Energy and Costs of Leaky Pipes:
Toward Comprehensive Picture
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Andrew F. Colombo1 and Bryan W. Karney, M.ASCE2
Abstract: Leaky distribution systems are costly in terms of lost water, potentially adverse water quality effects, and the energy
consumed in supplying the leaks. To characterize the energy effectiveness of a leaky segment in a single pipe, several dimensionless
parameters are analytically derived, which relate the leak size and location to its associated energy burden and water loss. The computer
program EPANET is used to simulate the energy costs of leaks on representative distribution networks. In particular, analysis is performed
to illustrate the influence of total system demand, leak location, and topological complexity. Furthermore, the connection between water
loss and energy costs illustrates the potential importance of energy costs when pipes are leaky. The impact of leaks on water age is also
evaluated through simulation and via a dimensionless expression relating leak size and location to residence time.
DOI: 10.1061/~ASCE!0733-9496~2002!128:6~441!
CE Database keywords: Leakage; Water pipes; Costs.
Introduction
With high quality water supplies becoming increasingly uncertain, and sustainable energy sources perhaps even more so, there
has been growing attention to the problem of unaccounted for
water ~UFW! and, specifically, to leak detection and control. An
obvious issue is the loss of water, which is often expensive to
provide and treat. However, leaky pipes are also known to increase pumping energy and system rehabilitation costs and can
increase the risk of compromised water quality by allowing intrusion of polluted groundwater. Leaks have been known to undermine roadways by eroding the underlying soil and may even recharge aquifers beneath urban areas at a sufficient rate to pose a
risk to building foundations ~Price and Reed 1989!.
That leaks are costly in terms of money and resources is a
well-established idea. One early survey revealed that Chicago was
pumping more than twice the water required ~Cole 1912!, a level
still not rare today. A typical range for UFW in Europe is 9–30%
~Lai 1991!, while rates for Malaysia of 43% ~Lai 1991! or for
Bangladesh of 56% ~Chowdhury et al. 1999! have been reported.
In North America, Brothers ~2001! suggests that some utilities
experience water losses of 20–50%. Leakage is the dominant
component of UFW.
Although it has long been acknowledged that leaky distribution systems require more energy in order to maintain desirable
service levels, there is a relative absence of literature regarding
the energy burden of leaks. Traditionally, leak reduction efforts
1
Graduate Student, Dept. of Civil Engineering, Univ. of Toronto,
Toronto ON, Canada M5S 1A4.
2
Professor, Dept. of Civil Engineering, Univ. of Toronto, Toronto ON,
Canada M5S 1A4. E-mail:
[email protected]
Note. Discussion open until April 1, 2003. Separate discussions must
be submitted for individual papers. To extend the closing date by one
month, a written request must be filed with the ASCE Managing Editor.
The manuscript for this paper was submitted for review and possible
publication on May 25, 2001; approved on September 10, 2001. This
paper is part of the Journal of Water Resources Planning and Management, Vol. 128, No. 6, November 1, 2002. ©ASCE, ISSN 0733-9496/
2002/6-441– 450/$8.001$.50 per page.
have focused on reducing the cost of lost water; however, current
prices are such that energy costs could be significant for some
systems. In many communities, energy consumption by pumps is
often the largest component of operating costs for the transmission of water. In addition, the energy wasted in feeding leaks
involves an environmental burden related to the many impacts
associated with energy production and consumption, including
greenhouse gas emissions, acid rain, and resource depletion.
The implicit recognition that important savings can be
achieved via improved leak characterization is underscored by the
appearance of numerous articles on leak detection and control in
recent years ~Hunaidi et al. 2000; Vı́tkovský et al. 2000; Vairavamoorthy and Lumbers 1998!. Brothers ~2001! recommends that
utilities practice ‘‘pressure reduction’’ management in off-peak
hours to minimize water loss. Leakage control measures such as
excess pressure minimization, while helpful for reducing unnecessary waste, only address the symptoms of the problem. If the
externalities associated with leaks were better understood, the impetus to repair and prevent them would likely be greater.
Simple Water Loss and Energy Relations
in a Leaky Pipe
Consideration of how leakage increases the energy expenditure of
transmitting water through a pipe segment provides a useful departure point for an analysis of leaky networks. When a single
leak is concentrated at a fractional distance x along a uniform
length of the pipe L, relatively simple equations can be derived
that relate energy efficiency to leak location and magnitude. Although elementary, such equations offer a concise description of
how leak location and size influence leakage rate and energy requirements. The assumption made throughout this paper is that,
whether the system leaks or not, the downstream demands and
pressure requirements must be met. Thus, the priority is to evaluate the losses in systems providing an equivalent level of service.
Although this approach may not exactly reflect practice in specific
communities, this simplified approach, by removing a significant
area of variability, greatly facilitates numerical comparisons between different systems and scenarios.
JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002 / 441
J. Water Resour. Plann. Manage. 2002.128:441-450.
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Fig. 1. Energy grade line ~EGL! of a leaky pipe segment
The impact of a leak on energy use is readily ascertained by
observing the energy grade line ~EGL! in Fig. 1 ~Colombo and
Karney 2001!. The pipe segment has diameter D, DarcyWeisbach friction factor f, and a leak situated at xL. By assumption, delivery constraints are satisfied if enough water is supplied
so that the flow through the leak Q l is compensated for, and the
required flow Q d , is supplied at a prescribed downstream head
H d . Thus, the flow upstream of the leak exceeds Q d by Q l ;
moreover, the slope of the EGL assumes a discontinuity at xL,
with the upstream portion following the broken line in Fig. 1. The
total head supplied upstream H s must reflect the modified EGL if
pressure at the demand end of the pipe is to be maintained. The
leakage flow Q l can either be expressed as a proportion of demand aQ d where a is the leakage fraction, or it can be modeled
using an orifice function of the form ~Rossman 2000!
Q l 5C d A @ 2g ~ H l 2H gw !# a 5C E DH a
(1)
where A5leak area; DH5head difference ~m! across the leak; H l
and H gw 5the heads ~m! in the pipe and in the surrounding
groundwater, respectively; C d 5discharge coefficient; and
C E 5EPANET2’s ~Rossman 2000! ‘‘emitter coefficient’’ ~in
m32a /s). The emitter exponent a is often assigned a value of 0.5
~the default value used here! to reflect flow through a fixed-size
orifice. Clearly, this relation implies that as internal pressure in
the pipe builds, Q l increases and creates a feedback loop that can
tax system capacity. An orifice function is usually a more realistic
representation than the traditional approach of assigning leaks as
fixed demands.
From the orifice expression, it is evident that a and C E are
linearly related; however, the slope that relates them is a nonlinear function of x and the system heads
a5C E ~ H l 2H gw ! a /Q d
Fig. 2. Relative leakage as a function of relative head loss and leak
location
The Darcy-Weisbach equation H f 5 f LQ 2d /2gDA 2 relates the
head loss in a leak-free pipe to the flow it conducts. For a pipe
with a single leak discharging aQ d at a point xL, the resulting
expression for the friction head ratio h F becomes a linear function
of x and a quadratic function of a
h F 5H 8f /H f 5x ~ 11a ! 2 1 ~ 12x ! 511ax ~ a12 !
(4)
Therefore, as x decreases, the additional head loss imposed by the
leak also decreases because a greater portion of the pipe segment
carries only the design flow. However, if the orifice relation of Eq.
~3! is substituted into Eq. ~4!, the friction head ratio becomes a
more complex function of distance, orifice properties, and the
relative head loss h f .
The difference between the mechanical energy delivered to the
downstream end of the conduit (E d ) and that supplied at the
source (E s ) indicates the energy consumed in feeding the leak.
Expressing these energy terms as a dimensionless quantity allows
for quick assessment of the energy effectiveness of the leaky pipe.
Because overall energy efficiency depends on the supply efficiency ~e.g., pump efficiency!, an empirical efficiency factor h
can also be incorporated into the final energy expression
Ed
h
hgQ d H d
5
5
E s gQ d ~ 11a !~ H d 1H 8f ! ~ 11a ! $ 11 @ xa ~ a12 ! 11 # h f %
(5)
The extension of Eqs. ~4! and ~5! to a multileak case, along with
a brief discussion of equivalent leak representation, is provided in
the Appendix. Fig. 3 shows the response of E d /E s to changes in
(2)
H l is determined from H l 5H d 1(12x)H f in which H f is the
head loss in a pipe without leaks ~Fig. 1!. If H gw is assumed to be
zero ~as for unsaturated soil conditions!, the resulting expression
for the leakage ratio a/a 0 can be written as
a/a 0 5 @ 11 ~ 12x ! h d # a
(3)
a 0 5C E H ad /Q d 5minimum
where
leakage fraction ~which occurs
when H l 5H d ); and h f 5H f /H d 5relative head loss. Fig. 2 shows
how the leakage ratio a/a 0 varies with x and h f . Clearly, as the
pressure in the pipe decreases, the ratio approaches unity. Thus, as
far as water loss is concerned, if a leak must exist, than the downstream end (x51) of a horizontal pipe ~or the point of lowest
pressure! is the ‘‘best’’ place to have it. For x,1, a/a 0 decreases
with decreasing h f , because the pressures at the leak are smaller,
thus confirming a common strategy for leakage control.
Fig. 3. Energy ratio as a function of leak location and magnitude
~h51, h f 50.5)
442 / JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002
J. Water Resour. Plann. Manage. 2002.128:441-450.
Table 1. Topology of Hypothetical 10-Loop System
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Pipe
Number
P1
P2
P3
P4
P5
P6
P7
P8
P9
P10
P11
P12
P13
P14
P15
P16
P17
P18
P19
P20
P21
P22
P23
P24
P25
Length
~m!
Diameter
~mm!
C
890
1015
243
570
422
450
320
580
750
750
500
378
570
560
700
610
631
875
890
808
826
810
585
631
350
305
152
406
152
152
203
152
152
406
203
152
152
152
152
254
152
152
305
152
152
203
203
152
152
203
65
140
70
70
65
70
70
65
70
70
70
80
70
65
70
70
75
75
75
75
80
140
140
75
140
Node
number
Elevation
~m!
Demand
~MLd!
N17
N1
N2
N3
N4
N5
N6
N7
N8
N9
N10
N11
N12
N13
N14
N15
N16
100
152
145
125
155
133
128
127
126
149
152
124
122
139
129
123
121
Reservoir
1.2
1.2
1.2
1.2
1.92
1.2
1.92
0.0
1.2
2.4
2.16
1.2
2.4
2.4
1.2
1.2
leakage fraction for three different values of the fractional distance x. For smaller leakage fractions, the energy ratio changes
only slightly with x; however, as a becomes larger, the dependence upon x is more noticeable. The descent rates are relatively
steep, reflecting the importance of leak size to energy efficiency.
Energy Costs of a Leaky Network
As insightful as the analyses of single pipe systems are, networks
generally defy analytical treatment. In order to evaluate the impact of leaks on distribution systems, a variety of steady state
EPANET ~Rossman 2000! simulations were performed on four
hypothetical looped networks. The goal is to find simple relationships that might characterize, at least in a rough way, the interdependence of leakage rate, energy costs, and system complexity.
Hypothetical 10-Loop Distribution System
The topology of the hypothetical 10-loop system is described in
Table 1 and in Fig. 4. Some aspects that distinguish this system
from a more realistic distribution network are the absence of storage ~there are no tanks or reservoirs other than the source reservoir!, a fixed demand pattern, and the existence of only one
pumping station. Ignoring both demand pattern and storage simplifies analysis and more clearly highlights the specific role of
leaks; moreover, because average conditions dominate in the estimation of long-term energy consumption, their omission is not
especially problematic. Naturally, a variety of additional operational considerations will also come into play when determining
how leakage is managed and how it influences the overall economic performance of a real system.
Fig. 4. Network map of the 10-loop system with average day nodal
pressure for the noleak and uncompensated 25% leakage ~in parentheses! cases
Leaks at specific nodes are represented in EPANET using
emitters that are governed by the orifice relationship of Eq. ~1!. A
leak at a particular node represents the existence of leaks in some
or all of the incident pipes, thus extending the equivalent leak
concept in the Appendix. For this system, leaks have been defined
at nodes N5-8, 10, 11, and each leak is assigned the same value of
C E . The leakage is then determined by assigning a new pump
curve so that the resulting pressure distribution closely resembles
the pressure distribution of the no leak scenario. Specifically, the
pump curve is modified until the pressure at the most downstream
node, N16, is nearly equal to its original ‘‘no-leak’’ value ~i.e.,
3560.1 m!. In this way, the system may be considered as ‘‘pressure compensated.’’ The daily energy cost is calculated by
EPANET.
Fig. 4 compares the nodal pressures both with no leaks and
with 25% leakage ~pressure values in parentheses!. Without any
leaks, the total flow through the network is equal to the total
demand of 24 MLd and all nodal pressures are at least 35 m.
When the leaks at the specified nodes have emitter coefficients
associated with a 25% leakage scenario, and the original pump
station curve still applies, the total flow through the system increases to 28.5 MLd. All flow requirements are still satisfied, but
pressures do fall significantly. Although satisfaction of nodal demands is a typical modeling requirement, Germanopoulos ~1985!
correctly indicates that this assumption may not be realistic when
system pressures drop too low. The feedback effect of the orifice
relationship of Eq. ~1! is apparent when the pump curve is adjusted to restore pressures and, thus, service conditions. In compensating for the leaks, the magnitude of the losses increases so
that the total system flow becomes 30 MLd; the extra 1.5 MLd
represents the pressure-dependent demand exerted by the leaks.
Role of System Demand and Orifice Hydraulics
The orifice function of Eq. ~1! is defined by two parameters—the
emitter coefficient C E and the emitter exponent a. C E generally
reflects the size and shape of a leak and is often adjusted when
modeling leaks of different magnitudes. Although the value of a
is usually set at 0.5, other values have been suggested. For example, Goodwin ~1980! reports an exponent value of 1.18, with
the higher value suggesting an ‘‘elasticity’’ factor that describes
how a leak’s effective area responds to internal pipe pressure. The
emitter exponent may also reflect the flow regime through the
JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002 / 443
J. Water Resour. Plann. Manage. 2002.128:441-450.
Table 2. Pressure Reduction Due to a Single Leak at Selected Nodes
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Node
number
Fig. 5. Leakage as a function of demand multiplier K D and orifice
properties. Total pressure compensated system flows ~MLd! are indicated beside selected markers.
leak. Clarke et al. ~1997! examined several pipe specimens with
different sized cracks and found that the flow regime across the
crack was a function of its width. For crack widths comparable to
the pipe material grain size, the fluid escaped via a system of
small openings comprising the overall fissure and the flow regime
was turbulent. Larger cracks, which served as continuous channels, exhibited flow similar to laminar flow through parallel
plates. The implication is that there may be a relationship between
C E and a.
To investigate the sensitivity of leak response to different configurations, the hypothetical 10-loop system was again considered. Fig. 5 depicts the relationship between the demand multiplier K D and leakage L k for leaks defined by three combinations
of parameters. K D is the factor by which each nodal base demand
is multiplied to reflect nonaverage day scenarios, while L k is the
fraction of total demand (24K D MLd! leaked. Curves A and B
represent leaks defined by a50.5 and C E values of 0.15 and 0.1
MLd/m1/2, respectively. Curve C is defined with a different leak
relationship, namely by C E 50.03 MLd/m1/2 and a50.8. The intersection of curves B and C illustrates how the orifice function,
with different combinations of parameters, can give the same
leakage for a given K D . At low K D , curve B gives higher leakage
because system pressures are small, and C E is the dominant parameter in the orifice function. However, when total system demand is higher (K D .1.2), the importance of the h a factor in Eq.
~1! becomes evident in the higher leakage associated with curve
C. An obvious characteristic of Fig. 5 is that curve C is flatter than
B. This is explained by considering the derivative of Eq. ~1!
dQ l /dh5aC E h a21
(6)
For a,1, Q l increases with h at a decreasing rate; however, as a
approaches unity, the rate of this decrease diminishes and higher
leakage volumes are associated with the same K D . When a51,
Q l is linearly related to h and the associated curve in Fig. 5 would
be flat; that is, L k would be independent of K D . All three curves
descend at a decreasing rate for large K D . The inverse relationship exists because the increase in total system demand outpaces
the increase in leaked volume as K D grows. The higher pressures
associated with larger K D in the pressure compensated system
lead to greater leakage volumes, and the rate of descent of each
curve is reduced. It should be noted that the increased pumping
required to meet higher flows causes excessively high pressures in
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Pressure
~m!
no leaks
N4
N5
N11
N16
48.0
41.9
38.5
41.6
52.5
55.8
39.1
42.9
42.1
30.6
40.8
35.6
45.5
39.5
34.0
35.3
2.8
3.7
4.3
4.4
3.2
2.8
4.2
1.5
4.3
5.7
4.2
4.7
4.0
4.4
5.0
4.8
3.1
7.9
8.6
4.5
9.2
6.6
8.8
7.9
5.4
11.3
8.0
9.0
5.2
7.6
9.2
8.9
2.5
6.0
14.5
3.6
4.9
5.2
14.0
14.0
4.9
10.3
22.6
19.8
5.9
13.6
19.1
19.4
2.1
5.2
16.0
3.1
4.1
4.4
12.7
11.0
4.1
8.3
14.0
28.1
5.2
12.7
30.0
34.4
Percent Reduction in Nodal Pressure ~%!
the upstream portion of the system. Ordinarily, the system capacity would be upgraded to avoid this, and the current analysis is
unrealistic in this sense.
The role of C E can be assessed by comparing curves A and B,
which represent leaks with the same exponent value ~a50.5! but
different values of emitter coefficient. The relative position of
these curves exposes the essential linear relationship between L k
and C E when a, K D and pressures are held constant. For example,
at K D 50.8, a move from A to B represents an increase of 50% in
C E from 0.1 to 0.15, which also corresponds to a 50% increase in
L k from 20 to 30%.
Relevance of Leak Location
Analysis of the single leaky pipe indicated that leak location affects energy consumption in that, as the specified leak is moved
further downstream, its impact is more dramatically felt. Although direct extrapolation of this analytical result is not feasible
for distribution networks, it is logical to expect that leaks situated
at the most downstream portions of a network will often involve
a larger energy cost, because the larger flows must be transmitted
through a greater portion of the system. A rudimentary analysis
was performed in which a single leak with C E 50.2 MLd/m1/2 was
placed at four different nodes ~N4, 5, 11, and 16! of the hypothetical network, and the resulting pressure distributions were
compared to the no-leak case for the average day regime. Table 2
shows the percent reduction in pressure of each node, relative to
the no-leak case, for a single leak at each of the four test nodes.
The results, though significant, are not surprising—a leak present
at any node causes every node to respond. However, the nodes
most severely affected are those adjacent to, or in the vicinity of,
the leaky node. Moreover, leaks at ‘‘downstream’’ nodes like N11
and N16 also cause a greater degree of pressure reduction, both in
terms of the magnitude of reduction and the number of nodes with
reductions over a given quantity.
System Complexity and Energy Cost Response
How the complexity in a system influences the relationship between leakage and cost is an interesting question for which there
444 / JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002
J. Water Resour. Plann. Manage. 2002.128:441-450.
tion systems. What is clear, however, is that leaks are definitely
costly with all curves well above the 1:1 datum despite their
obvious differences; the relative increase in energy costs can be
expected to significantly exceed the associated leakage rate. The
effect of leak distribution in a network is evident from the disparity between the two Walski curves.
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Leaks and Water Quality
Fig. 6. Energy cost response due to system complexity
is no comprehensive answer. Nonetheless, simulations of systems
with different degrees of complexity can provide an idea of the
influence of system structure on the energy costs of leaky systems.
The number of loops is used here as a crude indicator of a
system’s complexity. Four different systems are compared in Fig.
6. These include the 10-loop system already discussed, modified
forms of the 20-loop network provided in Walski et al. ~1987! and
of the 2 loop system in the EPANET 2 User’s Manual ~Rossman
2000! tutorial, and a single pipe ~a ‘‘zero-loop’’ system!. The
chief modification to the Walski and EPANET tutorial systems is
the elimination of tanks and an exclusive focus on average conditions. The single pipe (L54 km, D5300 mm, and C5100)
simulations were based on a downstream demand of 30 l/s at 40
m pressure and a single leak at the demand node. The Walski
network ~Fig. 7! was simulated with two different leak distributions. The system referred to as Walski #1 was assigned leaks at
the central nodes N60, 80, 90, 100, 150, and 160. For Walski #2,
several of the leaks were relocated to the periphery of the network
~N55, 90, 120, 140, 150, and 170!. All leaks had the same C E and
simulations were conducted according to the methodology described earlier.
A family of second-order polynomials of the form ay2 1by fit
the curves in Fig. 6 with excellent accuracy. For example, the
energy cost curve of the 10-loop system is well described by the
function z50.012y2 11.63y, where z and y are percent increases
in energy cost and leakage, respectively. Despite each curve following the shape of a quadratic function, there is no simple ‘‘rule
of thumb’’ for relating energy cost to leakage for water distribu-
Another important aspect of leaks is their influence on water quality. Of the many possible impacts that might be considered, two
are discussed here. One is the negative impact of leaks as entry
points for potentially contaminated groundwater, pathogens, and
soil constituents when a pipe experiences a hydraulic transient.
The other, the largely positive role leaks play in reducing water
age, is discussed first.
Water Age
Water age is a popular indicator of the general water quality in a
distribution system. Like all surrogate parameters, it must be
viewed in the light of its limitations. Theoretically, if there were
no exchange of matter with the outside environment, interaction
with pipe material or breakthrough from the treatment plant, it
would not matter if the residence time in the system were 10
hours or 10 years. Of course, these assumptions are invalid, and it
is well documented that tuberculation, disinfectant residual decay
and biofilm interactions deteriorate quality within distribution
systems over time. Although comprehensive relationships between residence time and water quality transformations are difficult to establish, particularly as they depend on the specific properties of individual systems, the general correlation between water
age and degradation is well accepted.
A key factor affecting water age is velocity. LeChevallier
~1990! indicates that higher velocities influence water quality by
promoting greater transport of disinfectants throughout the system
and increasing the likelihood of biofilm detachment due to higher
shear stresses. In essence, higher velocities provide a more or less
continuous ‘‘flushing’’ of the pipes. Donlan and Pipes ~1988!
found an inverse relationship between maximum velocity and heterotrophic plate count ~HPC! on cast iron test cylinders exposed
to drinking water at several sites within a distribution system.
Elton et al. ~1995! plotted the number of customer taste complaints on the distribution system map of Gloucester, England and
found a clear correlation between customer dissatisfaction and
water age extremes. In general, lower water age is preferable
from a water quality standpoint.
The effect of leaks on residence time is easily demonstrated by
revisiting the leaky pipe of Fig. 1. The total residence time t for
water travelling the full length of the conduit is the sum of the
advection times on either side of the leak. These times differ
according to the flow and the location of the leak xL. The sum of
residence times gives
t5
xL
~ 12x ! L AL @ 11a ~ 12x !#
5
1
Q d /A
Q d ~ 11a !
~ 11a ! Q d /A
(7)
which can be nondimensionalized to yield an expression for the
relative water age
t
11a ~ 12x !
5
to
11a
Fig. 7. Network map for the system presented in Walski et al. ~1987!
(8)
where t o 5AL/Q d is residence time when no leak is present.
JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002 / 445
J. Water Resour. Plann. Manage. 2002.128:441-450.
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Fig. 9. Water age at selected nodes for minimum day demands
Fig. 8. Relative water age as a function of leak location and magnitude
parison. Table 3 shows the percentage reduction in the water age
at each node as a result of two different leakage amounts for each
demand scenario. Fig. 9 shows the water age at nodes 1, 5, 8, 11,
and 16 when C E 50, 0.1 and 0.15 for the minimum day scenario.
Not surprisingly, several of the leaky nodes ~N5– 8! exhibit
some of the largest reductions in water age. The tendency of leaks
to decrease residence times is clearly evident for both scenarios in
Table 3. Of particular interest is the discrepancy between demand
regimes. For a given C E , the leakage is greater during the minimum day demand period, because the lost volume of water comprises a larger share of total demand ~14.4 MLd! and, as a result,
the proportional impact of leaks is more significant than for average day conditions. This is the same type of relationship depicted in Fig. 5 between the average (K D 51) and maximum day
(K D 51.5) scenarios. Leakage figures are typically based on average day conditions; yet, a 17% average day leakage is associated with roughly 28% leakage during the minimum day period.
Overall, leaks reduce water age and may entail a water quality
benefit that becomes more obvious during periods of reduced
flows. This is somewhat analogous to the difficulty encountered
with air quality in air-tight buildings and their need for greater
ventilation.
The relative water age is the ratio of the leaky-pipe advection
time t to the advection time t o when the pipe has no leak. Fig. 8
shows how t/t o varies with the dimensionless parameters a and x.
The value of t/t o is greater than 0 but does not exceed 1 ~i.e., no
leak when a50) for any combination of values for a and x and
decreases with increasing leak size ~larger a! and downstream
location ~larger x!. As a increases, the sensitivity of t/t o to x also
increases.
Derivation of a concise expression to describe the effect of
leakage on water age for a looped network is not possible. Boulos
et al. ~1992! presents a general algorithm for calculating the water
age in a multisource nonleaky network that could be adapted to
account for leaks. Programs are well suited to calculate water
ages for a network and, thus, EPANET was used to conduct a
water age analysis for the 10-loop base network. Both average
day ~24 MLd! and minimum day ~demand multiplier 0.6! demand
regimes were considered, and for each regime, the leaks were
assigned C E values of 0.1 and 0.15 MLd/m1/2. The pressure distribution for minimum day is necessarily different from the average day, and a more relaxed criterion of 30 m pressure head at the
node with the lowest pressure was used in order facilitate com-
Table 3. Water Age Analysis for 10-Loop Network for Average and Minimum Day Demand
AVERAGE DAY
Age ~hrs!
Node Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
MINIMUM DAY
% Reduction in Age
Age ~hrs!
% Reduction in Age
No leak
C E 50.1
C E 50.15
No leak
C E 50.1
C E 50.15
0
0.22
0.61
0.05
0.22
0.31
0.51
0.43
0.26
0.51
0.80
0.96
0.53
0.74
0.91
1.71
0
18.6
13.0
12.5
18.9
20.3
17.9
19.9
12.4
14.1
11.1
6.3
10.2
11.2
11.0
5.0
0
25.3
17.6
18.8
25.7
27.4
24.2
26.6
17.4
20.2
15.6
8.2
14.6
15.7
15.6
11.3
0
0.37
1.02
0.08
0.37
0.52
0.85
0.72
0.43
0.85
1.34
1.61
0.88
1.24
1.52
2.86
0
28.2
20.0
21.3
28.1
30.2
27.3
29.9
19.5
22.1
18.0
8.6
16.6
18.1
18.2
8.4
0
37.4
42.7
28.8
37.3
39.5
25.5
39.1
27.2
30.4
24.7
13.6
23.2
25.1
25.4
13.4
446 / JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002
J. Water Resour. Plann. Manage. 2002.128:441-450.
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Transient Intrusion Events
Leaks may entail some benefit in reducing water age, but they
also create a serious water quality risk under transient conditions.
In essence, hydraulic transients are pressure waves that propagate
in the pipe system as a response to relatively rapid flow adjustments. Transients have the potential to burst a pipe ~high pressure! or to cause regions of low pressure or vacuum conditions.
Specifically, leaks may enhance the likelihood that foreign matter
is drawn into a pipe when a low-pressure transient event occurs.
Matter drawn into the pipe might include potentially toxic pollutants, pathogens, and soil constituents. Pathogens pose a direct
health risk by increasing the likelihood of waterborne disease and
certain soil compounds, though not directly toxic, may act as
disinfectant byproduct precursors. The extent of transient intrusion depends on the severity and duration of internal pressure
changes, the external groundwater pressure, and the orifice parameters of the leak. Funk et al. ~1999! defines an intrusion potential factor that incorporates these elements and is a function of
the head difference across the leak. Because the leak is a two-way
orifice, an intrusion volume, determined simply from the head
gradient across the leak, could be misleading unless contaminant
concentrations are considered in light of this bidirectionality.
There may be several mitigating factors in the intrusion scenario. The water in the immediate vicinity of the leak may be of
superior quality relative to the surrounding groundwater, as it is
likely to be treated drinking water that originally leaked from the
pipe. Transient phenomena often involve some kind of oscillation
between high and low pressures. When a sudden outflow of water
occurs due to the high internal pressures of a water hammer, the
immediate area around the leak is ‘‘flooded’’ with treated water.
Fernandes and Karney ~2001!, using a two-way orifice and a
tank as a boundary condition, showed that much of the water that
is drawn into the pipe may be immediately released as a result of
the same transient event. Of course, there is the question of the
time period for water exchange. Water that has escaped when the
internal pipe pressure was high ~or due to leaks under steady state
conditions! may have sufficient time while outside the pipe to
solubilize contaminants or mix with ambient groundwater that
already contains impurities. When this water is returned to the
pipe, it may be thought of as the same water, except with possibly
diminished quality.
The transient intrusion phenomenon is worthy of further investigation. A better understanding of intrusion potential and volumes, as well as the role of water exchange for mitigating adverse
intrusion effects, is required so that this process can be accounted
for within the context of broader pipe network modelling.
Cost of Leaks in a Broader Perspective
Fig. 10 depicts three conceptual maintenance cost curves of a pipe
~or portion of a distribution system! adapted from Kleiner et al.
~1998!. The ‘‘assumed’’ curve represents the increase in annual
maintenance cost for a pipe due to the general degradation of its
capacity with age ~i.e., lower C values!. Because this curve does
not account for leaks, a pipe’s service life may be erroneously
overestimated when based on it. The presence of leaks implies
that annual maintenance costs are higher than anticipated and will
cross the replacement cost threshold earlier than planned. The
threshold replacement cost serves as a criterion by which the
decision to replace a pipe is made. The time gap between the
transgression of this threshold and the design service life constitutes the ‘‘delay period’’ during which costs run over budget. If
Fig. 10. Conceptual maintenance cost curves for a pipe ~or portion
of a distribution network!
the onset of this period could be estimated, leak repair or other
rehabilitation measures might be implemented to minimize the
extra cost. Conversely, the pipe represented by the ‘‘improved’’
curve is initially more expensive due to better fabrication and
materials choices, but also more leak resistant. A pipe that conforms to it may offer planners surplus time in which to recoup the
extra capital costs associated with its manufacture and application. The opportunity to save money during the pipe’s extended
service life implies that funds can be allocated to repair or replace
other pipes and infrastructure. Improved leak characterization and
cost assessment will help determine the nature of the improved
curve.
The difference in cost between the ‘‘actual’’ and ‘‘assumed’’
curves of Fig. 10 comprises both lost water and energy costs.
Although lost water costs have dominated concern regarding leak
expense, consideration of the trade-off between water and energy
costs has tended to be ignored. The extra daily cost of system
operation due to lost water through a leaky pipe P w can be computed from P W 53,600k W Q l T as
P W 5k W C E @ H d 1 ~ 12x ! H f # a 3,600T
(9)
3
where k W 5unit price of water in $/m ; and T5analysis duration
~i.e., 24 hours!. The extra daily energy cost P E is the product of
the unit price of electricity ~$/kWh!, the difference in supply energy DE s between the leak and no-leak cases, and the analysis
duration T and is given simply as P E 5k E DE s T. From Eqs. ~4!
and ~5! the expression is resolved into system heads and the nondimensional parameters a and x
P E 5k E gQ d @~ 11a !~ H d 1H 8f ! 2 ~ H d 1H f !# T
(10)
5k E gQ d ~~ 11a ! $ H d 1H f @ 11ax ~ a12 !# %
2 ~ H d 1H f !! T
(11)
where a is computed according to Eq. ~2!.
These equations were tested for a typical water main (L
52 km, D5254 mm) with demand constraints Q d
50.07 m3 /s and H d 525 m and leak parameters C E
50.001 m5/2/s and a50.5. Fig. 11 plots the extra daily water and
energy costs as a function of leak location x when the pipe is
assigned Hazen-Williams roughness coefficients of C5130
~dashed curves! and C580 ~solid curves!. These C values reflect
the tendency for pipes to leak when they are new ~due to manufacture and/or installation defects! and when they are old, and
they are included to illustrate how leakage costs are distributed
between lost water and wasted energy according to the pipe’s
friction characteristics. Unit prices for water and electricity are
loosely based on summer 2001 prices in the City of Toronto. A
JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002 / 447
J. Water Resour. Plann. Manage. 2002.128:441-450.
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Fig. 11. Water and energy cost curves for a leaky pipe with specified
demand and leak characteristics (C580 and C5130)
price of $0.10/kWh is chosen for electricity. Residential customers typically pay about $0.50/m3 for water, and, therefore, the
City pays a fraction of this amount as its marginal cost for a cubic
meter of water. A value of $0.05/m3 is chosen in order that the
extra daily costs of the pipe due to lost water and energy are
commensurate. Fig. 11 shows that, at these prices, extra daily
water costs dominate those for energy at all possible leak locations.
The role of leak location is clearly evident in Fig. 11 and
exhibits the relationships depicted in Figs. 2 and 3. As x increases,
energy costs follow while water costs decline. When C is changed
from 130 to 80, both water and energy costs increase at all values
of x ~except at x51 where water costs are equivalent because
H l 5H d ); however, their associated curves approach each other
more quickly. These changes reflect the fact that rougher pipes
dissipate energy ~and, thus, pressure! more effectively as water
travels downstream. As a result, leakage decreases more quickly
with x while supply energy must be boosted to overcome greater
friction. The relative flatness of the C5130 energy cost curve
reflects the compensatory nature of leakage costs when a leak is
modelled using an orifice. Close to the upstream end of the pipe
pressures are higher and, therefore, more water is lost. Energy
consumption is lower here, because most of the pipe carries only
the design flow. Near to the downstream end, pressures are lower
and less water is lost; however, most of the pipe carries a larger
flow, and thus, friction losses are greater. Overall, more of the
total extra operating cost due to the leak is comprised of energy
wastage for a rougher pipe. In fact, for this basic example, when
the pipe is assigned C580 and the leak is located in the middle of
the pipe ~i.e., x50.5), the yearly cost of lost water is about
$10,400, while the cost of wasted energy is approximately
$5,900. Consequently, even if the marginal cost of water is
higher, the leak is still expensive from an energy perspective
alone. Clearly, from a financial perspective, the relative importance of water or energy costs depends on their relative prices.
Although the results of the paper need to be placed in a
broader economic context before changes in operational procedure can be prescribed, the preceding discussion illustrates that
the motivation for leak repair certainly exists. Locating and repairing leaks requires both monetary expense and the commission
of resources. Consequently, planners must make decisions regarding which leaks to repair based on a variety of other concerns.
Walski ~1993! indicates that water distribution systems must satisfy many objectives, some of which compete against energy use
minimization, and that there are several ways ~other than repair-
ing leaks! in which to save on pump energy costs. While such
tactics as improving pump efficiency and taking advantage of
time-of-day pricing are effective for reducing the financial burden
of leaks, they do not fully eliminate either their environmental
burden or the opportunity cost of failing to fix them. Operational
approaches such as maintaining lower tank levels or minimizing
excess pressures ~especially in off peak hours! can also reduce the
amount of water and energy wastage, although their application
may be impractical.
Despite the obvious benefits of repairing leaks, it is nonetheless interesting to briefly consider some of the ‘‘hidden’’ costs of
leak repair. One such ‘‘benefit’’ is diminished water age during
periods of reduced flows. Another is the possible attenuation of
hydraulic transients, because leaks can provide a means of dissipating excess pressures in much the same way as pressure relief
valves. Consequently, leaky systems may experience fewer crippling pipe breaks and other damage when experiencing transients.
Thus, an interesting trade-off between leaks and pipe breaks could
exist. Although transient analysis is beyond the scope of this
paper, it is obvious that the impact of leaks on the performance
and economics of distribution networks is multifaceted.
Conclusions
Leaks are expensive for a variety of reasons, including the loss of
water and treatment chemicals, the increased risk of water quality
deterioration, unnecessary capacity expansion, and the increased
energy expenditure required to feed the leaks. Given current typical prices, lost water costs upstage those associated with energy
wastage. Moreover, if either water or energy prices continue to
rise, the importance of leak repair will become even more pronounced. For both pipe segments and distribution networks, leaks
are shown to substantially increase energy costs. These costs depend on a variety of factors including demand regime, the spatial
distribution of leakage, and system complexity. In general, percentage increase in energy cost appears to be a second-order polynomial function of leakage. Although system topology has an
impact on energy response, no simple ‘‘rule of thumb’’ seems to
account for it.
The externalities associated with leaks are several and varied.
Although the overall impact of leaks on water quality appears to
be negative, leaks do reduce water age, especially during periods
of reduced demand and, by acting as relief mechanisms, may
mitigate pressures during transient events. A comprehensive picture of the role of leaks should consider these interesting attributes so that a prioritization scheme may be introduced into
leak detection and repair strategies.
Leaks, and the reasons for controlling them, are not new issues. The ubiquity of pipes in contemporary infrastructure is such
that leaks exist virtually everywhere and perhaps in a greater
number than actually realized. A recently reprinted statement,
originally made over a century ago, is still to the point: ‘‘There is
no water-supply in which some unnecessary waste does not exist,
and there are few supplies, if any, in which the saving of a substantial proportion of that waste would not bring pecuniary advantage to the Water Authority’’ ~Hope 1996!.
Acknowledgments
The authors would like to thank Cristovão Fernandes for his technical assistance and support, and to NSERC Canada for financial
support.
448 / JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002
J. Water Resour. Plann. Manage. 2002.128:441-450.
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
Fig. 12. EGL for a pipe with multiple leaks and corresponding
equivalent leak
lence. The first criterion requires that the leakage fraction of the
equivalent leak a e is equal to the sum of the leakage fractions of
both leaks: a e 5a 1 1a 2 . Energy equivalence requires that the
total head loss H 8f is the same regardless of which leak representation ~EGL path! is chosen. The presence of the two leaks implies that the EGL follows the path defined by ABDE. The H 8f
experienced is the sum of the individual loss terms: H 8f 5H AB
1H BD 1H DE . This is also equal to the sum of the head loss
terms of the two segments (H AC 1H CE ) associated with the
single equivalent leak ~path ACE!. H CE is determined from the
Darcy-Weisbach equation using the design flow Q d applied over
the reach (12x e )L, where x e is the fractional location of the
equivalent leak. H AC is evaluated similarly except with the larger
flow of (11a 1 1a 2 )Q d applied over the reach x e L. If one has
knowledge of the leakage fractions and the friction head ratio,
h F ,x e can be determined as
Appendix: Formulations for a Pipe
with Multiple Leaks
x e5
Energy Ratio for a Single Pipe with Multiple Leaks
When N leaks are present, the EGL is resolved into N11 distinct
segments reflecting the same number of different flows passing
through the pipe. Downstream of each leak, the flow decreases
until, after the last leak, it becomes equal to the design flow Q d .
Consistent with declining flow is a reduction in the EGL slope
~i.e., unit head loss! after each successive leak until the slope for
the pipe segment between the last leak and the downstream end is
equal to that for the overall segment (H f /L) when no leak exists.
The friction head ratio h F of a pipe segment with multiple leaks is
obtained by extending the single leak relationship.
The relative head loss for the single leak is given by Eq. ~4!;
the first term in Eq. ~4! can be expanded into a series of N terms
to account for the N leaks
N
h F 5H 8f /H f 5
(
m51
S
N
~ x m 2x m21 ! 11
(
i5m
ai
D
2
1 ~ 12x N !
(12)
where x m 5fractional distance from the supply end to the mth
leak, a i 5leakage fraction of the ith leak; and x o 50. The energy
ratio E d /E s for a single pipe with multiple leaks is then easily
determined by making the appropriate adjustments to the corresponding single leak relationship
E d /E s 5h
YS
N
11
(
m51
D
a m ~ H d 1H 8f !
(13)
Equivalent Leak Concept
In practice, quality information concerning the number and severity of leaks is difficult to acquire. The fact that most water distribution pipes are buried is the most obvious reason. In addition,
uncertainty regarding true demand ~i.e., actual Q d ) exists despite
vastly improved water accounting procedures and technologies
over the past few decades. Although it is easier to assume a single
concentrated leak for a pipe segment, there may be more than one
leak, all with different properties, along the conduit.
A pipe segment with two leaks and their associated equivalent
leak is presented in Fig. 12. Leaks 1 and 2, which are located at
x 1 L and x 2 L, respectively, are responsible for a total loss of (a 1
1a 2 )Q d . The equivalent leak that represents them must satisfy
two criteria: ~1! water loss equivalence; and ~2! energy equiva-
h f 21
~ 11a e ! 2 21
(14)
Thus, the equivalent leak associated with leaks 1 and 2 has a
magnitude of a e and is located at x e . The same approach can be
used to derive an expression for the emitter coefficient and x e of
an equivalent leak given knowledge of the emitter coefficients for
the original leaks and the relationship between a and C E . The
resulting expression is slightly more complex, but fundamentally
the same.
Notation
The following symbols are used in this paper:
A 5 cross-sectional area of pipe;
a 5 leakage fraction;
a/a o 5 leakage ratio;
a e 5 leakage fraction for equivalent leak;
a i 5 leakage fraction for leak i;
C 5 Hazen-Williams roughness coefficient;
C d 5 discharge coefficient of orifice function;
C E 5 emitter coefficient ~m5/2/s or MLd/m1/2!;
D 5 pipe diameter ~m!;
E d 5 flow energy received at the downstream end
of the pipe ~kWh!;
E d /E s 5 energy ratio;
E s 5 supply energy ~kWh!;
H d 5 demand head ~m!;
H f 5 head loss due to friction when no leak is
present ~m!;
H 8f 5 head loss due to friction when one or more
leaks are present ~m!;
h F 5 friction head ratio;
h f 5 relative head loss;
K D 5 demand multiplier;
k E 5 unit price of electricity ~$/kWh!;
k W 5 unit price of water ~$/m3!;
L 5 length of pipe ~m!;
L k 5 leakage ~%!;
m 5 current leak number;
N 5 total number of leaks along a pipe segment;
P E 5 extra daily energy costs ~$!;
P W 5 daily cost of lost water;
Q d 5 demand flow ~m3/s!;
Q l 5 flow through leak ~m3/s!;
T 5 analysis duration ~hr!;
JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002 / 449
J. Water Resour. Plann. Manage. 2002.128:441-450.
Downloaded from ascelibrary.org by UNIVERSITY OF TORONTO on 07/16/14. Copyright ASCE. For personal use only; all rights reserved.
t
to
x
xm
xN
5
5
5
5
5
y
z
a
g
DE s
5
5
5
5
5
h 5
residence time for a leaky pipe ~s!;
residence time for a pipe without leaks ~s!;
fractional location of leak;
fractional location of leak m;
fractional location of most downstream leak
~leak N!;
percent leakage;
percent increase in energy costs;
emitter exponent ~usually 0.5!;
specific weight of water ~9.81 KN/m3!;
difference in supply energy between leak
and no-leak cases ~kWh!; and
wire-to-water pump efficiency.
References
Boulos, P. F., Altman, T., and Sadhal, K. S. ~1992!. ‘‘Computer modeling
of water quality in large multiple-source networks.’’ J. Appl. Math.
Modeling, 16~8!, 439– 445.
Brothers, K. J. ~2001!. ‘‘Water leakage and sustainable supply-truth or
consequences?’’ J. Am. Water Works Assoc., 93~4!, 150–152.
Chowdhury, M. A. I., Ahmed, M. F., and Gaffar, M. A. ~1999!. ‘‘Water
system leak detection in secondary towns of Bangladesh.’’ Water Supply, 17~3,4!, 343–349.
Clarke, L. V., Bainbridge, H., Beck, S. B. M., and Yates, J. R. ~1997!.
‘‘Measurement of fluid flow rates through cracks.’’ Int. J. Pressure
Vessels Piping, 71, 71–75.
Cole, E. S. ~1912!. ‘‘The cost of leaks: Does it pay to stop them?’’ Proc.,
32nd Annual Convention of the American Water Works Association,
Louisville, Ky., American Water Works Association, Denver.
Colombo, A. F., and Karney, B. W. ~2001!. ‘‘The energetics of leaky pipes
in distribution systems.’’ Proc., CCWI 2001 6th Int. Conf. on Computing and Control in the Water Industry, Research Studies Press,
Hertfordshire, U.K.
Donlan, R. M., and Pipes, W. O. ~1988!. ‘‘Selected drinking water characteristics and attached microbial population density.’’ J. Am. Water
Works Assoc., 80~11!, 70–76.
Elton, A., Brammer, L. F., and Tansley, N. S. ~1995!. ‘‘Water quality
modeling in distribution networks.’’ J. Am. Water Works Assoc., 87~7!,
44 –52.
Fernandes, C. S., and Karney, B. W. ~2001!. ‘‘Transient transport of disinfectant introduced through an external boundary condition.’’ Proc.,
CCWI 2001 6th Int. Conf. on Computing and Control in the Water
Industry, Research Studies Press, Hertfordshire, U.K.
Funk, J. E., Wood, D. J., van Vuuren, S. J., and LcChevallier, M. ~1999!.
‘‘Pathogen intrusion into water distribution systems due to transients.’’ Proc., 3rd ASME/JSME Joint Fluids Engineering Conference,
San Francisco, American Society of Mechanical Engineers, Fairfield,
N.J.
Germanopoulos, G. ~1985!. ‘‘A technical note on the inclusion of pressure dependent demand and leakage terms in water supply network
models.’’ Civ. Eng. Syst., 2, 171–179.
Goodwin, S. J. ~1980!. ‘‘The results of the experimental program on
leakage and leakage control.’’ Tech. Rep. TR 154, Water Research
Centre, Swindon, U.K.
Hope, W. ~1996!. ‘‘The waste of water in public supplies, and its prevention.’’ Proc. Inst. Civ. Eng., 115 ~June!, 68 –75.
Hunaidi, O., Chu, W., Wang, A., and Guan, W. ~2000!. ‘‘Leak detection
for plastic water distribution pipes.’’ J. Am. Water Works Assoc.,
92~2!, 82–94.
Kleiner, Y., Adams, B. J., and Rogers, J. S. ~1998!. ‘‘Long-term planning
methodology for water distribution rehabilitation.’’ Water Resour.
Res., 34~8!, 2039–2051.
LeChevallier, M. ~1990!. ‘‘Coliform regrowth in drinking water: A review.’’ J. Am. Water Works Assoc., 82~11!, 74 – 86.
Lai, C. C. ~1991!. ‘‘Unaccounted for water and the economics of leak
detection.’’ Water Supply, 9~3,4!, IR1-1–IR1-8.
Price, M., and Reed, D. W. ~1989!. ‘‘The influence of mains leakage and
urban drainage on groundwater levels beneath conurbations in the
UK.’’ Proc., Inst. Civ. Eng., Part 1, 86, 31–39.
Rossman, L. A. ~2000!. EPANET 2 Users, Manual, U.S. Environmental
Protection Agency, Cincinnati.
Vairavamoorthy, K., and Lumbers, J. ~1998!. ‘‘Leakage reduction in
water distribution systems: Optimal valve control.’’ J. Hydrologic
Eng., 124~11!, 1,146 –1,154.
Vı́tkovský, J. P., Simpson, A. R., and Lambert, M. F. ~2000!. ‘‘Leak
detection and calibration using transients and genetic algorithms.’’ J.
Water Resour. Plan. Manage., 126~4!, 262–265.
Walski, T. M. ~1993!. ‘‘Tips for saving energy in pumping operations.’’ J.
Am. Water Works Assoc., 85~7!, 49–53.
Walski, T. M. et al. ~1987!. ‘‘Battle of networks models: Epilogue.’’ J.
Water Resour. Plan. Manage., 113~2!, 191–203.
450 / JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT / NOVEMBER/DECEMBER 2002
J. Water Resour. Plann. Manage. 2002.128:441-450.