Fusion Engineering and Design 65 (2003) 303 /322
www.elsevier.com/locate/fusengdes
The toroidal field coil design for ARIES-ST
W. Reiersen *, F. Dahlgren, H.-M. Fan, C. Neumeyer, I. Zatz,
The ARIES Team
Princeton Plasma Physics Laboratory, Princeton University, James Forrestal Campus, P.O. Box 451, Princeton, NJ 08543, USA
Abstract
An evolutionary process was used to develop the toroidal field (TF) coil design for the ARIES-spherical torus (ST).
Design considerations included fabricability, assembly, maintenance, energy efficiency, and structural robustness.
Design options were identified early in the process. Trade studies were carried out to identify preferred choices. Design
points were re-optimized based on the design choices in the TF and other systems. An attractive design for the ARIESST TF coil system evolved. This design addresses a number of the concerns (complexity) and criticisms (high cost, high
recirculating power) of fusion. It does this by: applying advanced, but available laser forming and spray casting
techniques for manufacturing the TF coil system; adopting a simple single turn TF coil system to make assembly and
maintenance much easier. The single turn design avoids the necessity of using the insulation as a structural component
of the TF coils, and hence, is much more robust than multi-turn designs; using a high conductivity copper alloy and
modest current densities to keep the recirculating power modest.
# 2002 Elsevier Science B.V. All rights reserved.
Keywords: ARIES-ST; Toroidal field; Embrittlement
1. Introduction
The goal of this study was to develop an
attractive toroidal field (TF) coil configuration
for a spherical torus (ST) power plant. The TF
system must be capable of providing a field of 2.14
T at a major radius of 3.2 m and be compatible
with the overall maintenance concepts. Trade
studies conducted to choose between key design
options are described in Section 2. A design
description of the TF coil and power supply
systems is provided in Section 3. System perfor-
* Corresponding author. Tel.: /1-609-243-2479
E-mail address:
[email protected] (W. Reiersen).
mance is described in Section 4. Conclusions of the
study are provided in Section 5.
2. Design options
2.1. Single or multi-turn TF coils
The choice of a single turn or multi-turn TF is
the most critical choice to be made in developing a
TF system for a ST. A single turn configuration
has some marked advantages:
. No turn-to-turn electrical insulation is required.
This results in an improved packing fraction,
reduced shielding requirements, elimination of
0920-3796/02/$ - see front matter # 2002 Elsevier Science B.V. All rights reserved.
PII: S 0 9 2 0 - 3 7 9 6 ( 0 2 ) 0 0 3 0 8 - 3
304
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
concerns about turn-to-turn electrical breakdown, and a stronger mechanical design for the
centerpost due to its monolithic construction;
. Operating voltages are much lower;
. Changes in electrical conductivity over time are
gracefully accommodated by natural current
redistribution within the centerpost.
A multi-turn configuration also has advantages:
. Power supplies and buses are in smaller units.
Joule losses in the power supplies and buses are
lower due to dramatically reduced coil currents
(in the range of tens to hundreds of kiloamperes in a multi-turn TF compared to tens
of mega-amperes for a single turn TF); and
. Compatibility with conventional coil fabrication techniques.
The large conductor currents in the single turn
configuration, while formidable, do not appear
intractable from a power supply standpoint. A
scheme for providing a very high current (multimega-ampere) power supply has been developed.
The scheme uses a large number of diode rectifiers
connected in parallel to provide current to the TF
load.
A single turn centerpost configuration can carry
more current than a multi-turn configuration of
the same radius because of its higher packing
fraction (no insulation, flexible conductor geometry) and reduced shielding requirement (no insulation). Thus, the single turn configuration provides
an upper bound on how economically attractive a
spherical tokamak (ST) power plant might be.
This is the reason it was adopted for the reference
design.
2.2. Centerpost material selection
Nearly pure copper alloys (e.g., C102-OFHC
Cu, C107-Oxygen free with Ag, and C110-Electrolytic Tough Pitch) were commonly the conductors
of choice for early normal (i.e., non-superconducting) tokamaks. Although not as strong as other
copper alloys, they provided adequate strength in
addition to outstanding electrical and thermal
characteristics and were readily available at rea-
sonable cost. For power plant applications, the
requirements are somewhat broader:
. Adequate mechanical properties (strength and
ductility) at end of life;
. Adequate physical properties (swelling, electrical conductivity, thermal conductivity, and
activation) at end of life; and
. Availability in required shapes and sizes.
The centerpost, unless very well shielded, will be
subject to high radiation doses. Potential radiation
effects in the centerpost include embrittlement,
activation, void swelling, irradiation creep, decrease in electrical and thermal conductivity, and
radiation hardening.
2.2.1. Mechanical properties
With the exception of precipitation heat-treated
or dispersion strengthened (DS) copper alloys,
copper must be cold worked to achieve high
strength. This is relatively easy to do with plates
(which are rolled) or wires and rods (which are
drawn), but would be extremely difficult, if not
impossible to perform with uniform properties on
a large assembly such as the centerpost. Furthermore some of the ST cooling options, as discussed
in the following sections, result in centerpost
temperatures in ranges that would anneal (soften)
pure copper and many of its alloys. Precipitation
heat-treated and DS copper alloys are favored for
these reasons.
Copper alloys are available that provide higher
strength (especially at elevated temperatures) but
with reduced electrical and thermal conductivity.
For this study, two alloys were considered */the
precipitation hardened (PH) alloy CuCrZr (with a
nominal composition of Cu-0.65%Cr-0.15%Zr)
and the DS alloy Glidcop AL-15 (with a nominal
composition of Cu-0.15%Al as oxide particles
0.28%Al2O3). These alloys represent two different
classes of materials. Both have been well characterized in a radiation environment as a result of
extensive testing conducted on the international
thermonuclear experimental reactor (ITER)
project. A summary of the material characteristics
for Glidcop AL-15 and CuCrZr is provided in
Table 1.
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
305
Table 1
Material characteristics for Glidcop AL-15 and CuCrZr
Property
Glidcop AL-15
Condition
Electrical
conductivity
Radiation-induced
swelling
As wrought
Solutionized and aged
89% IACS. Degrades under irradiation, primarily due 80% IACS [5]. Degrades under irradiation, primarily due
to Cu transmuting to Ni and Zn [5]
to Cu transmuting to Ni and Zn [5]
Not susceptible to swelling low temperature (B/
Not susceptible to swelling low temperature ( B/150 8C)
150 8C)
Strength
Room temperature, unirradiated (AL-25):
Room temperature, unirradiated:
TYS/435 MPa, UTS/475 MPa [13]
TYS/340 MPa, UTS/410 MPa [13]
Radiation hardens (/150 MPa) above 0.1 dpa at low Radiation hardens (/150 MPa) above 0.1 dpa at low
temperature ( B/150 8C) [3]
temperature (B/150 8C) [3]
Maximum TYS following brazing or welding 350 MPa
[5]
Fatigue
Room temperature, unirradiated */maximum stress at
105 cycles is 300 MPa [5]
Low ( B/10 8/s) at stress levels below 250 MPa and
temperatures below 300 8C [5]
Room temperature, unirradiated */maximum stress at
105 cycles is 250 MPa [5]
Low (B/10 8/s) at stress levels below 250 MPa and
temperatures below 300 8C [5]
Fracture
toughness
Drops markedly with temperature between 25 and
250 8C [12]
Drops slightly with temperature between 25 and 250 8C
[12]
Better than Glidcop AL-15 before and after irradiation
[7]
Embrittlement
Drop in uniform elongation to 0.1 /1% above 0.01 dpa
[3]
Includes 0.28% Al2O3, not a differentiating factor in
the WDR
Drop in uniform elongation to 0.1 /1% above 0.01 dpa
[3]
Includes 0.65% Cr and 0.10% Zr, not a differentiating
factor in the WDR
Normally produced by powder metallurgy techniques,
consolidated by hot extrusion or hot rolling
Feasibility of laser forming appears unlikely */extremely difficult to do with DS copper as the Al2O3
particles would tend to redistribute during the melting
process [7]
Can be cast and heat-treated
Creep
Activation
Fabricability
Both materials exhibit very good strength
(greater than 300 MPa TYS and 400 MPa UTS)
at room temperature in the unirradiated condition.
Because of the complexity of manufacturing the
centerpost, no cold working was assumed for
comparing material properties. The electrical conductivity of Glidcop AL-15 is approximately 90%
IACS at room temperature, significantly higher
than CuCrZr with an electrical conductivity of
approximately 80%.
Irradiation at temperatures below 150 8C
causes hardening in pure copper and PH and DS
copper alloys. Hardening resulting from low
temperature irradiation is accompanied by severe
embrittlement [1] in PH and DS alloys. The
CuCrZr
Compatible with laser forming technique if the material
can be properly heat-treated either during or after the
deposition and shaping process [7]
uniform elongation generally decreases to less
than 1% even at doses as low as 0.01 /0.1 dpa.
The expected peak dose at the centerpost after 1
full power year (FPY) of operation is 12 dpa [2].
Thus, these materials, if used in the centerpost and
irradiated at low temperatures (B/150 8C), would
be brittle.
At temperatures greater than 150 8C, PH and
DS copper alloys remain ductile, with irradiated
elongations in the range of 50 /90% of the
unirradiated values [3]. However, the Joule losses
in the centerpost would be elevated due to the
increase in electrical resistivity with temperature.
The increase in electrical resistivity for OFHC Cu,
Glidcop AL-15, and CuCrZr with temperature is
306
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
Fig. 1. Resistivity of OFHC Cu, Glidcop AL-15, and CuCrZr.
shown in Fig. 1. For CuCrZr, the electrical
resistivity increases by 50% when the temperature
is increased from 20 to 190 8C. To avoid the
higher Joule losses associated with high conductor
temperatures, the inlet temperature for the reference design was set at 30 8C, slightly above
ambient temperature. Peak temperatures were
below 100 8C. Brittle material allowables were
used in evaluating the design. At temperatures less
than 150 8C with stress levels below 250 MPa,
creep is not expected to be an issue. Likewise,
swelling should not be significant at temperatures
less than 150 8C [1].
2.2.2. Physical properties
All copper alloys will be subject to transmutations that decrease the electrical and thermal
conductivity and elevate the waste disposal rating
(WDR). One of the requirements for ARIES-ST is
to limit the WDR of the TF coils to Class C waste
(low-level waste qualified for shallow land burial).
With a 20-cm helium-cooled, ferritic steel shield,
the design life of the centerpost in ARIES-ST is 3
FPY using 10CFR61 limits and 6 FPY using
Fetter limits [4]. The design life of the ferritic
shield structures surrounding the plasma is 3 FPY
so the centerpost would have to be replaced either
every replacement or every second replacement of
the ferritic steel structures, depending on which
limits were used, in order to satisfy WDR requirements. The 10CFR61 WDR is determined mainly
from the long-lived isotopes produced from the Cu
itself (63Ni), not from the alloying elements. The
Fetter WDR is determined mainly from 108mAg,
produced from silver impurities that are not
presently controlled in the material specifications.
In either case, the WDR does not appear to be a
differentiating factor in selecting the conductor
material.
A thinner shield would require more frequent
replacement of the centerpost based on WDR
considerations and result in more nuclear heating
and radiation damage in the centerpost. The
nuclear heating in the centerpost with a 20-cm
shield is approximately 164 MW [2]. This energy is
not recovered because of the low operating tem-
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
perature in the centerpost. The peak radiation
damage in the centerpost is 12 dpa/FPY. After 6
FPY, the peak radiation damage would be 72 dpa.
The dominant transmutation products affecting
the electrical and thermal conductivity are nickel
and zinc [5]. In addition, there is a decrease in
conductivity due to radiation damage. This component appears to saturate at very low radiation
fluence whereas the component due to transmutations is proportional to the radiation fluence. At
the fluence levels calculated in the centerpost at the
end of its useful life, the decrease in conductivity
would be predominantly due to transmutations.
Calculations were performed to assess the
increase in the electrical resistance of the centerpost over time due to transmutations. The results
are shown in Fig. 2 and Fig. 3. Initially, the current
distribution in the centerpost is nearly uniform.
The decrease near the outer edge is due to the
higher temperature resulting from nuclear heating.
Over time, the current density near the outer edge
drops dramatically due to the local increase in
electrical resistivity. The current density in the
center of the centerpost increases to keep the total
307
Fig. 3. Increase in centerpost resistance as a function of time.
current constant. The net effect, as shown in Fig.
3, is that the resistance of the centerpost increases
more than 4% per FPY. After 3 FPY, the centerpost resistance would increase by approximately
12.5%. This represents a decrease in net electrical
power of approximately 33 MW. After 6 FPY, the
centerpost resistance would increase by approximately 23%, resulting in a decrease in net electrical
power of 58 MW. Plant economics appear to favor
Fig. 2. Current density redistribution with accumulated neutron damage.
308
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
replacing the centerpost every 3 FPY (corresponding to the replacement time for the plasma facing
ferritic steel structures) because the centerpost is
relatively inexpensive ($7M), although WDR considerations might allow a 6 FPY replacement time.
2.2.3. Fabricability
The economics of fusion power are driven by the
capital cost of the plant. The cost of the magnet
systems has traditionally been a large element in
the overall capital cost. For ARIES-ST, a study of
low cost fabrication options for the TF system was
performed by the Boeing Company with support
from the AeroMet Corporation [6]. Two low cost
fabrication methods were identified */laser forming for the centerpost and spray casting for the TF
outer shell. The cost of laser forming the centerpost from powdered copper was estimated to be
approximately $8/kg. The cost of spray casting the
outer shell from molten aluminum was approximately $4/kg. Applying these methods substantially lowers the capital cost of the plant.
Use of the laser forming technique for fabricating the centerpost may be a differentiating factor
in selecting the best copper alloy. For Glidcop AL15, a copper alloy which is DS with Al2O3, it
would be difficult to use the current technology for
laser forming as the Al2O3 particles would tend to
redistribute during the melting process. Using a
PH alloy such as CuCrZr may be feasible if the
material could be properly heat-treated either
during or after the deposition and shaping process
[7].
Throughout most of the ARIES-ST study,
Glidcop AL-15 properties were assumed for the
centerpost because of its superior electrical conductivity. Following the fabrication study,
CuCrZr properties were adopted because it appeared more feasible to fabricate the centerpost
using laser forming with this material. However,
from a broad perspective, these two alloys represent a class of materials (high conductivity, high
strength copper alloys, with good fabrication
characteristics) that appears able to meet the
requirements for the centerpost of a low aspect
ratio, tokamak power plant.
2.3. Cooling options
Early in the design of the ARIES-ST TF coil
system, a trade study was conducted to assess
candidate cooling options. Several cooling options
were identified for evaluation:
. Liquid lithium at elevated temperature (200 8C
inlet)
. Water at elevated temperature (180 8C inlet)
. Water at ambient temperature (35 8C inlet)
. Liquid nitrogen (LN2) (80 K inlet)
. Gaseous helium (30 K inlet)
. Gaseous helium (10 K inlet)
A simple power flow model (Fig. 4) for the plant
was constructed for the purpose of evaluating
these options. Organic coolants, commonly used
in process industries in elevated temperature
applications, were not modeled because of their
rapid degradation in a high radiation environment.
A minimum shield thickness of 20 cm was imposed
based on WDR considerations. For the cryogencooled options, the shield thickness was chosen to
minimize the heat load to the refrigerator. An
increased shield thickness reduces the nuclear
heating at the expense of increased Joule heating.
All options are limited to an inlet pressure of 3.47
MPa (500 psi). Coolant velocities were limited to
20 m/s for gaseous helium and 10 m/s for all other
coolants.
Liquid metal cooling was first considered in the
context of an integrated blanket coil (IBC). In the
IBC concept, liquid lithium serves as a breeding
material, a conductor, and a coolant. Calculations
showed that a pure liquid lithium system is
unattractive because of excessive Joule losses.
Using the liquid metal as a coolant inside a copper
conductor can reduce these losses. Glidcop AL-15
was assumed as the conductor material because of
the need to operate at temperatures above the
melting point of lithium (180 8C). A thin steel
sleeve is required between the lithium and the
conductor because of material compatibility issues. An electrically insulating coating must be
applied to the inside of the steel sleeve to reduce
MHD pressure drops to manageable levels. The
option would only be interesting if water cooling
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
Fig. 4. Power flow model for cooling options study.
309
310
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
was not compatible with the blanket or first wall
cooling scheme. The maximum conductor temperature is necessarily high (290 8C), owing to the
high inlet temperature (200 8C) and high temperature drop across the conductor, steel sleeve,
and insulator. Radiation embrittlement should not
be a concern in this temperature range but loss of
fracture toughness is a concern. Joule losses are
70% higher than in a water-cooled coil because of
the higher operating temperature and higher coolant fraction. Even with optimistic assumptions for
energy recovery, the higher Joule losses are only
marginally offset. In addition, the engineering
difficulties associated with the liquid lithium coolant are severe.
Embrittlement due to irradiation at low temperatures (B/150 8C) and loss of fracture toughness at elevated temperatures and in a high
radiation environment (data at 250 8C) are radiation effects relevant to Glidcop AL-15. Water is a
candidate coolant that can be used to keep the
conductor within a 150/230 8C temperature
range without exceeding reasonable pressures or
flow velocities. However, Joule losses will be about
50% higher than when the conductor is cooled
with ambient water. Thus, the ambient water
option is preferred over the warm water option if
stresses in the centerpost can be kept within
allowable limits for brittle materials.
A fourth option is to use copper operating in a
temperature range appropriate for LN2 cooling
(80 /110 K). The resistivity of copper drops
substantially from room temperature to 80 K, in
the ratio of approximately 7.7:1, so there is an
incentive for operating at lower temperatures.
However, in order to minimize the heat load to
the refrigerator, the shield thickness has to be
increased from 20 to 44 cm. The peak TF field
increases to 8.8 T and the conductor current
density to 2.1 kA/cm2. The Joule heating in the
centerpost drops from 300 to 76 MW, even with
the smaller centerpost radius. The nuclear heating
in the centerpost drops from 158 to 35 MW.
Nevertheless, the net electric power drops to 423
MW (far less then the nominal 1000 MW for the
ambient water-cooled option) because of the poor
thermodynamic efficiency in removing heat at 80
K, approximately 7 W per watt removed.
Another option is to use copper operating in the
temperature range of 30/50 K using gaseous
helium. The resistivity of copper drops substantially from room temperature to 30 K, in the ratio
of approximately 100:1, so there is incentive for
operating at temperatures even lower than 80 K.
In order to minimize the heat load to the
refrigerator, the shield thickness has to be increased to 66 cm. The peak TF field increases to
11.5 T and the conductor current density to 4.1
kA/cm2. The Joule heating in the centerpost drops
to 15 MW. The nuclear heating in the centerpost
drops to 9 MW. Nevertheless, the net electric
power is still only 388 MW because of the very
poor thermodynamic efficiency in removing heat
at 30 K, approximately 37 W per watt removed.
The resistivity of copper becomes independent
of temperature at temperatures below /20 K.
Copper also exhibits a strong magneto-resistance.
For temperatures less than 20 K, the magnetoresistance for high conductivity copper (RRR /
100) is dominant above 4 T. Aluminum exhibits a
much weaker magneto-resistance than copper that
saturates with increasing field. Thus, high purity
aluminum is often proposed as a conductor in very
low temperature (B/20 K), high field applications.
Using high purity aluminum conductor in the
temperature range of 10/20 K appears optimal
based on a minimization of the product of the
resistivity and the Carnot work (Wc /(Th/Tc)/Tc
in W/W). The average resistivity is assumed to be
0.008 mV cm with an average field of 9.7 T. This is
lower than RT copper by the ratio of 215:1. The
zero field resistivity for this high purity (99.999%
pure) aluminum is 0.0009 mV cm at 15 K and has a
RRR exceeding 5000 at 4 K. The high purity
aluminum conductor can be cooled with gaseous
helium. In order to minimize the heat load to the
refrigerator, the shield thickness has to be increased to 80 cm. The peak TF field increases to
14.5 T and the conductor current density to 5.5
kA/cm2. The Joule heating in the centerpost drops
to 5.0 MW. The nuclear heating in the centerpost
drops to 3.8 MW. Nevertheless, the net electric is
still a meager 57 MW because of the extremely
poor thermodynamic efficiency in removing heat
at 10 K, approximately 119 W per watt removed.
The bottom line is that the cryogen-cooled options
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
do not appear to offer any improvement over the
water-cooled and Li-cooled options based on
thermodynamic efficiencies for the design point
used in this study. Cryogen-cooled options also
appear to be much more complex.
The conclusion of the study of alternate cooling
options was that none of the options, which
ranged from gaseous helium at 10 K to liquid
lithium at 200 8C, appeared superior to ambient
water cooling when thermodynamic efficiency and
design simplicity are taken into account.
3. Design description
3.1. TF coil system design
The configuration concept for the single turn
coil system adopted for ARIES-ST is illustrated in
Fig. 5. The configuration features a tall centerpost
that is oriented along the major axis of the
machine. The centerpost is connected to an outer
shell that surrounds the first wall, blanket, shield,
divertors, and PF coils. The TF system provides
the primary vacuum boundary for the machine.
The centerpost is designed to be physically
separable from the power core assembly. The
bottom portion of the centerpost is a thick
cylinder. It is electrically connected to the outer
Fig. 5. Isometric view of TF coil system.
311
shell by sliding joints. The centerpost and outer
shell are keyed together in this location, permitting
relative motion radially and vertically while keeping them registered toroidally. Numerous concepts
for sliding electrical contacts have been developed,
tested, and even deployed for fusion applications.
These concepts include; Feltmetal pads (used on
C-Mod and proposed on MAST), Multilam sliding contacts [8], and spring-loaded, in-line contacts
[9]. Liquid metal joints have also been considered.
For this study, a sliding joint utilizing Feltmetal
pads was assumed in developing the configuration
concept. In addition to easing assembly and
maintenance, the sliding joints significantly reduce
axial stresses in the centerpost. This is a very
important feature, since the centerpost will be
come embrittled during operation.
The centerpost transitions from a large diameter
(3.2 m) cylinder at the bottom to a smaller
diameter (1.8 m) cylinder between the upper and
lower divertors. This is the region of high current
density, accounting for most of the Joule losses.
Flaring the centerpost on top as it is on the bottom
would have trapped the centerpost with the power
core assembly. Instead, the flaring is incorporated
into the upper section of the outer shell. The
centerpost has a conical shape above the upper
divertor assembly where it is pulled against a
mating surface in the outer shell for electrical
continuity. Gravity support of the centerpost and
the preload for the required contact pressure
between the upper part of the centerpost and outer
shell are provided where the centerpost penetrates
the top of the outer shell. This arrangement allows
the centerpost to be removed either without
disturbing the power core assembly or as part of
the power core assembly, as shown in Fig. 6. It
also minimizes Joule losses by restricting the
region of high current density to the cylindrical
section between the upper and lower divertors.
Since the TF provides the primary vacuum
boundary, there are bellows connections above
and below the outer shell where the centerpost
penetrates the outer shell to provide vacuum seals.
The outer shell is segmented into three pieces, as
shown in Fig. 5. The lower section of the outer
shell provides the gravity support for the power
312
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
Fig. 6. Paths for centerpost removal.
core assembly, including the first wall, blanket,
inboard shield, divertors, and lower PF coils. The
lower section is in turn supported by removable
supports from below. The upper section extends
from the centerpost to the outboard midplane. At
the outboard midplane, there is a joint between the
upper section and middle section. The upper and
middle sections are bolted together with an
electrically insulating material in between. A
bellows-type connection (with an insulating break)
on the inside of the outer shell provides the
vacuum barrier across the joint. The TF leads
connect to the upper and middle sections at eight
equally spaced toroidal locations.
The middle section of the outer shell is connected to the lower section at approximately the
same elevation as the lower divertor. At this
elevation, the major radius of the joint is adequate
to permit vertical removal of the power core. This
joint provides the electrical continuity between the
middle and lower sections. For removal of the
bottom section of the outer shell and power core,
the bellows connection is cut and the joint
unbolted. The connections between the centerpost
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
and upper section of the outer shell must also be
undone. The middle section of the outer shell is
supported off the floor of the test cell. These
supports bear the gravity loads of the middle and
upper sections of the outer shell, the centerpost,
and the upper PF coils attached to the outer shell.
When fully assembled, the outer shell provides a
continuous shell that is effective in reacting both
in-plane and out-of-plane electromagnetic loads.
In additional to the centerpost, penetrations will
be required for helium cooling in the power core,
the Li /Pb breeding material, vacuum pumping,
neutral beam injection, and PF coil services. Some
diagnostic penetrations are also likely to be
required. Vacuum seals and electrical isolation
will be provided at all these locations.
ARIES-ST features a set of five pairs of PF coils
located symmetrically about the horizontal midplane, as shown in Fig. 7. The PF coils are
supported by the outer shell or shield. The coil
supports permit relative motion radially but not
vertically. Thus, only gravity and vertical electromagnetic loads are transmitted through the PF coil
supports.
3.2. TF power system design
In order to minimize Joule losses in the leads,
the TF power supplies have to be located as close
to the TF coils as possible. A cylindrical biological
shield is provided at a major radius of approximately 13 m. The concrete shield is greater than 2m thick. The TF power supplies are located just
outside this shield.
The large conductor current (34 MA) in the
single turn configuration, while formidable, does
not appear intractable from a power supply
standpoint. One possible scheme for providing a
high current power supply has been developed.
The overall configuration is depicted in Fig. 8.
Power is taken from a high voltage bus. During
the charging of the load, power is fed through a
step down transformer such that, after additional
step down through converter transformers and DC
rectification, the required DC charging voltage is
obtained. After charging, an AC bus transfer takes
place such that the charging transformer is excluded and the holding transformer is included.
313
The holding transformer ratio is such that the
required DC holding voltage is obtained. Additional features could be included to regulate the
AC voltage applied to the converter transformers,
and hence, the DC voltage, if required, rather than
provide two discrete levels. Or, a single step down
transformer could be used and additional regulation features could be included to cover the range
of required DC voltage.
A large number of diode rectifiers are connected
in parallel to provide current to the load. The basic
rectifier unit is shown in Fig. 9. It is based on a 6pulse midpoint topology with interphase reactor.
This topology is commonly used for high current
rectifiers. It is preferred because there is only one
diode in series with the load current (and therefore
only one diode voltage drop), and the diode
conduction duty is 1208 (1/3 of a cycle). By
adjusting the phase shifting of the converter
transformers, 12- and 24-pulse behavior of the
parallel connected groups of converters can be
obtained to reduce AC and DC side harmonics.
Current limiting reactors (CLRs) and explosively actuated (pyro) fuses are connected in series
with groups of the basic rectifier units as depicted
in Fig. 8. The purpose of the CLR is to limit the
rate of rise of fault current fed into any one
rectifier group in case it suffers a short circuit. The
purpose of the pyro fuse is to isolate the faulty
rectifier group. In practice, the CLR may not be
required as a discrete component; rather the
inductance of the bus bar system may be tailored
to provide the needed inductance. It may be
possible to use a conventional type of fuse instead
of a pyro fuse, but this requires more design
development and study. The voltage is low and
the clearing time (as will be described further on
herein) is not unusually short. However, the duty
would be DC, which could be problematic.
The best location for inductance and fuses needs
to be evaluated by further design development and
study. Considering that the bus bar system would
consist of a radial tree structure starting with 8
parallel branches and ending in thousands, there
are many opportunities for placement and many
issues to consider.
The use of a modern large device (Powerex
RBS8) was evaluated as a possible commercial
314
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
Fig. 7. TF coil system elevation view.
diode for this type of application. Voltage drop
characteristics from the data sheet were fit to a
curve as shown in Fig. 10. An average diode
current of 3 kA was selected so as to produce a
reasonable operating temperature (126 8C is less
than the maximum temperature of 150 8C for a
diode) considering the conduction duty (1/3 cycle),
power dissipation, and likely heat sink characteristics. Diode voltage drop at peak 3-pulse bridge
current (9 kA) is roughly 1.0 V. This would be the
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
Fig. 8. Overall power supply scheme.
resistive voltage drop across the bridge. Assuming
typical characteristics of the AC source impedance, short circuit current of each 6-p bridge
would be roughly 5 times rated current, 5/9/
2 /90 kA.
With a 34.3 MA load, the total number of diodes
required would be 11 400. If only one diode path
was included in each rectifier bridge leg then the
total number of 6-p bridges (3-p pairs) would be
1900. For comparison, the TFTR power supply
system uses 7488 thyristors. So, the number of
diodes required here is 50% more, but the diodes are
much simpler passive devices compared to thyristors.
Total losses in the diodes are on the order of 34
MW. Total prospective short circuit current from
315
the power supply is 5/34 /170 MA. Clearly the
bus bar layout and physical separation must be
designed to absolutely prevent a short circuit, with
the level of criticality increasing as one moves
through the radial branches of the tree toward the
final connection to the load.
In case a diode suffers a short circuit, it must be
isolated by the pyro fuse, and it is important that
the I2t be limited to a value such that the diode
does not rupture (explode). For the selected diode,
this value is 1.5 /107 A2 s. Assuming the power
supply produces 10 VDC, a 1 mH inductance
between the faulty diode and all of the other
power supply feeding it would be sufficient to limit
the rate of rise of current such that more than 5 ms
would be available to achieve the isolation prior to
reaching the limiting I2t. This should be adequate
to sense and interrupt. Probably, the sensing
would be based on dI/dt being abnormally high
in such a case. Also, the maximum current would
be less than the inherent short circuit current of the
bridge (mentioned earlier) for which it would have
to be braced in any case.
There may be opportunities for reducing the
losses in the diodes, and for using fewer diodes, by
immersing them in LN2.
4. System performance
4.1. Electrical characteristics
Electrically, the TF system has only a single
turn. A current of 34.3 MA is required to satisfy
Fig. 9. Six-pulse midpoint converter with interphase reactor.
316
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
Fig. 10. Diode voltage drop characteristics.
the TF requirement of 2.14 T at 3.2 m. The voltage
drop across the TF coil system is 8.5 V, corresponding to Joule losses of 291 MW. The Joule
losses occur predominantly in the centerpost (242
MW) with the balance occurring in the outer shell
(31 MW) and bus (19 MW). The current density in
the centerpost conductor at the midplane is 1.47
kA/cm2. The electrical resistivity of CuCrZr is 80%
IACS and varies with temperature as shown in
Fig. 1.
The outer shell is constructed of a 5000 series
aluminum alloy. This class of conductor was
chosen because the outer shell can be fabricated
using a spray casting technique. There are alloys in
this series that exhibit good electrical conductivity
(/3.7 mV cm) and weldability. The outer shell
thickness is approximately 0.7 m. This thickness
results in low stresses, low current density in the
outer shell (0.07 kA/cm2), and low Joule losses (31
MW).
A feature of this configuration concept is the
sliding joint that provides electrical continuity
between the bottom section of the centerpost and
the lower section of the outer shell. The sliding
joint is located at a radius of 1.6 m and has a
height of 3.6 m. The sliding joint concept is
patterned after C-Mod and MAST, utilizing
Feltmetal pads. One key design criterion for the
joint is the current density. Guidance received
from the MAST project [10] based on their testing
was to keep the current density in the Feltmetal
pads below 1 kA/cm2 for steady state applications.
At a radius of 1.6 m, it should be possible to fit 200
joints (with 2 pads per joint) around the circumference of the interface. Because the sliding joint is
located near a sharp corner, the current distribution is peaked near the corner with a 4:1 peaking
factor. Nevertheless, the peak current density in
the Feltmetal pads is an acceptable 0.8 kA/cm2.
The stored energy in the TF coil system is 6.2
GJ. In the event of a LOCA incident during which
all coolant flow to the TF was lost, the temperature rise in the centerpost would be a modest
32 8C due to dissipation of the stored energy. For
prolonged periods without any cooling in the
centerpost, the temperature rise due to the afterheat in the centerpost needs to be considered. The
calculated peak temperature of 1018 8C should
not be large enough to jeopardize plant safety by
volatilizing activated particulates. However, the
temperature excursion in the centerpost might well
put the capital investment at risk. For this reason,
provisions for auxiliary cooling of the centerpost
for removal of the modest afterheat (:/2 kW
maximum) should be made.
Fig. 11. TF centerpost cross-section view.
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
4.2. Thermal/hydraulic performance
The centerpost is cooled with water with a
30 8C inlet temperature, slightly above ambient
temperature. The water is fed in at the top and
exits at the bottom. The feed on top was chosen to
minimize thermal stresses across the contact interface between the centerpost and outer shell. The
top plenum feeds 386 individual circular cooling
passages that are collected in a plenum at the
bottom. Each cooling passage has a diameter of
approximately 2.6 cm with an average spacing of
9.2 cm. A cross-section view of the TF centerpost
at the midplane is shown in Fig. 11. The coolant
holes are more closely spaced towards the plasma
because that is where the nuclear heating is
localized. The coolant fraction is approximately
8.3% at the midplane of the centerpost.
The heat load to be removed from the centerpost during initial operation is approximately 406
MW, consisting of 242 MW of Joule heating and
164 MW of nuclear heating. The coolant velocity
was limited to 10 m/s to avoid excessive erosion.
The required flow rate is 2155 kg/s with an outlet
temperature of 75 8C. To achieve this flow rate,
the required inlet pressure is a modest 1.36 MPa
with an outlet pressure of 0.15 MPa. The average
conductor temperature at the midplane is approximately 33 8C higher than the bulk temperature of
the coolant due to an 18 8C film temperature rise
and a 15 8C temperature rise across the conductor. The Joule heating in the centerpost increases
by 33 MW after 3 FPY. With the same flow rate,
the outlet temperature increases by 4/79 8C.
The heat load to be removed from the outer
shell is low (70 MW) [2]. Nuclear heat loads in the
outer shell are /21 MW in the lightly shielded
collar and only 18 MW elsewhere. The 70 MW
total heat load is removed by water flowing
through stainless steel tubes embedded in the
spray cast outer shell.
4.3. Structural analysis
A preliminary structural analysis of the ARIESST TF coil system was performed using the
ANSYS code. ANSYS is a convenient choice
because the code calculates the current distribution
317
in the TF coil, the resulting electromagnetic loads,
and the associated stress distribution as part of one
package. The ANSYS model included the PF coils
and plasma in its calculation. The PF coils and
plasma cause out-of-plane (toroidal) forces in the
TF centerpost and outer shell due to interactions
between their poloidal fields and the TF current.
In addition, vertical loads on the PF coils attached
to the outer shell produce mechanical loads on the
TF outer shell at the point of attachment.
Two options for supporting the centerpost were
explored:
1) Let the centerpost be free to expand vertically
and radially at the bottom where the centerpost penetrates the outer shell. No relative
torsional displacements would be permitted.
2) Tie the centerpost to the outer shell at the
bottom, allowing no relative vertical or torsional displacements. Relative radial displacements would still be permitted.
The first option was chosen as the baseline
because it is the simplest and it appears to work
acceptably well. Thermal growth of the centerpost
is not an issue because the centerpost is not
vertically constrained. In the second option, the
thermal growth is vertically constrained. This
feature might actually prove advantageous and
make the second option more attractive than the
first. It would reduce the peak VonMises stress in
the centerpost, put the centerpost in a state of triaxial compression, increase the contact pressure
across the joint between the centerpost and outer
shell at the top, and would have no relative vertical
displacement at the bottom to complicate the
sliding joint design and cooling connections to
the centerpost.
The centerpost is subject to radial, compressive
loads due to the vertical TF current crossing the
TF. These radial loads result in stresses in the
toroidal direction, i.e., hoop stresses, that range
from 16 MPa (compression) at the outer surface to
60 MPa (compression) in the center, as shown in
Fig. 12. In addition, there is a vertical separating
force on the centerpost due to radial currents near
the ends of the centerpost crossing the TF. Because
the diameter of the centerpost is larger at the
318
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
Fig. 12. TF coil hoop stress contours.
bottom than at the top, there is also a net
downward vertical force on the centerpost. The
net vertical load is reacted where the centerpost is
attached to the outer shell at the top. Sufficient
preload must be provided at this attachment to
maintain adequate contact pressure across the
joint, which provides electrical continuity between
the centerpost and outer shell.
In the first option, the centerpost is free to
expand vertically. Vertical forces on the centerpost
result in axial tensile stresses ranging from 24 MPa
(tension) in the center to 46 MPa (tension) at the
outer surface of the centerpost, as shown in Fig.
13. Note that the axial stresses are smaller in
magnitude and opposite in sign to the hoop
stresses. Note also that they peak on the outer
surface whereas the hoop stresses peak in the
center. The VonMises stress in the centerpost is
fairly uniform along its length, ranging from 55
MPa at the outer surface to 76 MPa in the center,
as shown in Fig. 14. Stresses in the outer shell are
low everywhere, with a VonMises stress less than
21 MPa except in a very local region near the
corner by the collar where the stresses are less than
30 MPa.
The continuous outer shell is ideal for resisting
both in-plane and out-of-plane loads. The absence
of turn-to-turn insulation in a single turn coil
design removes the traditional weak link for
stresses arising from out-of-plane loads. The only
electrical insulation is at the outboard midplane.
Interlaminar shear stresses are very low in this
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
319
Fig. 13. TF coil axial stress contours.
region, less than 4 MPa. More detailed design and
analysis are required to quantify stresses due to
out-of-plane loads where the centerpost interfaces
with the outer shell at the top and bottom.
In the second option, the bottom of the centerpost is tied to the outer shell, so it is not free to
expand vertically. This does not substantially
change the stresses due to EM loads. However,
there is a substantial change in thermal stresses.
The only element that has a substantial temperature gradient is the centerpost. The inlet temperature for the coolant is nominally 30 8C at the top
with an outlet temperature of 75 8C at the
bottom. Temperature differences across the outer
shell are small because of the shorter coolant path
lengths and much lower current density. The
centerpost tends to grow thermally whereas the
outer shell does not. However, in the second
option, the axial displacements at the bottom are
forced to be equal. This causes an axial thermal
stress in the centerpost of 38 MPa (compression).
Because the axial thermal stress is opposite in sign
to the axial stress arising from the EM loads, the
peak axial stress in the center of the centerpost
changes from approximately 46 MPa (tension) in
the first option to 20 MPa (compression) in the
second option. This reduces the peak VonMises stress from 76 to 44 MPa. In the second
option, the centerpost is in a state of tri-axial
compression.
320
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
Fig. 14. TF coil VonMises stress contours.
The development of structural design criteria for
fusion materials and applications has been an
ongoing activity for the past two decades. Recent
work has been done under the auspices of the
ITER project. For calculating allowable stresses in
the ARIES-ST design, the ITER criteria [11] were
followed. In general, for structural materials, the
design Tresca stress value, Sm, at design temperatures less than 500 K shall be the lower of 2/3 Sy
(yield strength) or 1/2 Su (ultimate tensile strength)
as long as the reduction of area at fracture is
greater than 40%. For materials where this is not
satisfied, a lower allowable stress limit should be
considered in view of possible brittle behavior. A
suggested guideline is a more conservative value of
Sm set at 1/2 Sy. Based on elastic analysis, the
stress limits are:
. 1.0 KSm for primary membrane stresses
. 1.3 KSm for primary membrane plus bending
stresses
. 1.5 KSm for primary plus secondary stresses
The appropriate K values in the base metal for
various load combination categories are
. For normal operating conditions, K /1.0
. For anticipated conditions, K /1.1
. For unlikely conditions, K /1.2; evaluation of
secondary stress not required
. For extremely unlikely conditions, K /1.3;
evaluation of secondary stress not required
Clearly, at least in the outer half of the centerpost (at a radius greater than 0.5 m), the material
will be embrittled within 3 FPY. For primary
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
membrane stresses under normal operating conditions, the allowable stress would be 1/2 Sy. High
strength, high conductivity copper alloys tend to
radiation harden in this temperature range. For
conservatism, we assumed unirradiated strength
properties. A wide range of strength properties is
quoted in the literature for CuCrZr, depending on
the thermo-mechanical history of the material. For
calculating the allowable stress in the centerpost,
we assumed a yield strength of 350 MPa, which is
consistent with the maximum yield strength that
might be expected following a welding or brazing
operation [5]. The allowable primary membrane
stress would be 175 MPa. The peak VonMises
stress (which approximates the Tresca stress) in the
first option is 76 MPa or 43% of the allowable
primary membrane stress. The peak VonMises
stress in the second option is 44 MPa or 25% of the
allowable primary membrane stress. Thus, it does
not appear that primary stresses will be limiting.
Based on the ITER criteria, no stress (primary
plus secondary) can exceed 1.5 KSm. For normal
operation, the allowable stress for this combination of stresses in the centerpost would be 3/4 Sy or
262 MPa. Stress concentrations around cooling
holes in the range of 2/3 can be expected. This
would result in a hoop stress of 120/180 MPa
(compression) around the cooling holes in the
center of the centerpost, rather than the average
value of 60 MPa (compression). Thermal stresses
can also be expected due to temperature gradients
around the cooling holes. The magnitude of these
stresses is estimated to range from 33 MPa
(tension) around the cooling holes to 15 MPa
(compression) away from the cooling holes. Note
that the thermal stress is opposite in sign to the
hoop stresses that peak around the cooling holes,
thereby offsetting their impact. More detailed
design and analysis and better material property
data for laser formed conductor are required to
make definitive judgements about the acceptability
of the stresses for the TF coil design. However,
these increments appear small relative to the
margin between the allowable stress of 262 MPa
and the calculated primary membrane stress values
of 76 and 43 MPa for the first and second options,
respectively. Therefore, it appears promising that
321
adequate structural margin exists for the ARIESST TF coil system design.
5. Conclusions
The ARIES-ST TF design is based on a single
turn construction consisting of a stepped cylindrical centerpost along the major axis and a
toroidally continuous outer shell. High strength,
high conductivity copper alloys operating at low
temperatures (between room temperature and
100 8C) appear to be interesting candidates for
use in the centerpost. Irradiation in this temperature range causes radiation hardening and embrittlement. However, stresses in the centerpost
appear low enough to satisfy brittle material
allowables. Swelling and creep are not issues at
these low temperatures and stresses. The key
consideration in selecting the copper alloy to be
used in the centerpost may be the fabrication
method. Using the laser forming technique identified by Boeing for fabricating the centerpost
strongly favors a PH alloy such as CuCrZr over
a DS alloy such as Glidcop AL-15. The outer shell
is fabricated with a high conductivity aluminum
alloy using a spray casting technique.
The centerpost and outer shell are both watercooled with an inlet temperature appropriate for
ambient heat removal, nominally 30 8C. Trade
studies were conducted to assess other options for
cooling, ranging from gaseous helium at 10 K to
liquid lithium at 200 8C. None of these options
appeared superior to ambient water cooling based
on expected thermodynamic efficiencies or design
simplicity.
The centerpost lifetime appears to be limited by
economic considerations. For ARIES-ST, disposal
of the centerpost as Class C waste requires
replacement every 6 FPY (using Fetter limits),
which is every second replacement of the ferritic
steel structures facing the plasma. Transmutations
will result in an increase in Joule losses of
approximately 12.5% after 3 FPY. Because the
centerpost is relatively inexpensive (B/$7M), economic considerations appear to favor replacement
322
W. Reiersen et al. / Fusion Engineering and Design 65 (2003) 303 /322
more frequently, i.e., concurrent with every replacement of the ferritic steel structures facing the
plasma. The TF coil system is designed to be
compatible with vertical maintenance from below.
The centerpost can be removed separately or as
part of the power core assembly. The outer shell is
divided into three segments. The upper and middle
segments are permanent structures, designed for
the life of the plant and not removed with the
power core assembly. The lower segment of the
outer shell provides support for the power core
assembly and although designed for the life of the
plant, is removed for replacement of the power
core assembly. The TF coil system provides the
primary vacuum boundary for the plasma and for
superconducting PF coils inside the outer shell.
Vacuum seals are provided at all penetrations.
The TF coil system is powered by a high current
(34 MA), low voltage (8.5 V across the TF leads)
power supply. Joule losses in the system are 291
MW, predominantly in the centerpost. Because of
the high current, large bus cross-sections are
required to keep the Joule losses in the bus low.
The power supply must be located as close to the
TF coil system as possible.
The TF coil system design addresses a number
of the concerns (complexity) and criticisms (high
cost, high recirculating power) of fusion. It does
this by:
. Applying advanced, but available laser forming
and spray casting techniques for manufacturing
the TF coil system.
. Adopting a simplified single TF coil system to
make assembly and maintenance much easier.
The single turn design also avoids the necessity
of using the insulation as a structural component of the TF coils, and hence, is much more
robust than multi-turn designs.
. Using high conductivity copper and modest
current densities to keep the recirculating power
modest.
References
[1] S.A. Fabritsiev, S.J. Zinkle, B.N. Singh, Evaluation of
copper alloys for fusion reactor divertor and first wall
components, J. Nucl. Mater. (1996).
[2] L. El-Guebaly, ARIES Team, ARIES-ST Nuclear Analysis and Shield Design, Fusion Eng. Des., in press.
[3] S.A. Fabritsiev, A.S. Pokrovsky, S.J. Zinkle, D.J. Edwards, Low temperature embrittlement of copper alloys, J.
Nucl. Mater. September (1996).
[4] H.Y. Khater, E.A. Mogahed, D.K. Sze, et al., ARIES
Team, ARIES-ST Safety Design and Analysis, Fusion
Eng. Des., in press.
[5] S.J. Zinkle, S.A. Fabritsiev, Final Report to US Home
Team for 1994 ITER R&D Task T7: Assessment of
Copper Alloys for High Heat Flux Applications.
[6] L.M. Waganer, D.A. Deuser, K.T. Slattery, et al., UltraLow Cost Coil Fabrication Approach for ARIES-ST,
Fusion Eng. Des., in press.
[7] M.C. Billone, Materials Input for the ARIES-ST Design
Program, in: Fusion Materials Semiannual Progress Report for the Period Ending December 1998, US Department of Energy report DOE/ER-0313/24, 1999.
[8] F. Puhn, et al., Mechanical Design of a High-Beta TFCX
Tokamak with a Demountable TF Coil, in: Proceedings of
13th Symposium on Fusion Technology (SOFT), Varese,
Italy, September, 1984.
[9] Holt Murray, High Current Density, Cryogenically Cooled
Sliding Electrical Joint Development, PPPL-2370, September, 1986.
[10] G. Voss, Culham Laboratorties, United Kingdom, private
communication, 1999.
[11] ITER Design Criteria, June 1, 1995.
[12] D.J. Alexander, S.J. Zinkle, A.F. Rowcliffe, Fracture
Toughness of Copper-Base Alloys for ITER Applications,
in: Fusion Materials Semiannual Progress Report for the
Period Ending December 1998, US Department of Energy
report DOE/ER-0313/24, 1999.
[13] J.W. Davis (Ed.), ITER Material Properties Handbook,
ITER Doc. S74-RE-1-97-08-01 W1.5, August, 1997.