Applied Thermal Engineering 31 (2011) 1923e1928
Contents lists available at ScienceDirect
Applied Thermal Engineering
journal homepage: www.elsevier.com/locate/apthermeng
Estimation of U-value of traditional North African houses
Bashir M. Suleiman
Department of Applied Physics, College of Sciences, University of Sharjah, P.O. Box 27272, Sharjah, United Arab Emirates
a r t i c l e i n f o
a b s t r a c t
Article history:
Received 11 June 2010
Accepted 20 February 2011
Available online 9 March 2011
The heat transfer and the U-values of wall layers in traditional North African houses in Libya have been
estimated. The locally produced building materials during 1970’s were used in the construction of such
buildings. These materials were limited to bricks, tiles, cement plasters, mortar and ground soils without
any insulation components. The masonry construction of these houses was based on concrete-backed
stone masonry made of limestone bricks joined by mortar forming the outer walls of the building
envelope. Based on the periodic seasonal weather conditions, within the Libyan cost region during
summer and winter, measured thermal conductivity values were used to implement such seasonal
variation of heat flow and the temperature variations through the walls. The estimation of the U-values is
based on measurements and calculations. The experimental measured thermal conductivity values were
obtained using the Hot Disk method known as Gustafsson’s probe. The numerical calculations were done
using an analytical model that considers different wall and floor constructions which are characteristics
of such houses. According to the obtained results, the U-values were quite high and therefore, several
suggestions have been proposed to improve the thermal loading performance that will lead to
a reasonable human comfort and reduce energy consumption.
Ó 2011 Elsevier Ltd. All rights reserved.
Keywords:
U-values
Building materials
North African houses
Thermal conductivity
Heat conduction
1. Introduction
There are two ways to calculate the U-value, namely the
numerical and the simplified methods. The numerical methods are
based on a detailed computer calculation that needs detailed input
data and may include a non-uniform multi-dimensional heat flow.
In general, they involve detailed variations in heat flow in all three
dimensions, however, it is almost always the case that the
construction is uniform in one direction, in other words, the
3-dimensional effects do not significantly affect the overall U-value.
There are several numerical techniques [1e5] that can be
employed, such as the finite element analysis, finite differences,
and boundary integral methods, etc. Software packages based on
such techniques are available for numerical analysis provided that
they comply with the standards [2]. It must be noted that the
numerical methods provide the most precise results, and they are
an acceptable choice. They have the option to be used to calculate
the U-value of the whole element or to calculate the thermal
resistance of single different layers within walls, roofs and/or floors
[3e8]. They are also the best choice for detailed pre-construction
and design purposes.
On the other hand, in the simplified method, the calculation
procedures are much easier to perform. It is very suitable for
E-mail address:
[email protected].
1359-4311/$ e see front matter Ó 2011 Elsevier Ltd. All rights reserved.
doi:10.1016/j.applthermaleng.2011.02.038
thermal load calculations of already constructed buildings where
much of the fine details may not be readily available. According to
standards, it involves one-dimension calculations of the upper and
the lower limits of thermal resistance of the element. Then, the
U-value of the components (the arithmetic mean of these two
limits) can be used to estimate the expected U-value of the element.
The expected result should lie within these limits, provided the
difference between the limits is not too large.
For example, for a building element which consists of plane,
parallel, uniform layers where the heat flows in one dimension
(straight lines) through these layers, the U-value is the inverse
simple sum of the thermal resistances of each layer. However,
almost all practical building components have non-uniformities
due to mortar joints between masonry units that may lead to the
presence of layers (thermal bridges) that are not parallel, and the
heat no longer travels in straight lines. These joints affect the total
heat transfer through the element and need to be included in the
calculation of the U-value, when using such simplified methods.
In this work, a simple U-value calculations formula (see
discussion section) is used to estimate the U-values for a typical
North African house with building envelope (outer walls) that are
based on concrete-backed stone masonry made of limestone bricks
joined by mortar, see the picture depicted in Fig. 1. These bricks are
excavated from two major places (mines) in the north-eastern
province of Libya. One mine produces soft limestone bricks and the
other produces hard limestone type as shown in Fig. 2. These
1924
B.M. Suleiman / Applied Thermal Engineering 31 (2011) 1923e1928
Fig. 1. A group of buildings with exposed and non-exposed limestone external walls
showing the mortar joints network and the plaster layers arrangement.
houses were built during the seventies (1970’s) with the lack of any
technical data on the construction materials such as the thermal
properties of the individual components of the wall structure. Thus
they were built without performing thermal transmittance (load)
calculations or considering any insulation measures. This made
them very unpleasant to occupants during both hot and cold
seasons. Therefore, technical data such as U-values within the
structure of such houses are essential for the calculations of
thermal loads and/or estimating energy consumptions for the
purpose of energy savings. Furthermore, such calculations could
provide basis for insulation materials manufactures to produce
suitable insulation materials that can be used to improve the
thermal performance of such houses.
2. Location and climate
Libya is located in north Africa facing the Mediterranean Sea and
shares border with Egypt in the east, Tunisia and Algeria in the west
Niger and Chad in the south, and Sudan in the south east. Libya
covers an area of some 1,759,540 km2 and extends between latitudes 22 and 33 N and longitudes 10 and 25 E.
It basically has two types of climate, desert in the south and
Mediterranean in north. In the north and along the coastal strip, in
extreme cases during the summer, temperatures can reach as high
as 45 C and the relative humidity goes up to 65%. In winter, due to
rain, the relative humidity can exceed seventy five present and
temperature can go below the freezing point. Along this coastal
strip lie the most populated cities namely Benghazi in the east and
Tripoli in the west. These cities represent the residential sector of
this relatively hot and humid region. The use of air conditioners
during the summer period causes a high thermal load and high
Fig. 3. A typical temperature limits and means relative humidity changes during one
year within Benghazi provinces. The squares and dots temperatures variations and the
triangles represent the average humidity variations.
electricity consumption which adversely has indirect impact on
global (CO2) environment. Therefore, the issue of energy saving in
designing new residential buildings and renovation of old buildings
in such locations is vital.
2.1. Climate of Benghazi
Benghazi is the 2nd largest city in the northern east coast of
Libya. It includes the part of the coastal province located in the
north of Libya at Latitude: þ32.12 (32 07’12"N) and extends
between longitudes: þ20.07 to (20 04’12"E). In Benghazi, the
climate can be divided into two periods. November to March is the
cold period and temperature during DeceJan can reach 10 C at
night with high relative humidity that can reach 75% due to rain.
June to September is the hot period, JulyeAugust are the months of
relatively harsh condition of heat. Both Temperature and humidity
are relatively high. Fig. 3 shows the typical daily temperature limits
and mean relative humidity changes during one year within Benghazi provinces [9].
At the present time, and during the summer period, more than
80% of the buildings are using air- conditioners excessively (splitunit type) within relatively small volumes. Fig. 4, shows a typical
building with relatively large number of conditioners as indicated by
the arrows in the picture. This led to an increase in the consumption
of electrical power to high levels that some times exceeds the
available sources and cause partial blackouts within the city.
Fig 2. Actual pictures of the bricks type with the mortar joints network.
1925
B.M. Suleiman / Applied Thermal Engineering 31 (2011) 1923e1928
Table 1
Characteristic properties of the building materials of the house envelope.
Fig. 4. The excessive use of air conditioners (split-unit type) within small building
sizes as indicated by the arrows.
3. Simplified theoretical model
When considering a multi-layered construction with simplified
index to represent the total heat-transfer processes, the U-value or
total transmittance is given by:
UT ¼
1
1
¼ P
xi
N
RT
i¼1
(1)
li
Where, N is the total number of layers, with xi referring to the
thickness and li the thermal conductivity of each layer. The overall
heat-transfer q through an area A and within a temperature
difference ∆T, then can be estimated by:
q ¼ UT ADT
(2)
This formula assumes steady state heat conduction and ignores
the dynamic aspects of material behavior and spatial differences. In
order to include the dynamic aspects of material behavior with
spatial differences, the variations of thermal conductivity with
temperature should be included [8]. However, as first approximation, Eq. (2) has been considered as a useful tool and is often used to
estimate the heat transfer. In this work, the thermal conductivity
values of the investigated building materials were measured in the
laboratory at fixed temperature value of 25 C, therefore, our
analysis was limited to using Eq.(1) to estimate UT values. It should
be mentioned that a more detailed calculation should involve the
effect of energy savings through the heating, cooling and ventilation system (HCVS). These buildings have no HCVS and the full
detailed information (fine details) was not available, in fact only
recently they have been equipped with the split-unit air condition
type. Due to the present legislative technical difficulties, the
thermal conductivity measured values were the only readily source
of data that can be used. Therefore it was not possible to do such
detailed calculations. In relation to the handbook of air conditioning [10], the cooling load (QCooling) of the building should be
possible to estimate using such split-unit conditioners. Hatamipour
et al. [11], estimated the total cooling load by considering the effect
of various parameters according to the following equation:
Material
Thickness
(m)
Thermal conductivity
(W/m-K)
Density (kg/m3)
Plaster
Tiles
Limestone Hard
Limestone Soft
Ground Soil
0.020
0.025
0.200
0.200
0.300
0.658
1.710
1.533
0.751
0.455
1708
2162
1900
1444
390
to heat generated by appliances, persons, etc. and QAirflow is the
cooling load due to airflow into the building (sensible and latent
heat). For each of above terms some well-known equations are
developed and can be used with care [11]. For example, wall
temperature could be calculated using mathematical modeling of
the unsteady state heat transfer in the wall. This will depend on
radiation intensity, variations of external air temperature (see
Fig. 3) and accumulation of heat inside the wall. Unfortunately, in
these buildings, during winter, daytime outside temperatures are
warmer than inside temperatures and hence the net flux into the
room continue throughout the walls until midday. During night
time the temperature outside drops and as the room stays relatively
warm the net flux is out of the room, such fluctuations of the heat
flux complicates the problem even further. As it was mentioned,
such estimations are not possible and we are planning for possible
future work to incorporate some of the fine details in the thermal
load calculations including the effect of intensity of the solar radiation through the windows. This can be done by incorporating
a network of temperature and humidity sensors within and around
the walls to collect data and build a database of information
throughout the year.
4. Discussion and results
Five different materials used in the construction of a typical
Libyan house were used to estimate the U-values, including two
types of limestone bricks, plaster, ground soft soil, and marble tiles.
The Hot Disk technique [12e14] was used to measure the thermal
conductivity of these materials at an average room temperature of
25 C. Depending on the time of the day and the seasonal variations,
in the eastern costal province, the average outer walls surface
temperature can vary from 40 to 10 C. The thermal conductivity of
these samples was measured at room temperature (around 25 C),
this value is a good approximation to the average temperature of
the local climate average temperature. Looking at the temperature
variations in the northern part of the country, in the hot summer
days the temperature will not exceed 40 and in cold winter nights
it will not go below 10 . Thus measuring the thermal properties of
the materials at room temperature gives a good approximated
QCooling ¼ QTransmission þ QSolar þ QInternal þ QAirflow
where, QTransmission the cooling load due to heat transfer from
exterior walls and envelopes, QSolar the cooling load due to sun
radiation transmitted from windows, QInternal the cooling load due
Fig. 5. A schematic drawing of the bricks type with the mortar joints network.
1926
B.M. Suleiman / Applied Thermal Engineering 31 (2011) 1923e1928
Fig. 6. Typical tile and plaster samples.
average value of the thermal conductivity, and hence all measurements were preformed at an average temperature of 25 C. These
measurements were done on isotropic basis with respect to microvoids distributions in the sample matrix.
The average apparent densities of the samples ranging from 390
to 2162 kg/m3 were calculated using the dimensions (volume) and
masses of the individual samples. The characteristic properties of
these materials are shown in Table 1.
These materials are the building blocks of three elements of the
outer house envelope, namely the outer walls and the flooring. The
outer walls are of traditional masonry type based on concretebacked stone masonry made of limestone bricks joined by mortar
and covered from both sides by common (sand and cement) plaster
layers of 20 mm each, see Fig. 5. The limestone bricks of outer walls
are either soft or hard bricks. Fig. 2a and b, respectively, show actual
Mortar fraction ¼ 1
estimation of the annual energy consumption for a split-unit airconditioning system is shown in the last column of the table, to be
discussed.
We can see that the calculated U-values are quite high, especially for the hard brick type. These values are without including
irregular thermal bridges such as concrete beams and/or regular
(frequent) thermal bridges due to the mortar joints between the
bricks. We may include the mortar joints in the calculation for both
inner and outer sides of walls simply by treating the bricks layer as
a bridged layer. The joints, to some extent, may reduce the U-value
if the difference in thermal resistance between bridging material
and the bridged material is exceeding 0.1 m2 k/W. In our case, the
differences are in the range of 0.1e0.25 m2 k/W. The mortar fraction
between the bricks can be estimated using the ratio of the surface
area of the brick with and without the mortar joints as follows:
brick length brick hight
ðbrick length þ joint thicknessÞ ðbrick height þ joint thicknessÞ
pictures of soft and hard bricks external walls without the plaster
layer. The ground floors are made of a common ground soft soil
enclosed with cement and sand mortar of the plaster type and
covered with tiles,(see Fig. 6). The approximate dimensions of these
samples were 10 by 10 cm square with various thicknesses.
The choice of these five samples was based on the fact that
construction of the outer walls and flooring of the ground floor
envelope of such houses were made of these materials. The
construction materials of the roofs were not included due to the
following two reasons:
First, most of these buildings are multi-stored and the effect is
limited to the highest floor, which has different outer wall bricks
(manufactured common cement type).
Second, the large variations of roof design in terms of their
thickness, methods of constructions mortar types, iron (steel)
networking and types of concrete used.
Table 2 shows the U-values of two types of external walls that
were made of soft and hard limestone bricks covered on both sides
by 2 cm thick plaster layers. Table 2 also shows the U-value of the
ground floor slab. It is a combination of three layers of soil, mortar
and tiles with an average thickness of 35 cm. Based on RT values an
Table 2
The U-values of the multi-layered construction elements of the building envelope
and the corresponding estimated annual energy consumption E.
Construction element
Effective
thickness(m)
RT
(m2 k/W)
UT
(W/m2 k)
E
(kWh/m2)
External wall (soft bricks)
External wall (hard bricks)
Slab on ground floor
0.240
0.240
0.345
0.33
0.19
0.70
3.03
5.26
1.46
40.26
69.93
18.98
Using the dimensions of the limestone bricks in meters, as 0.40, 0.20
and 0.02 for length, height and joint thickness, respectively, the calculations lead to a mortar fraction of around 13% of the total surface area.
Furthermore, the possibility of including the surface resistances
of naturally presented thin insulating layers of air at the inner and
outer surfaces of the external walls, which are in the range of
0.03e.013 m2 K/W, may further reduce the estimated U-values.
Unfortunately, including these effects, namely mortar bridging and
air insulations will not help very much and the U-values are still
high and far from comfortable.
The annual energy consumption (E) given by the last column in
Table 2 was calculated using the following equation from ref. [7]:
E ¼
0:024 D
kWh=m2
R C
Where, D is the degree-days of the location (D ¼ 1476); R is the
thermal resistance of the construction element, and (C ¼ 2.65) is
the coefficient of thermal performance (COP) of a commonly used
LG wall split-unit air-conditioning system. The value of C was taken
from the technical specification catalog for LG wall split-unit 2.5 ton
capacity/heating & cooling mode (model #S306GH). It is worth
mentioning that the efficiency of hot and cold air-conditioning
systems is measured by a coefficient of performance (COP) - the
amount of heat they generate compared to the amount of electricity
needed to run them. A good quality air-conditioning system can
have a COP of around 3 to 1.(which means you can transfer 3 kW of
heat for 1 kW of electricity).
The D value was estimated over a period of five years using the
mean value of the heating and cooling degree-days of the location
B.M. Suleiman / Applied Thermal Engineering 31 (2011) 1923e1928
HLLB (airport): Benina, Benghazi-Libya (20.27E, 32.10N) [15].
According to ref. [7],the E values can be used to calculate the total
discount cost or the net present value per square meter of the
construction elements. Unfortunately, this requires parameters
such as the present worth factor and energy discount/inflation
rates that are not available for this type of construction elements.
It should be noted that UT calculations were made at dry
conditions, not including the moisture effect on the thermal
conductivities of the individual materials and/or the overall
thermal conduction of the walls. The source of this moisture may be
caused by wind-driven rains, foggy weather conditions, or relatively high outside temperature leading to high humidity. Moisture
effect on thermal conductivity had been estimated in a previous
work [13].
The moisture has considerable effect on the conductivity of the
materials, owing to the fact that liquid water has thermal conductivity which 25 times greater than that of air. In addition to that, it is
the complexity related to moisture content that is associated with
several factors such as mode of heat transfer (sensible and/or
latent), the moisture location, arrangement of moisture in the
building blocks, etc. Such factors result in considerable effect on the
measured heat conduction. Because of the complexity, there are no
tables which can state that for a given percentage of moisture in the
material there will be a certain percentage increase in its conductivity. The only certain statement which can be made is that
moisture in the liquid phase will increase the conductivity. It is well
known that the insulating value of most materials is greatly
reduced by the presence of free water. Furthermore, it is generally
agreed that the durability of masonry depends primarily on its
resistance to the penetration of moisture into the body of masonry
[16]. Therefore, we conclude that reliable insulation and/or vapor
barriers are required for such buildings.
In this work, it is not possible to do quantitative analysis
regarding the benefits of insulation/vapor barriers, however, there
are two factors that could illustrate such benefits:
1 The estimated values of the annual energy consumption
depicted in Table 2 are clear indication of the effective role of
insulation barriers in reducing energy consumption.
2 During hot season, vapor molecules in the form of moisture
will flow into the building from the outside. Vapor barriers
provide protection from external wind-driven moisture or bulk
water penetration through capillary water breaks and/or
micro-cracks in the wall structure. If buildings are not well
ventilated during summer the indoor air quality could cause
health hazard e mold conditions known as SBS, (Sick Building
Syndrome). Thus, beside reduction in energy use, the benefits
of improving indoor air quality are invaluable.
In general, adding insulation and vapor barriers to the walls will
damp temperature fluctuations and prevent vapor penetration
inside the house envelope and provide better comfort [17].
As it was stated in section 3, more detailed work of thermal load
calculation that include other parameters and/or factors such as the
thickness of insulation as well as the surface to volume ratio [18],
the location and extreme weather conditions will be presented in
the near future. However, according to the calculated U-values, the
external walls of these houses are in need for proper assessment
and building codes to select a suitable insulation scheme to
improve their performance in terms of energy conservation and
human comfort. As far as my knowledge, for the time being, there
are no specific energy conservation building codes to promote
energy efficient buildings in Libya; however, there are some
universal rules to implement energy conservation and environmental issues. This work is a very small contribution to the basis of
1927
such codes that require extensive building simulations followed by
detailed measurements in model building.
5. Conclusions
Five different materials used in the construction of a typical
Libyan house were used to estimate the U-values for the external
walls and the ground floor. The external walls are of traditional
masonry type based on concrete-backed stone masonry made of
limestone bricks joined by mortar and covered from both sides by
common (sand and cement) plaster layers of 20 mm each. The
ground floor is made of a common ground soft soil enclosed with
cement and sand mortar of the plaster type and covered with tiles.
Including the surface resistances of naturally presented thin
insulating layers of air at the inner and outer surfaces of the external
walls will not reduce the U-values more than few percentage.
Furthermore, including the mortar bridging through the bricks have
a little effect due to the fact that the mortar fraction surface area is
less than 13% of the total surface area of the individual brick. It is
anticipated that the situation is more severe if moisture reaches the
walls and the insulating value is greatly reduced by the presence of
free water. The calculated U-values indicate that the external walls of
these houses which are built using two types of bricks are in need for
proper assessment to select a suitable insulation scheme to improve
their performance and to make the houses pleasant and comfortable.
Thus, this work might provide the basis for insulation materials
manufactures to produce suitable and reliable insulation materials
that can be used to improve the thermal performance of such houses.
It should be noted that measurements made by laboratory test may
not be truly indicative of the properties of the materials in service and
aging effects on dimensional stability (ability to retain size and
shape) should be anticipated. Finally, a more detailed work of
thermal load calculation which includes other factors such as the
location and moisture effect and extreme weather conditions should
be investigated. It is recommended to do more detailed measurements in model building and extensive building simulations in order
to develop reliable building codes in Libya.
Acknowledgements
The financial support from the University of Sharjah for the
project is gratefully acknowledged. This work is associated with
research project No. 021303.
References
[1] R. Butler, The computation of heat flows through multi-layer slabs, Build.
Environ. 19 (3) (1984) 197e206.
[2] R. Yumrutas, M. Unsa, M. Kanog¢, Periodic solution of transient heat flow
throw through multilayer walls and flat roofs by complex finite Fourier
transform technique, Build. Environ. 40 (3) (2005) 1117e1126.
[3] M.F. Zedan, A.M. Mujahid, An efficient solution for heat transfer in composite
walls with periodic ambient temperature and solar radiation, Int. J. Appl.
Energy 14 (2) (1993) 83e97.
[4] C. Lombard, E.H. Mathews, A two-port envelope model for building heat
transfer, Build. Environ. 34 (1999) 19.
[5] J.J. del Coz Diaz, et al., Non-linear thermal analysis of light concrete hollow
brick walls by the finite element method and experimental validation, Appl.
Therm. Eng. 26 (2006) 777e786.
[6] Jose-Luis Vivanocos, et al., A new model based on experimental results for
thermal charactarization of bricks, Build. Environ. 44 (2009) 1047e11052.
[7] L.M. Al-Hadhrami, A. Ahmad, Assessment of thermal performance of different
types of masonry bricks used in Saudi Arabia, Appl. Therm. Eng. 29 (2009)
1123e1130.
[8] H. Asan, Y.A. Sancaktar, Effects of wall’s thermophysical properties on time lag
and decrement factor, Energ. Build. 28 (1998) 159e166.
[9] BBC (2009).http://www.bbc.co.uk/weather/bbcweather/weather_forecast_media.
shtml.
[10] Carrier Air Conditioning Company, Handbook of Air Conditioning System
Design. McGraw Hill, New York, 1965.
1928
B.M. Suleiman / Applied Thermal Engineering 31 (2011) 1923e1928
[11] M.S. Hatamipour, H. Mahiyar, M. Taheri, Evaluation of existing cooling systems
for reducing cooling power consumption, Energ. Build. 39 (2007) 105e112.
[12] S.E. Gustafsson, Transient plane source techniques for thermal conductivity and
thermal diffusivity measurements of solid materials, Rev. Sci. Instrum. 62 (1991) 797.
[13] B.M. Suleiman, Moisture effect on thermal conductivity of some major elements
of a typical Libyan house envelope, J. Phys. D: Appl. Phys. 39 (2006) 547e551.
[14] Suleiman Bashir M. (1993). The transient plane source technique for
measurement of thermal properties of polycrystalline ceramics including
high-Tc superconductors, Ph.D. Thesis, ISBN 91-7032-905-2, Physics Department, Chalmers University of Technology, Gothenburg, Sweden.
[15] A free worldwide data calculation site on Heating & Cooling Degree
Days.http://www.degreedays.net [accessed 03.01.11.].
[16] G.H. Galbraith, Jintang Li, G. Jiansong, David Kelly, R. McLean, Grunewald
J. Craig, Evaluation of discretized transport properties for numerical modeling
of heat and moisture transfer in building structures, Journal of Thermal
Envelope and Building Science 24 (3) (2001) 240.
[17] M. Ciampi, F. Fantozzi, F. Leccese, G. Tuoni, On the optimization of building
envelope thermal performance, Civ. Eng. Environ. Syst. 4 (2003) 231e254.
[18] N.K. Bansal, A. Bhattacharya, Parametric equations for energy and load
estimations for buildings in India, Appl. Therm. Eng. 29 (2009) 3710e3715.