[Indoor air quality in school facilities in Cassino (Italy)]

[Indoor air quality in school facilities in Cassino (Italy)]

Igiene e sanita pubblica, 2008
Abstract
This study evaluated the indoor air quality of 26 classrooms of secondary schools in the city of Cassino (Italy). Two types of school buildings were assessed: buildings specifically designed as schools, and former dwellings converted to schools. Measurements were taken in both winter and spring months, before students entered the classrooms and while the classrooms were occupied. Lower thermal comfort levels were observed during the winter months; in fact, during the winter, ideal temperature, humidity and air speed parameters were found in only a small percentage of classrooms and students were found to experience thermal discomfort as a result. Air velocity was often found to be inadequate both in winter and spring months and in both types of school buildings evaluated. Illumination levels measured during the winter months with both natural daylight and mixed illumination, were found to be below 200 lux, the minimum recommended level recommended by the ministerial decree 18.12.197...