ARTICLE IN PRESS
Energy Policy 37 (2009) 3650–3658
Contents lists available at ScienceDirect
Energy Policy
journal homepage: www.elsevier.com/locate/enpol
Energy and emission analysis for industrial motors in Malaysia
R. Saidur a,, N.A. Rahim b, H.W. Ping b, M.I. Jahirul a, S. Mekhilef b, H.H. Masjuki a
a
b
Department of Mechanical Engineering, University of Malaya, 50603 Kuala Lumpur, Malaysia
Department of Electrical Engineering, University of Malaya, 50603 Kuala Lumpur, Malaysia
a r t i c l e in f o
a b s t r a c t
Article history:
Received 9 February 2009
Accepted 16 April 2009
Available online 19 May 2009
The industrial sector is the largest user of energy in Malaysia. Industrial motors account for a major
segment of total industrial energy use. Since motors are the principle energy users, different energy
savings strategies have been applied to reduce their energy consumption and associated emissions
released into the atmosphere. These strategies include using highly efficient motors, variable speed
drive (VSD), and capacitor banks to improve the power factor. It has been estimated that there can be a
total energy savings of 1765, 2703 and 3605 MWh by utilizing energy-efficient motors for 50%, 75% and
100% loads, respectively. It was also found that for different motor loads, an estimated US$115,936
US$173,019 and US$230,693 can be saved in anticipated energy costs. Similarly, it is hypothesized that a
significant amount of energy can be saved using VSD and capacitor banks to reduce speed and improve
the power factor, thus cutting energy costs. Moreover, a substantial reduction in the amount of
emissions can be effected together with the associated energy savings for different energy savings
strategies. In addition, the payback period for different energy savings strategies has been found to be
reasonable in some cases.
& 2009 Elsevier Ltd. All rights reserved.
Keywords:
Industrial motors
Energy savings
Emission reduction
1. Introduction
There has been a growing concern recently about energy
use and its adverse impact on the environment. Most of the
developing countries shifted from agriculture to industrialization
and urbanization within a process of economic growth and
development over the last few decades. Energy losses in a large
number of industries exist, and potential for energy efficiency
improvements is evident (Mohsen and Akash, 1998). Among the
various sectors contributing to greenhouse gas (GHG) emissions,
the contribution of the industrial sector is significant. Thus,
lowering GHG emissions from the industrial sector offers the
means of reducing overall GHG emissions. Energy conservation
means less reliance on energy imports and, thus, less GHG
emissions. Previous studies have reported that implementing a
few select options at little or no cost in the industrial sector could
reduce GHG emissions by 10–30% of GHG emissions (Ghaddar and
Mezher, 1999; IPCC, 1996).
In Malaysia, the industrial sector was found to be major user of
energy. It accounted for some 48% of total energy use in 2007, as
shown in Fig. 1 (EC, 2007). The increased use of energy raised
serious concerns in the Malaysian government about the need
to overcome heightened energy expenditure by promoting the
end-use energy efficiency, which means using less energy while
Corresponding author. Tel.: +60 3 79674462; fax: +60 3 79675317.
E-mail address:
[email protected] (R. Saidur).
0301-4215/$ - see front matter & 2009 Elsevier Ltd. All rights reserved.
doi:10.1016/j.enpol.2009.04.033
maintaining the same level of service. It can be achieved either by
reducing total energy use or by increasing the production rate per
unit of energy used. On the other hand, improving energy
efficiency is the key to reduce greenhouse gas emissions.
Therefore, energy research organizations and governments are
actively engaged in developing methods of assessing energy
efficiency. This assessment can provide a basis for establishing
energy policy and can help in reducing GHG emissions. One way
to achieve more efficient use of final energy in an industry is to
determine the precise amount of energy used and identifiable
energy losses. Various types of equipment and devices that use
energy at varying levels of efficiency depend on the characteristics
and working conditions (Fromme, 1996; Ibrik and Mahmoud,
2005; Priambodo and Kumar, 2001; Thollander et al., 2005; Chan
et al., 2007). Energy use performances and energy efficiency in
industry have also been studied in various countries (Ozturk,
2005; Christoffersen et al., 2006; Subrahamanya, 2006).
Comprehensive literature on electrical motor energy savings,
policy and technology can be found in a handbook written by
Nadel et al. (2002). In Slovenia, the industrial sector consumes
about 52% of total electrical energy (Al-Mansour et al., 2003). In
Turkey, about 35% of total energy is used in the industrial sector
(Onut and Soner, 2007). Approximately half of the total generated
electricity in the UK is used to drive electrical motors. This means
that efficiency improvements to electrical machines can have a
very large impact on energy consumption (Mecrow and Jack,
2008). Motor-driven systems account for approximately 65% of
the electricity used by industry in the European Union (Anon,
ARTICLE IN PRESS
3651
R. Saidur et al. / Energy Policy 37 (2009) 3650–3658
Hr
ISIC
L
0.746
n
PF
P
Savings
SSR
Nomenclature
AES
annual energy savings
AFD
adjustable frequency drive
c
average energy cost (US$/kWh)
energy-efficient motor efficiency rating (%)
Eee
EF
emission factor (kg/kWh)
ER
emission reduction in kg
standard motor efficiency rating (%)
Estd
energy savings with the application of VSD
ESVSD
GDP
gross domestic products
GHG
greenhouse gas
Havg_usage annual average usage hours
HEM
high efficiency motor
HP
motor rated horsepower
TNB
VAV
VFD
VSD
2004). In Jordan, the industrial sector consumes about 31% of total
energy (Al-Ghandoor et al., 2008).
In Malaysia, about 48% of total energy is used to drive
industrial motors, as shown in Fig. 2 (Saidur et al., 2009). In
many industrialized countries, more than 70% of the total energy
is consumed by electric motors. Therefore, the cost of energy to
operate motors has become a real concern for industry (Akbaba,
annual operating hours
international standard industrial classification
load factor (percentage of full load)
conversion factor from horsepower to kW
number of motors
power factor
motor power (kW)
expected annual bill savings (US$)
percentage energy savings associated certain percentage of speed reduction
tenaga nasional Berhad
variable air volume
variable frequency drive
variable frequency drive
1999). The energy consumed to drive electric motors used in
industrial plants is about 65% of the total energy consumption in
Turkey. Therefore, it is important to ensure placement of ‘‘high
efficiency’’ motors in industrial plants wherever possible (Kaya
et al., 2008). APEC-ESIS (2003) carried out some works on motor
standards in APEC region.
There are a number of different terms used to describe the AC
drive. AFD, variable speed drive (VSD), VFD and inverters all are
employed, but have the same meaning. The main purpose for
all AC drives is to control the operation of the AC motor with
regard to speed and torque. A drive is a technology that controls
a motor’s speed to correspond with its load requirements. VSD’s
have been used to provide significant savings in a number of
applications.
By introducing variable speed to the driven load, it is possible
to optimize the efficiency of the entire system, and it is in this area
that the greatest efficiency gains are possible (Mecrow and Jack,
2008). Power factor (PF) correction equipment that can be applied
at the motor level will not only decrease energy use but also will
significantly extend the life of the equipment (Bayindir et al.,
2009; Colak et al., 2004).
Capacitors today are smaller and can be applied more easily at
the motor level than a few years ago. They have also come down
in price to a level where the return on investment (ROI) is usually
Others, 1%
Residential,
19%
Industrial,
48%
Commercial,
32%
Fig. 1. Statistics of energy uses in Malaysia.
Others
Electric furnaces
Workshop machines
Cranes ( Overhead & gantry)
Conveyor systems
Lifts/elevators/escalators
Air cleaning equipments
Ventilation & exhaust systems
pumps
Reciprocating air-compressor
Refrigeration systems
Air conditioning systems
Steam/hot water boilers
Electric motors
Electric lights
0
5
10
15
20
25
30
Percentage (%)
35
Fig. 2. End use energy breakdowns in Malaysian industrial sector.
40
45
50
ARTICLE IN PRESS
3652
R. Saidur et al. / Energy Policy 37 (2009) 3650–3658
less than 1 year making them a fast return on the money spent. By
combining several of the solutions, aggregate energy savings can
easily approach 30–35% (Nakahoma, 2008).
In the existing literature, no study has quantified the details of
motor energy savings in the ASEAN industrial sector. This study
presents the energy savings, bill savings and associated emission
reductions by industrial motors for different energy savings
strategies. It is hoped this study will be useful for formulating
policy measures for industrial motors energy use in ASEAN and
other countries. Furthermore, the results can furnish important
guidelines and insights for future research and development
allocations and energy projects to reduce motor energy use.
Table 2
Number of audited industrial sector with ISIC code.
Sectors
Sector/ISIC code
Number of audited factories
Food products
Wood and wood products
Paper and paper products
Chemicals
Petroleum refineries
Rubber and rubber products
Plastic and plastic products
Glass and glass products
Iron and steel
Fabricated metal products
Cement
Total
311
331
341
352
353
355
356
362
371
381
390
9
8
13
4
5
13
7
4
5
12
6
91
2. Methodology
This section explains the targeted factories, walkthrough audit,
data collected, and approaches used to estimate energy savings
and emission reductions by variable speed drive, high efficiency
motor and power factor improvement. The payback period and
economics of energy savings for different strategies have been
shown as well. These are elaborated below.
2.1. Targeted manufacturing factories
The targeted industries in the present study are electricity
users of TNB (a national utility company) from the industrial
sector in various regions within Peninsular Malaysia.
More than 2500 questionnaires were distributed by mail to
various industrial firms, amounting to 10% of the total Malaysian
industrial sector. Based on the response received, 125 industries
(5% of the 2500 industries) were selected to perform the
walkthrough audit. However, audit team managed to visit and
collect complete data for 91 industries. The selection of these
industries is based on the information provided during the mail
survey, their willingness to accept our audit team and the amount
of energy used. The locations of industrial regions along with
number of audited factories in each region are shown in Table 1.
The audited factories were divided into 11 sectors according to
the product they manufactured. Table 2 shows the sectors with
three digit International Standard Industrial Classification (ISIC)
code and the number of factories audited from each sector.
2.2. Energy audit data
Energy audit data have been collected using a walkthrough
energy audit. Details of walkthrough energy audit can be found in
Saidur et al. (2009). During the walkthrough audit in a factory, the
audit team counted all the equipment on the production floor, and
took notes on rated power from technical specifications on the
equipment and operating hours per working day. The audit team
also estimated total working days in a year in consultation with a
responsible person associated with the production process.
Table 1
Locations of audited factories.
Location
Number of audited factories
Central (Selangor, Kuala Lumpur)
North (Perak, Penang, Kedah, and Perlis)
South (Johor, Melaka and Negeri Sembilan)
East (Pahang and Terengganu)
Total (East-coast of Malaysia)
41
25
14
11
91
The most important data that have been collected during the
walkthrough audit are power rating and operation time for
equipments/machineries using energy, fossil fuel and other
sources of energy use, production figure, peak and off-peak tariff
usage behavior, and power factor. From this study and published
work (Saidur et al., 2009), it was found that the industrial motor
consumes a major share of total industrial energy. Consequently,
the electrical motor has been targeted to estimate energy savings
and emission reduction by applying various energy savings
strategies.
2.3. Estimating electric motor energy savings, its payback period and
emission reductions
Energy can be saved in different ways for different types of
machinery using industrial energy, working with the different
energy savings strategies. However, the focus of the present study
is to identify major energy-using equipment and to apply energysaving options for this major energy-using equipment. Since
motors consume a substantial share of total industrial energy (see
Fig. 2), energy savings through the use of energy-efficient motors,
VSDs and capacitors is considered.
2.4. Energy savings by using a high efficiency motor
A high efficiency motor (HEM) uses low-loss materials to
reduce core and copper losses. Therefore, it generates less heat
and requires a smaller and, more energy-efficient cooling fan. The
most popular approach is demand-side management, one aspect
of which is to improve the efficiency to offset load growth. These
facts led electric motor manufacturers to seek methods for
improving the motor efficiency, which resulted in a new
generation of electric motors that are known as energy-efficient
electric motors. Several leading electric motor manufacturers,
mainly in the US and Europe, have developed product lines of
energy-efficient electric motors (Akbaba, 1999).
Switching to energy-efficient motor-driven systems can save
Europe up to 202 billion kWh in electricity use, equivalent to a
reduction of h10 billion per year in operating costs for industry. It
was reported that a reduction of 79 million tons of CO2 emissions
(EU-15), or approximately a quarter of the EU’s Kyoto target, is
achievable using energy-efficient motors. This is the annual
amount of CO2 that a forest the size of Finland transforms into
oxygen. If industries are allowed to trade these emission
reductions based on energy saved, this would generate a revenue
stream of h2 billion per year. For EU-25, the reduction potential is
100 million tons (Anon, 2004).
ARTICLE IN PRESS
3653
R. Saidur et al. / Energy Policy 37 (2009) 3650–3658
2.4.1. Mathematical formulations to estimate energy savings using
HEMs
Annual energy savings (AES) by replacing a standard efficient
motor with a high energy-efficient motor can be estimated using
methodology described in Garcia et al. (2007):
1
1
100
(1)
AES ¼ hp L 0:746 h
Estd
Eee
Annual bill savings associated with the above energy savings
can be calculated as
Savings ¼ AES c
(2)
2.5. Motor energy savings using variable speed drive
Many building systems are designed to operate at maximum
load conditions. However, most building systems operate at their
full load only for short periods of time. This often results in many
systems operating inefficiently over long periods of time. Most
such inefficient operations in buildings are encountered in airconditioning systems that are normally sized to meet peak load
conditions. These occur only for short periods during the normal
day. The efficiency of such systems can be improved by varying
their capacity to match actual load requirements.
As all these are variable torque applications, the power
required (to drive the pumps or fans) varies to the cube of the
speed and, therefore, large power reductions result from small
reductions in speed, as shown in Fig. 3. The most common method
is to modulate the speed of the motors of pumps and fans to vary
their capacity using VSDs (Beggs, 2002).
Variable frequency drives provide continuous control, matching motor speed to the specific demands of the work being
performed. Variable frequency drives are an excellent choice for
adjustable-speed drive users, because they allow operators to
fine-tune processes while reducing costs for energy and equipment maintenance in heating, ventilating and air-conditioning of
buildings (Jayamaha, 2006; Teitel et al., 2008).
VSD installations can increase energy efficiency (in some cases
energy savings can exceed 50%), improve power factor and process
precision, and afford other performance benefits such as soft
starting and overspeed capability. They also can eliminate the
100
Power consumption (%)
90
80
70
need for expensive and energy-wasting throttling mechanisms
such as control valves and outlet dampers (Beggs, 2002).
Electric motors are over 90% efficient when running at their
rated loads. However, they are very inefficient at load following, or
at part loads running. Conventional electric motors typically use
60–80% of their rated input energy, even when running at less
than 50% load (Bouzidi, 2007). It is very important to select an
electric motor of suitable power to work efficiently. In general,
motors are chosen in big capacities to meet extra load demands.
Big capacities cause motors to work inefficiently at low load.
Normally, motors are operated more efficiently at 75% of rated
load and above. Motors operated at less than 50% of rated load
because they were chosen based on large capacity, perform
inefficiently and, due to the reactive current increase, power
factors are also decreased. These kinds of motors do not use the
energy efficiently because they have been chosen for large motor
power, not according to the needs. These motors should be
replaced with new suitable-capacity motors, and when purchasing new motors, energy-saving motors should be preferred (Kaya
et al., 2008). VSDs yield sizable energy savings (15–40% in many
cases) and extend equipment life by allowing for gentle start-up
and shutdown (Nadel et al., 2002).
2.5.1. Mathematical formulations to estimate energy savings using
VSD
There are many ways to estimate the energy savings associated
with the use of VSD for industrial motors for various applications.
This paper employed the methods found in Anon (2008).
Energy use of fans and pumps varies according to the speed
raised to the third power. So small changes in speed can result in
huge changes in energy use. A motor energy savings using VSD
can be estimated by
(3)
ESVSD ¼ nPHavg_usage SSR
Table 3 shows the potential energy savings associated with the
speed reduction using VSD for industrial motors (Anon, 2002).
These data have been used to estimate motor energy savings using
VSD.
2.6. Motor loss reductions using capacitor bank
A power factor is the ratio of the real power to the apparent
power and represents how much real power a piece of electrical
equipment utilizes. It is a measure of how effectively electrical
power is being used. Induction motors convert some 80–90% of
the delivered apparent power into useful work. The remaining
power is used to establish an electromagnetic field in the motor.
The field is alternately expanding and collapsing (once each cycle).
So the power drawn into the field in one instant is returned to the
electrical supply system in the next instant. Therefore, the average
power drawn by the field is zero and a reactive power does not
60
50
Table 3
Potential savings from VSD (Anon, 2008).
40
30
20
10
0
10
20
30
40
50
60
70
Rated speed (%)
80
90
Fig. 3. Relationship between motor power reduction and rated speed.
100
Average speed reduction (%)
Potential energy savings (%)
10
20
20
40
50
60
89
22
44
61
73
83
ARTICLE IN PRESS
3654
R. Saidur et al. / Energy Policy 37 (2009) 3650–3658
register on a kilowatt-hour meter. Although it does no useful
work, it circulates between the generator and the load and places
a heavier drain on the power source as well as the transmission
and distribution system (Kwiatkowski, 2009).
Adding capacitors is generally the most economical way
to improve a facility’s power factor, as shown in Fig. 4. While
the current through an inductive load lags behind the voltage,
current to a capacitor leads the voltage. Thus, capacitors serve
as a leading reactive power to counter the lagging current in a
system.
The choice of the optimum type, size, number and strategic
locations for capacitors in the plant is very important. There are
three methods of improving a power factor using capacitors:
100
90
Power factor (%)
80
70
60
50
40
30
20
Power factor with capacitor
Power factor without capacitor
10
0
0
10
20
30
40
50
60
Motor load (%)
70
80
90
Fig. 4. Power factor improvements by using capacitor.
100
(a) individual motor compensation (static capacitors)
(b) centralized compensation located at the incoming power
source (automatic capacitor banks) and
(c) use of synchronous motor (in overexcited mode) as synchronous capacitors.
Table 4
Multipliers to determine capacitor kilovars required for power factor correction (Gilbert and John, 2002).
Existing PF (Cos +)
before applying
capacitors
Target power factor required (Cos +)
0.80
0.85
0.90
0.92
0.95
0.98
1.0
0.40
0.42
0.44
0.46
0.48
0.50
0.52
0.54
0.56
0.58
0.60
0.61
0.62
0.63
0.64
0.65
0.66
0.67
0.68
0.69
0.70
0.71
0.72
0.73
0.74
0.75
0.76
0.77
0.78
0.79
0.80
0.81
0.82
0.83
0.84
0.85
0.86
0.87
0.88
0.89
0.90
0.91
0.92
0.93
0.94
0.95
1.54
1.41
1.29
1.18
1.08
0.98
0.89
0.81
0.73
0.65
0.58
0.55
0.52
0.48
0.45
0.42
0.39
0.36
0.33
0.30
0.27
0.24
0.21
0.19
0.16
0.13
0.11
0.08
0.05
0.03
1.67
1.54
1.42
1.31
1.21
1.11
1.02
0.94
0.86
0.78
0.71
0.68
0.65
0.61
0.58
0.55
0.52
0.49
0.46
0.43
0.40
0.37
0.34
0.32
0.29
0.26
0.24
0.21
0.18
0.16
0.13
0.10
0.08
0.05
0.03
1.81
1.68
1.56
1.45
1.34
1.25
1.16
1.07
1.00
0.92
0.85
0.81
0.78
0.75
0.72
0.68
0.65
0.63
0.59
0.56
0.54
0.51
0.48
0.45
0.42
0.40
0.37
0.34
0.32
0.29
0.27
0.24
0.21
0.19
0.16
0.14
0.11
0.08
0.06
0.03
1.87
1.73
1.61
1.50
1.40
1.31
1.22
1.13
1.05
0.98
0.91
0.87
0.84
0.81
0.77
0.74
0.71
0.68
0.65
0.62
0.59
0.57
0.54
0.51
0.48
0.46
0.43
0.40
0.38
0.35
0.32
0.30
0.27
0.25
0.22
0.19
0.17
0.14
0.11
0.09
0.06
0.03
1.96
1.83
1.71
1.60
1.50
1.40
1.31
1.23
1.15
1.08
1.00
0.97
0.94
0.90
0.87
0.84
0.81
0.78
0.75
0.72
0.69
0.66
0.64
0.61
0.58
0.55
0.53
0.50
0.47
0.45
0.42
0.40
0.37
0.34
0.32
0.29
0.26
0.24
0.21
0.18
0.16
0.13
0.10
0.07
0.03
2.09
1.96
1.84
1.73
1.60
1.53
1.44
1.36
1.28
1.20
1.13
1.10
1.06
1.03
1.00
0.97
0.94
0.90
0.88
0.85
0.82
0.79
0.76
0.73
0.71
0.68
0.65
0.63
0.60
0.57
0.55
0.52
0.49
0.47
0.44
0.42
0.39
0.36
0.34
0.31
0.28
0.25
0.22
0.19
0.16
0.13
2.29
2.16
2.04
1.93
1.83
1.73
1.64
1.56
1.48
1.40
1.33
1.30
1.27
1.23
1.20
1.17
1.14
1.11
1.08
1.05
1.02
0.99
0.96
0.94
0.91
0.88
0.86
0.83
0.80
0.78
0.75
0.72
0.70
0.67
0.65
0.62
0.59
0.57
0.54
0.51
0.48
0.46
0.43
0.40
0.36
0.33
ARTICLE IN PRESS
3655
R. Saidur et al. / Energy Policy 37 (2009) 3650–3658
If the plant contains many small motors (in the 12 to 10 hp size
range), it may be more economical to group the motors and place
single capacitors or banks of capacitors at or near the motor
control centers. In Malaysia, the capacitors are generally placed at
a central location (at the incoming substation) and switched into
the system automatically when the motors are started.
It is important not to overcorrect, as overcorrection may result
in greater problems such as overvoltage and insulation breakdown. It is recommended that the power factor be kept above 90%
and below unity (100%) for optimal performance of the electrical
system.
2.6.1. Calculating size of capacitor banks
In the case of a centralized compensation, it is recommended
that the first capacitor step be equal to half the value of the
following steps, to allow a smooth overall linear correction
system.
Table 4 has been used in calculating capacitor values for a
specific application. The correct capacitor size can be calculated
by multiplying the factor when crossing the horizontal and
vertical columns in the table by kW. The average installed cost
of capacitors per kVAR at higher voltage levels (2400 V and up) are
generally about US$11.4/kVAR (Yang, 2006). The payback period
for power factor correction can be calculated using Eq. (4). Input
data needed to estimate payback period are shown in Table 6.
2.6.2. Mathematical formulations of the payback period
A simple payback period for different energy savings strategies
can be calculated by
Simple payback period ðyearsÞ ¼
Incremental cost
Annual dollar savings
(4)
Input data needed to estimate energy savings and the payback
period for these strategies are shown in Tables 5–7. Average usage
Table 5
Input data for motor energy savings.
Parameters
Value
Average usage hours
Average electricity cost (US$/kWh)
6000
0.064
Table 7
Incremental price for VSD (Anon, 2002).
HP
Incremental price (US$)
3
5
7.5
10
15
20
25
30
2216
2461
3376
3349
4176
5316
6123
6853
Table 8
Emission factors of fossil fuels for electricity generation (Source: Mahlia, 2002).
Fuels
Coal
Petroleum
Gas
Hydro
Others
Emission factor (kg/kWh)
CO2
SO2
NOx
CO
1.18
0.85
0.53
0.00
0.00
0.0139
0.0164
0.0005
0.000
0.000
0.0052
0.0025
0.0009
0.0000
0.0000
0.0002
0.0002
0.0005
0.0000
0.0000
hours have been collected from the energy audit survey data.
Efficiency of standard and high efficiency motors has been
collected from Garcia et al. (2007). Incremental costs associated
with the usage of high efficient motor, VSD and power factor
improvement capacitor have been taken from Garcia et al. (2007),
Anon (2002) and Yang (2006). Since there is no comprehensive
work on motors in Malaysia, these data have been used at least to
obtain some modicum of insight into how much energy and cost
can be saved along with emission reductions. Moreover, motors
are manufactured, sold and used around the world. So data from
variety of countries have been used in this estimation.
2.6.3. Estimation of emission reduction
The energy savings is likely to reduce the electricity generation
from power plants. As a consequence, the reduction of CO2 and
other emissions from the fuels used by the power sector can be
estimated. The amount of emission that can be reduced associated
with the energy savings can be estimated using (Mahlia, 2002)
ER ¼ AES EF
Table 6
Efficiency of standard and high efficiency motors at different loads (Garcia et al.,
2007).
Motor HP
1
1.5
2
3
4
5.5
7.5
15
20
25
30
40
50
60
75
Load (50%)
Load (75%)
(5)
Emission factor for per unit energy is shown in Table 8 and is
used to estimate the amount of emission that can be reduced.
Load (100%)
Estd
Eee
Estd
Eee
Estd
Eee
70.05
76.04
77.20
77.78
81.07
81.15
84.07
84.92
86.03
87.61
88.43
88.15
89.63
87.89
88.77
75.28
80.06
80.02
82.44
83.69
84.35
85.51
88.32
88.51
90.26
90.89
90.39
91.16
90.07
90.86
74.43
78.03
79.29
79.87
82.39
84.73
86.23
86.45
87.58
88.39
89.32
90.54
89.86
91.31
90.19
79.49
81.28
83.07
84.55
85.24
86.50
87.58
89.85
91.05
91.66
91.73
91.91
92.58
92.09
92.72
77.00
78.50
81.00
81.50
82.90
85.30
86.61
87.94
88.95
89.50
90.70
90.36
92.06
91.78
92.44
80.97
82.55
83.55
85.01
85.96
87.75
89.50
90.44
91.64
91.80
91.83
92.85
93.28
93.00
93.02
3. Results and discussion of electrical motor energy savings,
payback period and associated emission reductions
Using Eqs. (1), (2) and (4) and input data in Table 5, energy
savings, bill savings and the payback period associated with
energy savings as a result of using a high efficiency motor have
been estimated and presented in Table 9 for different motor sizes
and loads.
Based on this table and by analyzing data, it was determined
that 1765, 2703 and 3605 MWh of total energy can be saved by
using energy-efficient motors for 50%, 75% and 100% motor
loading, respectively. Similarly, associated bill savings for the
estimated amount of energy savings are US$115,936, US$173,019
and US$230,693, respectively. It also has been found that the
payback period for using energy-efficient motors ranges from 0.53
ARTICLE IN PRESS
3656
R. Saidur et al. / Energy Policy 37 (2009) 3650–3658
Table 9
Energy savings and payback period for high efficient motor.
HP
Quantity
(no.)
1
3968
1.5
331
2
1653
3
2976
4 13,556
5.5
331
7.5
661
15
165
20
3306
25
992
30
331
40
661
50
331
60
827
75
165
Incremental
price (US$)
Load (50%)
24
21
25
27
60
65
91
147
197
246
257
231
281
574
518
Load (75%)
Load (100%)
Energy savings
(MWh)
Bill savings
(US$/year)
Payback Energy savings
(yr)
(MWh)
Bill savings
(US$/year)
Payback Energy savings
(yr)
(MWh)
Bill savings
(US$/year)
Payback
(yr)
74
6
28
122
393
16
19
21
404
156
11
140
58
257
60
4730
394
1814
7798
25,169
1022
1194
1351
25,888
9989
682
8938
3721
16,417
3862
2.05
1.80
2.25
1.02
3.22
2.10
5.05
1.80
2.52
2.44
2.33
1.71
2.50
2.89
2.22
6118
458
3421
11,155
39,675
792
1598
1957
51,883
18,046
5261
7852
9746
8295
6763
1.59
1.55
1.19
0.71
2.04
2.71
3.77
1.24
1.26
1.35
1.62
1.95
0.95
5.72
1.27
8158
611
4562
14,873
52,900
1056
2131
2609
69,177
24,061
7014
10,469
12,994
11,060
9018
1.19
1.16
0.89
0.53
1.53
2.04
2.83
0.93
0.94
1.01
1.21
1.46
0.71
4.29
0.95
96
7
53
174
620
12
25
31
811
282
82
123
152
130
106
127
10
71
232
827
16
33
41
1081
376
110
164
203
173
141
Table 10
Motor energy savings with VSD for different % of speed reduction.
Motor power (HP)
0.25
0.5
0.75
1
1.5
2
3
4
5.5
7.5
15
20
25
30
40
50
60
75
Energy savings (MWh)
10% speed reduction
20% speed reduction
30% speed reduction
40% speed reduction
50% speed reduction
60% speed reduction
114
57
97
391
49
325
880
5341
179
487
251
6519
2437
975
2600
1625
4904
1256
228
114
195
782
97
650
1761
10,682
357
975
502
13,038
4874
1950
5199
3250
9808
2511
316
158
270
1084
135
901
2441
14,809
496
1352
696
18,075
6758
2703
7208
4505
13,597
3481
378
190
323
1297
162
1078
2921
17,723
593
1617
833
21,631
8087
3235
8626
5391
16,272
4166
430
215
368
1475
184
1226
3321
20,151
674
1839
947
24,594
9,195
3678
9808
6130
18,501
4737
461
231
394
1582
197
1315
3561
21,607
723
1972
1016
26,372
9860
3944
10,517
6573
19,839
5079
Table 11
Bill (US$) savings for VSD.
Motor power (HP) Speed reduction
10%
0.25
0.5
0.75
1
1.5
2
3
4
5.5
7.5
15
20
25
30
40
50
60
75
20%
30%
40%
50%
7295
14,590
20,227
24,205
27,521
3655
7311
10,135
12,129
13,790
6239
12,478
17,300
20,703
23,539
25,020
50,040
69,373
83,020
94,393
3120
6239
8650
10,351
11,769
20,797
41,595
57,665
69,009
78,462
56,342 112,683 156,220 186,952 212,562
341,832 683,664 947,806 1,134,260 1,289,638
11,439
22,877
31,716
37,955
43,154
31,196
62,392
86,498
103,514
117,694
16,071
32,141
44,559
53,325
60,630
417,206 834,412 1,156,799 1,384,366 1,574,005
155,980 311,959 432,489
517,569 588,469
62,392 124,784 172,996
207,028 235,387
166,378 332,757 461,322 552,073 627,700
103,986 207,973 288,326 345,046 392,312
313,850 627,700 870,220 1,041,411 1,184,070
773,970 1,547,940 2,146,008 2,568,173 2,919,978
60%
29,511
14,787
25,240
101,216
12,620
84,134
227,928
1,382,865
46,274
126,202
65,013
1,687,789
631,009
252,403
673,076
420,672
1,269,666
3,131,060
to 5.05 years for different percentages of motor loading. These
payback periods indicate the introduction/implementation
of energy-efficient motors would seem cost effective, as their
payback periods are less than one-third of the motor life
(if average motor life 20 years is considered) in some cases.
Using Eqs. (3) and (4) and data from Tables 3, 5 and 7, the
energy savings, bill savings and payback period for speed
reduction of motors using VSD have been estimated and are
shown in Tables 10–12.
From Table 10, it is evident that a huge amount of energy
can be saved for different percentages of speed reductions.
More energy can be saved for higher speed reductions. Along
with energy savings, a substantial amount in expense can be
saved and associated emission reductions can be achieved using
VSD for industrial motors in Malaysia as can be found in Table 11.
From Table 12, it can be seen that the payback period for larger
motors is economically very viable, since the payback period is
very short. However, VSD is not economically viable for smaller
motors, since the payback period is significantly higher as
reported by other researchers as well (Tolvanen, 2008a, b). Abbott
(2006) reported that the payback period of using VSDs for
ARTICLE IN PRESS
3657
R. Saidur et al. / Energy Policy 37 (2009) 3650–3658
different sizes and categories of motors ranges from 0.4 to 1.5
years.
Using data in Table 4 and considering cost of kVAR as US$11.4/
kVAR based on the study of Yang (2006), the required kVArs,
to improve the power factor for 0.85–0.9, 0.95 and 0.98 have been
estimated and are shown in Table 13. It should be noted that the
cost effectiveness of power factor correction depends on several
factors: utility power factor penalties, the need for additional
system capacity, energy and demand cost, hours of facility
operation, distribution system wire sizes, and the distance
between the motor and the electrical meter (Gilbert and John,
2000).
Using the data shown in Table 8, and Eq. (5), the amount of
emissions that can be reduced as a result of introducing energyefficient motors has been estimated and is presented in Table 14.
Table 12
Payback period for speed reduction with the application of VSD.
Motor power (HP)
0.25
0.5
0.75
1
1.5
2
3
4
5.5
7.5
15
20
25
30
40
50
60
75
Payback period (yr) for speed reduction
10%
20%
30%
40%
50%
60%
113.79
58.28
39.77
30.52
21.27
16.64
12.02
9.70
7.81
6.47
4.62
4.15
3.88
3.69
3.46
3.32
3.23
3.14
56.89
29.14
19.89
15.26
10.63
8.32
6.01
4.85
3.91
3.23
2.31
2.08
1.94
1.85
1.73
1.66
1.61
1.57
41.04
21.02
14.34
11.01
7.67
6.00
4.33
3.50
2.82
2.33
1.66
1.50
1.40
1.33
1.25
1.20
1.16
1.13
34.29
17.56
11.99
9.20
6.41
5.02
3.62
2.92
2.35
1.95
1.39
1.25
1.17
1.11
1.04
1.00
0.97
0.95
30.16
15.45
10.54
8.09
5.64
4.41
3.19
2.57
2.07
1.71
1.22
1.10
1.03
0.98
0.92
0.88
0.86
0.83
28.13
14.41
9.83
7.54
5.26
4.11
2.97
2.40
1.93
1.60
1.14
1.03
0.96
0.91
0.86
0.82
0.80
0.78
Table 15 shows the emission reduction associated with the energy
savings by motors using VSD.
It should be pointed out that the amount of energy, money
savings and emission reductions has been estimated for only 91
industries in Malaysia. Thus, there is a tremendous potential for
saving of energy and lowering electricity bills for the total number
of industries in Malaysia. Along with energy savings, it will reduce
emission of pollutants released into the atmosphere as well.
4. Conclusion
It can be concluded that
(a) The study found that a substantial amount of energy and
utility bills can be saved if high efficiency motors, VSD and
capacitor banks are used for industrial motors.
(b) It has been found that the payback period for using energyefficiency strategies for larger motors for VSD is reasonable
(i.e. within 1–3 years).
(c) The study also estimated that emissions can be substantially
reduced by applying energy savings strategies to industrial
motor.
(d) It was also found that more energy can be saved at levels of
higher speed reduction (i.e. speed reduction above 40%).
(e) The required kVAr and cost of kVAr to improve the power
factor that can reduce resistance (I2R) losses are estimated in
this paper.
Table 14
Emission reductions (ton) associated with energy savings for energy efficient
motor.
CO2
SO2
NOx
CO
27,140
40,707
39,562
162
244
311
77
115
128
17
25
19
Table 13
cost of kVAr period for adding capacitor to improve power factor of industrial motors.
HP
0.25
0.5
0.75
1
1.5
2
3
4
5.5
7.5
15
20
25
30
40
50
60
75
Quantity (no.)
4629
1157
1323
3968
331
1653
2976
13,556
331
661
165
3306
992
331
661
331
827
165
PF ¼ 0.90
PF ¼ 0.95
PF ¼ 0.98
kVAr required (kVAr)
Cost of kVAr (US$)
kVAr required (kVAr)
Cost of kVAr (US$)
kVAr required (kVAr)
Cost of kVAr (US$)
121
60
104
414
52
345
932
5663
190
518
258
6906
2590
1037
2761
1728
5182
1292
1378
689
1181
4724
591
3936
10,630
64,560
2168
5902
2947
78,724
29,527
11,823
31,480
19,705
59,078
14,734
250
125
215
858
107
715
1931
11,731
394
1073
535
14,304
5365
2148
5720
3580
10,735
2677
2854
1427
2447
9786
1225
8154
22,019
133,731
4490
12227
6104
163,070
61,164
24,490
65,208
40,817
122,377
30,520
363
181
311
1243
156
1036
2797
16,989
570
1553
775
20,717
7770
3111
8284
5185
15,547
3877
4134
2066
3544
14,173
1773
11,809
31,889
193,680
6503
17,707
8840
236,171
88,582
35,468
94,440
59,114
177,235
44,202
ARTICLE IN PRESS
3658
R. Saidur et al. / Energy Policy 37 (2009) 3650–3658
Table 15
Emission reductions associated with energy savings by VSD.
Motor
power
(HP)
0.25
0.5
0.75
1
1.5
2
3
4
5.5
7.5
15
20
25
30
40
50
60
75
Emission reductions (kg) for 20% speed
reduction
Emission reductions (kg) for 40% speed reduction
Emission reductions (kg) for 60% speed reduction
CO2
SO2
NOx
CO
CO2
SO2
NOx
CO
CO2
SO2
NOx
CO
1,140,634
570,194
978,003
3,911,026
489,371
3,258,531
8,799,809
53,445,435
1,794,361
4,886,319
2,439,463
65,170,629
24,443,914
9,787,422
26,060,366
16,312,370
48,907,541
12,197,316
6828
3413
5854
23,411
2929
19,506
52,676
319,924
10,741
29,249
14,603
390,111
146,321
58,587
155,997
97,646
292,760
73,013
3217
1608
2758
11,029
1380
9189
24,815
150,716
5060
13,779
6879
183,781
68,932
27,601
73,490
46,001
137,919
34,396
694
347
595
2379
298
1982
5352
32,507
1091
2972
1484
39,639
14,868
5953
15,851
9922
29,747
7419
1892,415
946,003
1622,596
6,488,748
811,911
5,406,200
14,599,683
88,670,836
2,977,008
8,106,847
4,047,291
108,123,998
40,554,676
16,238,223
43,236,517
27,063,705
81,142,057
20,236,456
11,328
5663
9713
38,842
4860
32,361
87,394
530,783
17,820
48,528
24,227
647,230
242,760
97,202
258,814
162,003
485,716
121,135
5337
2668
4576
18,298
2290
15245
41171
250,052
8395
22,861
11413
304,910
114,364
45,792
121,927
76,320
228,821
57,067
1151
575
987
3947
494
3288
8880
53,932
1811
4931
2462
65,764
24,667
9877
26,298
16,461
49,353
12,308
2,307,191
1,153,346
1,978,233
7,910,939
989,864
6,591,120
17,799,614
108,105,540
3,629,502
9,883,690
4,934,369
131,822,409
49,443,372
19,797,286
52,713,014
32,995,476
98,926,617
24,671,844
13,811
6904
11,842
47,355
5925
39,454
106,548
647,119
21,726
59,164
29,537
789,089
295,968
118,506
315,540
197,511
592,174
147,686
6506
3252
5579
22,309
2791
18,587
50195
304,858
10,235
27,872
13,915
371,739
139,430
55,828
148,651
93,047
278,973
69,575
1403
702
1203
4812
602
4009
10,826
65,753
2208
6012
3001
80,178
30,073
12,041
32,062
20,069
60,170
15,006
Acknowledgement
Authors would like to acknowledge the service provided by the
University of Malaya ISI (UPISI) Journal centre for polishing the
language.
References
Abbott III, L., 2006. Power quality and cost analysis of industrial electrical
distribution systems with adjustable speed drives. MS Thesis, California State
University, USA.
Akbaba, M., 1999. Energy conservation by using energy efficient electric motors.
Applied Energy 64, 149–158.
Al-Ghandoor, A., Al-Hinti, I., Jaber, J.O., Sawalha, S.A., 2008. Electricity consumption
and associated GHG emissions of the Jordanian industrial sector: empirical
analysis and future projection. Energy Policy 36, 258–267.
Al-Mansour, F., Merse, S., Tomsic, M., 2003. Comparison of energy efficiency
strategies in the industrial sector of Slovenia. Energy 28, 421–440.
Anon, 2002. Measure Analysis and Life Cycle Cost, Part II, California Energy
commission.
Anon, 2004. Variable Speed Driven Pumps, Best Practice Guide. Automation
instrumentation & control laboratory technology, /www.gambica.org.ukS,
downloaded on 31/12/08.
Anon, 2008. Ways to Save on Motor Energy Costs, 2008, /http://www.aps.com/
main/services/business/WaysToSave/BusWaystoSave_16S, Downloaded on 28/
11/2008.
APEC-ESIS, 2003. ASEA-Pacific Economic Cooperation—Energy Standards Information System A Survey of Efficiency Levels Specified for Three-Phase Cage
Induction Motors.
Bayindir, R., Sagiroglu, S., Colak, I., 2009. An intelligent power factor corrector for
power system using artificial neural networks. Electric Power Systems
Research, 52–160.
Beggs, C., 2002. Energy Management and Conservation. Elsevier Ltd., Amsterdam.
Bouzidi, F., 2007. Energy savings on single-phase induction motors under light load
conditions. MS Thesis, University of Nevada Las Vegas, USA.
Chan, D.Y.L., Yang, K.H., Hsu, C.H., Chien, M.H., Hong Gui, B., 2007. Current situation
of energy conservation in high energy-consuming industries in Taiwan. Energy
Policy 35, 202–209.
Christoffersen, L.B., Larsen, A., Togeby, M., 2006. Empirical analysis of energy
management in Danish industry. Journal of Cleaner Production 14 (5),
516–526.
Colak, I., Bayindir, R., Sefa, I., 2004. Experimental study on reactive power
compensation using a fuzzy logic controlled synchronous motor. Energy
Conversion and Management 45 (15–16), 2371–2391.
EC, 2007. Statistics of electricity supply in Malaysia, Energy Commission Malaysia.
Fromme, J.W., 1996. Energy conservation in the Russian manufacturing industry.
Energy Policy 24, 245–252.
Ghaddar, N., Mezher, T., 1999. Modeling of current and future energy intensity and
greenhouse gas emissions of the Lebanese industrial sector: assessment of
mitigation options. Applied Energy 63, 53–74.
Garcia, A.G.P., Szklo, Alexandre S., Schaeffer, Roberto, McNeil, Michael A., 2007.
Energy-efficiency standards for electric motors in Brazilian industry. Energy
Policy 35, 3424–3439.
Gilbert, A.M., John, G.D., 2002. Energy Management for Motor-Driven Systems
Washington State University Cooperative Extension Energy Program Olympia.
Washington State University.
Gilbert, A.M., John, G.D., 2000. Energy Management for Motor Driven Systems.
Washington State University.
Ibrik, I.H., Mahmoud, M.M., 2005. Energy efficiency improvement procedures and
audit results of electrical, thermal and solar applications in Palestine. Energy
Policy 33, 651–658.
IPCC, A., 1996. Impacts, Adaptation and Mitigation of Climate Change: ScientificTechnical Analysis. Contribution of Working Group II to the Second Assessment
Report of the Intergovernmental Panel Climate Change (IPCC). Cambridge
University Press, Cambridge, UK.
Jayamaha, L., 2006. Energy Efficient Building Systems. McGraw-Hill, New York.
Kaya, D., Alptekin Yagmur, E., Suleyman Yigit, K., Kilic, Fatma Canka, Salih Eren, A.,
Celik, Cenk, 2008. Energy efficiency in Pumps. Energy Conversion and
Management 49, 1662–1673.
Kwiatkowski, E., 2009. The Economics of Improving Power Factor, Staco Energy
products Co, Available from: stacoenergy.com/y/The Economics of Improving
Power Factor for PR.pdf, Access date 23/1/2009.
Mahlia, 2002. Emissions from electricity generation in Malaysia. Renewable Energy
27, 293–300.
Mecrow, B.C., Jack, A.G., 2008. Efficiency trends in electric machines and drives.
Energy Policy 36, 4336–4341.
Mohsen, M.S., Akash, B.A., 1998. Energy analysis of the steel making industry.
International Journal of Energy Research 22, 1049–1054.
Nakahoma, 2008. Power Factor Correction at the Residential Level–Pilot Project.
Report to the LDC Tomorrow. /http://www.nakahoma.com/Res%20App%20Power%20Co.pdfS, Downloaded 18/01/09.
Nadel, S., Elliott, R.N., Shepard, M., Greenberg, S., Katz, G., de Almeida, A.T., 2002.
Energy-Efficient Motor Systems: A Handbook on Technology, Program, and
Policy Opportunities, second ed. American Council for an Energy-Efficient
Economy, Washington, DC.
Onut, S., Soner, S., 2007. Analysis of energy use and efficiency in Turkish
manufacturing sector SMEs. Energy Conversion and Management 48, 384–394.
Ozturk, H.K., 2005. Energy usage and cost in the textile industry: a case study for
Turkey. Energy 30, 2424–2446.
Priambodo, A., Kumar, S., 2001. Energy use and carbon dioxide emission of
Indonesian small and medium scale industries. Energy Conversion and
Management 42, 1335–1348.
Saidur, R., Rahim, N.A., Masjuki, H.H., Mekhilef, S., Ping, H.W., Jamaluddin, M.F.,
2009. End-use energy analysis in the Malaysian industrial sector. Energy 34
(2), 153–158.
Subrahmanya, M.H.B., 2006. Labour productivity, energy intensity and economic
performance in small enterprises: a study of brick enterprises cluster in India.
Energy Conversion and Management 47 (6), 763–777.
Teitel, M., Zhao, A.L.Y., Barak, M., Eli, Bar-lev., Shmuel, D., 2008. Energy saving in
agricultural buildings through fan motor control by variable frequency drives.
Energy and Buildings 40, 953–960.
Tolvanen, J., 2008a. Saving energy with variable speed drives. World Pumps, 32–33.
Tolvanen, J., 2008b. LCC approach for big motor-driven systems savings. World
Pumps November, 24–27.
Thollander, P., Karlsson, M., Soderstrom, M., Creutz, D., 2005. Reducing industrial
energy costs through energy-efficiency measures in a liberalized European
electricity market: case study of a Swedish iron foundry. Applied Energy 81,
115–126.
Yang, M., 2006. Demand side management in Nepal. Energy 31, 2677–2698.