use concrete bollards or other obstructions to prevent unwanted vehicles from getting any closer than a
predetermined distance from the building.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
19
Glossary
Terms that appear in bold are defined in this glossary.
access control
Controlling entry of people into buildings, rooms, and racks, and controlling the use of keyboards and
equipment, by the use of automated devices that either read information stored on an object such a card (what
you have), receive a code or password (what you know), or recognize a physical trait by biometric analysis
(what you are).
access point
A place along the perimeter of a secure area where there is a door and some type of access control method to
screen users attempting entry to the area.
availability
A calculated prediction of a network’s percentage of “uptime.” For mission-critical facilities, the goal is “five
nines” or 99.999% – less than 5 minutes of downtime per year.
bar-code card
A type of access control card that uses a bar code to store information; read by swiping through a reader.
barium ferrite card
A type of access control card that uses a pattern of magnetic spots to store information; read by laying flat on a
reader. Also called a “magnetic spot card.”
biometric lock
A lock that is controlled by a biometric scanner.
biometrics
Establishing personal identity using technology to measure a physical or behavioral trait – for example, a
fingerprint.
cipher lock
A lock that is opened by pressing its buttons in a specific sequence. It differs from a coded lock in that it
typically has only 4-5 buttons, and each button can only be pressed once. The cipher lock, with metal buttons,
was the mechanical precursor of today’s electronic coded lock with a telephone-like keypad.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
20
coded lock
A lock that is opened by typing a code on a keypad.
contact smart card
A smart card that must make contact with the reader. Compare with contactless smart card.
contactless smart card
A smart card that uses RFID technology to enable its use without physical contact with the reader. Maximum
distance from the reader is either the proximity range (10 cm. / 4 inches) or the vicinity range (one meter / 3
feet) depending upon which of two RFID standards is used.
depth of security
Concentric perimeters of security having different or increasingly stringent access methods. An inner area is
protected both by its own access methods and by those of the areas that enclose it and must therefore be
entered first.
facial geometry
One of the physical traits that can be measured by biometric technology – the relative position of eyes, nose,
and mouth on the face.
false acceptance
In biometric identification, the erroneous result of identifying someone who isn’t in the database of known
people. It is one of two ways biometric identification can fail; the other is false rejection.
false rejection
In biometric identification, the erroneous result of failure to recognize a known person. It is one of two ways
biometric identification can fail; the other is false acceptance.
FAR
False Acceptance Rate. For a biometric device, the percentage of readings that are a false acceptance.
FRR
False Rejection Rate. For a biometric device, the percentage of readings that are a false rejection.
hand scan
A technique for biometric identification that measures three-dimensional hand geometry – the shape of the
fingers and the thickness of the hand.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
21
iButton®
A microchip similar to those used in a smart cards but housed in a round stainless steel button about a halfinch in diameter, which can be attached to a key fob or jewelry. iButtons are extremely rugged, but (as of May
2004) are not available with RFID technology for contactless use.
IFPO
International Foundation for Protection Officers. A non-profit organization founded for the purpose of
standardized training and certification of protection officers. Its Security Supervisor Training Manual is a
reference guide for protection officers and their employers.
infrared shadow card
A type of access control card that has a bar code sandwiched between two layers of plastic. The reader
passes infrared light through the card, and the shadow of the bar code is read by sensors on the other side.
iris scan
A technique for biometric identification that maps the pattern of colors in the iris of the eye.
levels of security
The range of security protection, low to high, provided at concentric perimeters – the least secure at the
outermost perimeter (such as entry to the building) and the most secure at the innermost perimeter (such as
access to a rack).
magnetic stripe card
magstripe card
A type of access control card that uses a magnetic strip to store information; read by swiping through a reader.
manageable
Able to be monitored and controlled remotely. Manageable access control devices can communicate with a
remote management system for monitoring (who’s coming and going and when), control (configuring the device
to allow access to certain people at certain times), and alarm (notification of repeated unsuccessful access
attempts or device failure).
management
Automated communication with remote devices for monitoring, control, and alarm. Traditionally called “building
automation” or “household automation,” the new term management refers to network-based communication with
all elements of a data center, including both the IT equipment itself (servers, storage devices,
telecommunications, and network devices) and the physical infrastructure (power, cooling, fire protection, and
security).
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
22
mantrap
An airlock-style arrangement having secured doors for entry and exit, with room for only one person between
the doors. It is a solution to the security loophole called piggybacking or tailgating, in which an unauthorized
person freely passes a security checkpoint by following an authorized person through an open door.
NCPI
Network-Critical Physical Infrastructure. Elements of a data center’s physical infrastructure (as distinguished
from IT infrastructure such as routers and storage managers) that contribute directly to availability by ensuring
uninterrupted operation. NCPI includes power, cooling, fire suppression, and physical security.
need to know
A very high level of security, with access restricted to people who have a specific, immediate need to be in the
secured area (for access to particular data, for example), with access only allowed for the time period during
which that need exists.
Network-Critical Physical Infrastructure – see NCPI
PAC
Personal Access Code. Another name for PIN (Personal Identification Number) – a code or password that
identifies a user at an access point.
physical security
Protecting physical facilities from accidents or sabotage caused by the presence of unauthorized or illintentioned people. A physical security system always includes access control devices for automated
screening at entry points, plus a sensor-based alarm system. Additional protection may include camera
surveillance and security guards. (Physical security is sometimes used in a more general way to refer to
protection from all kinds of physical damage including weather, earthquakes, and bombing. In this paper it
refers only to protection from trouble caused by unauthorized people inside the facility.)
piggybacking
The security breach that occurs when an authorized person, having unlocked a door using legitimate credentials,
holds the door open for an unauthorized person to follow through the checkpoint with no credentials. (A similar
breach is tailgating, where the unauthorized user slips through undetected behind the authorized user.)
prox card
proximity card
An access control card that has an onboard RFID transmitter/receiver, allowing it to communicate with a
reader from a distance of up to one meter (3 feet).
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
23
proximity smart card
A smart card that has RFID technology in its chip, so that it can communicate with the reader from a distance
of up to 10 cm. (4 inches). Also called a contactless smart card.
retinal scan
A technique for biometric identification that maps the pattern of blood vessels in the retina of the eye.
RFID
Radio frequency identification. Communication between card and reader without physical contact. RFID
technology is what makes proximity cards, vicinity cards, and contactless smart cards work. The RFID
chip is powered by an electromagnetic field from the reader, and so does not need a battery.
smart card
A type of access control card that stores information in a microchip. The chip not only stores data, but can
perform computation and exchange data with the reader. It is read by touching the card to the reader so that
the electrical the contacts line up. See also contactless smart card.
smart media
Small objects of any shape that contain the same type of chip used in a smart card. Smart media are typically
small objects (tokens) that can be attached to a key ring or worn as jewelry.
social engineering
The use of ordinary guile and deceit to con people into relaxing security procedures – for example, such as
revealing passwords, lending keys, or opening doors.
tailgating
The security breach that occurs when an unauthorized person slips past a checkpoint undetected, by following
an authorized user through an open door. (A similar breach is piggybacking, where the authorized user is
complicit and holds the door open.)
template
In biometrics, a computed transformation of a scan – still unique to the individual but taking up much less
storage. It is the template, not the raw scan, that is stored in a database of users or on the chip of a smart
card, for comparison to a live scan taken at an access point.
threshold
In biometrics, the user-adjustable parameter that can be used to adjust the two failure rates (false acceptance
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
Rev 2004-1
24
and false rejection). Since it represents “How close is close enough?” decreasing one of the failure rates
automatically increases the other.
token
A small object with a microchip that carries your personal identifying information. The token is touched to a
reader, or simply brought within range if it includes RFID capability.
vicinity card
An access control card that has an onboard RFID transmitter/receiver, allowing it to communicate with a
reader from a distance of up to one meter (3 feet).
voice print
In biometrics, a digital representation of a user’s voice used for comparison with the user’s live speech at an
access point.
Weigand card
A type of access control card that uses specially treated and magnetized imbedded wires to hold information;
read by swiping through a reader.
what you have
In access control, any method of identification based on an object in your possession, such as a card or token.
It is the least secure category of identification because there is no guarantee that the object is being used by the
intended person.
what you know
In access control, any method of identification based on something that you know, such as a numeric code or
a password. It is more secure than what you have, but can still be told to someone else, or written down and
discovered.
who you are
In access control, any method of identification based on a biological or behavioral trait unique to you. It is the
most secure category of identification because it very difficult to forge such a trait, but it is not 100% reliable
because of the risk of errors in reading or interpretation. Another name for this type of identification is
biometrics.
2004 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored
in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com