Energy and Buildings 41 (2009) 500–511
Contents lists available at ScienceDirect
Energy and Buildings
journal homepage: www.elsevier.com/locate/enbuild
Prediction of yearly energy requirements of indoor ice rinks
Lotfi Seghouani, Ahmed Daoud, Nicolas Galanis *
Département de Génie Mécanique, Université de Sherbrooke, Sherbrooke, Qc, Canada J1K 2R1
A R T I C L E I N F O
A B S T R A C T
Article history:
Received 24 April 2008
Received in revised form 20 October 2008
Accepted 22 November 2008
A model of the transient heat transfer between the ground under and around the foundations of an
indoor ice rink and the brine circulating in pipes embedded in the concrete slab under the ice has been
coupled with a previously developed model calculating heat fluxes towards the ice by convection,
radiation and phase changes. Subroutines calculating the energy consumption for heating and
humidifying (or cooling and reheating) the ventilation air have also been added to the model. The
resulting simulation tool has been used to calculate monthly refrigeration loads and energy
consumption by the ventilation system, the lights, the brine pump, the radiant heating system of the
stands and the underground electric heating used to prevent freezing and heaving for four North
American cities with very different climates. Correlations expressing the energy consumption of the
ventilation air stream in terms of the sol-air temperature are formulated.
ß 2008 Elsevier B.V. All rights reserved.
Keywords:
Zonal method
Ground conduction
Radiation exchanges
Convection
Condensation
Refrigeration load
1. Introduction
Indoor ice rinks are large buildings without internal partitions
and with high-energy consumption. They have a complex energy
system in which a large ice sheet is cooled and maintained at a low
temperature by a refrigeration system, while the stands are heated
(or cooled) to ensure comfortable conditions for the spectators.
Also, the building is ventilated to ensure good air quality. The
movement of the ventilation air through these wide-open areas
and the simultaneous operation of heating and cooling equipments
increase energy consumption and greenhouse gas (GHG) emissions.
A study by Lavoie et al. [1] shows that the potential for energy
savings in a typical ice rink in Quebec is roughly 620 MWh/year
and the potential GHG emission reduction is 146 tons-equivalent
CO2/year. Since there are 435 indoor ice rinks in Quebec and
several thousand in North America, it would be interesting to
improve their energy efficiency while preserving good ice quality
and comfort for the spectators. To achieve this objective precise
methods for the calculation of the corresponding loads are
necessary.
Three different methods are commonly used for the thermal
modeling of buildings: the nodal method, computational fluid
dynamics (CFD) and the zonal method. The first one is the simplest
* Corresponding author.
E-mail address:
[email protected] (N. Galanis).
Abbreviations: AIM, above ice model; BIM, below ice model; IST, ice surface
temperature.
0378-7788/$ – see front matter ß 2008 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2008.11.014
and is implemented by representing the inside volume of the entire
building, or of large parts thereof, by a single node. Therefore the
nodal method does not necessitate an important computing
capacity but, on the other hand, it does not provide a detailed
description of the indoor conditions. The application of such a
model to ice rinks (or other large buildings without internal
partitions such as supermarkets or gymnasia) can lead to very
imprecise results because the mass fluxes between different parts
of the inside volume are extremely difficult to estimate.
On the other hand, the modeling of an ice rink for CFD
calculations is very complex due firstly to their size and geometry,
and secondly to the variety of the heat and mass transfer
mechanisms which take place therein. Thus, the model must take
into account heat transfer through the envelope and heat gains from
the ground, air motion within the building due to forced and natural
convection, vapour diffusion and condensation on the ice sheet, heat
transfer by radiation between all internal surfaces, conduction in the
ice and floor as well as heat generation by the lights, the resurfacing
operations, the refrigeration system, etc. Hence, the literature
review revealed few CFD studies for large buildings such as ice rinks.
Jones and Whittle [2] described the status and capabilities of CFD for
building air flow prediction while Jian and Chen [3] as well as Yang
et al. [4] used a CFD code to evaluate air quality in large ventilated
enclosures. However, these studies did not calculate heating and
refrigeration loads and ignored the interaction between the indoor
and outdoor environments.
More recently Bellache et al. [5,6] have carried out numerical
simulations in 2D and steady state conditions using a CFD code
which predicts velocity, temperature and absolute humidity
distributions in an indoor ice rink with ventilation and heating.
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
Nomenclature
A
Cp
Cd
g
h
k
ṁi; j
ṁB
M
P
qcd
qcv
qrd
qcond
qrs
QCool
QHeat
QHumid
QRe heat
QH
QIce
Qnode
R
Snode
t
T
Tb
Tgr
Tnode
Tsol-air
Unode
Ẇg
z1, z2
area (m2)
specific heat (J/kg K)
discharge coefficient
acceleration of gravity (m/s2)
height (m)
thermal conductivity (W/(m K)
airflow between zones i and j (kg/s)
brine flow rate (kg/s)
mass (kg)
static pressure (Pa)
conductive flux (W/m2)
convective flux (W/m2)
radiative flux (W/m2)
condensation flux (W/m2)
heat flux due to resurfacing (W/m2)
cooling rate (W)
heating rate (W)
energy rate due to humidification (W)
energy rate due to reheating (W)
electrical power in sand layer (W)
heat rate into node 1 calculated by AIM (W)
lateral heat transfer to node n (W)
thermal resistance (m2 K/W)
surface for lateral heat transfer at node n (m2)
time (h)
temperature (K)
brine temperature (K)
temperature of ground surface (K)
temperature at node n (K)
sol-air temperature (8C)
average conductance for lateral heat transfer at
node n (W/m2 K)
moisture source term (kg/s)
top and bottom depths of ground segment (m)
Subscripts and superscripts
i
i, j
o
p
p+1
cell i or surface i
between surface or cell i and j
outside
present time step
next time step
Greek symbols
Dt
time step (s)
eij
constant depending on flow direction (1)
r
air density (kg/m3)
v
absolute humidity (kgmoisture/kgdry air)
The CFD code also calculates the heat fluxes toward the ice due to
convection from the air, to condensation of vapour and to radiation
from the walls and ceiling. However, these calculations did not
take into account the contributions of ice resurfacing, system
pump work and ground heat to the refrigeration load.
This 2D CFD model was later improved by Bellache et al. [7] by
including transient phenomena, heat transfer through the ground
and energy gains from lights as well as the effects of resurfacing
and dissipation of pump work in the coolant pipes. The ground at a
501
depth of 2 m was assumed to have a constant temperature while
the horizontal plane through the centers of the brine pipes was
assumed to be an isothermal surface with temperature equal to the
average of the supply and return brine temperatures.
Ouzzane et al. [8] contributed preliminary experimental
measurements for a Canadian indoor ice rink which provide a
better understanding of its thermal and energy behaviour. These
measured values were also used for the verification and calibration
of the numerical model developed by Bellache et al. [7]. The main
drawback of the CFD approach is that it requires considerable
computer memory and CPU time for the simulations. Thus, the
transient 2D model by Bellache et al. [7] requires approximately
24 h of calculations on a modern desktop computer to simulate the
response of an ice rink over a period of 1 day.
An alternative method to CFD, which requires less calculation
time and computer memory, was developed by Daoud et al. [9–11].
It combines a zonal airflow model, a radiation model, a humidity
transport and condensation model and takes into account resurfacing and occupation. This above ice model (AIM) predicts the heat
fluxes through the envelope as well as the temperature and absolute
humidity distributions for a 3D transient regime during an entire
typical meteorological year. In particular it calculates the heat fluxes
into the ice sheet by convection, radiation and condensation. The
temperature below the ice sheet was assumed uniform and
constant. The results show a satisfactory agreement with corresponding measurements and CFD calculations.
The present article describes a second part in the development
of a global 3D transient model of an ice rink. The below ice model
(BIM) was developed using an implicit unidirectional electrical
analogy, taking into account the secondary loop and brine
movement and the heat gain from the ground (with changing
meteorological conditions). The BIM was coupled successfully with
the previously mentioned AIM. The combined model eliminates
the assumption of constant temperature below the ice sheet used
in AIM. Instead the temperature of the brine entering the pipes
below the ice sheet must be specified. The combined model
evaluates the return brine temperature, the total refrigeration load,
the ice surface temperature (IST), the heat gain from ground, as
well as the energy consumption of the ventilation system and of
the radiant heaters. Parametric studies were undertaken in order
to evaluate the impact of the climate, brine inlet temperature, ice
thickness and other parameters on the calculated results and their
results are presented in the last part of the present paper.
2. Description and modeling
2.1. Ice rink description
Figs. 1 and 2 show a schematic representation of the studied ice
rink ‘‘Camilien Houde’’ located in Montreal (Canada). The building
is 64.2-m long, 41.5-m wide and its height is 9.2 m. The ice surface
is 61-m long, 25.9-m wide and is surrounded by a narrow corridor.
The space above the stands is heated by eight radiant heaters
(22 kW 8) which are controlled by a thermostat. Seven inlets
supply a stream of ventilation air. Its flow rate is 4270 L/s except
during resurfacing of the ice when it is increased to 10,384 L/s to
evacuate the combustion gases of the resurfacing vehicle. The air
exits through four outlets on the walls. Heat gains from lighting are
10 W/m2 above the ice and 5 W/m2 above the stands; those due to
the presence of the audience are also taken into account while the
number of spectators is specified according to a weekly schedule
[7,11]. The ice resurfacing takes place several times per day, lasts
12 min and is modeled as a 1 mm film of hot water at 60 8C. Its
frequency, specified in the schedule mentioned above, is higher in
the evenings and weekends. The stands, corridors and boards are
also modeled in the AIM.
502
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
Fig. 1. Schematic section of the ice rink and the different layers under the ice (not to scale).
Fig. 2. Top view of the ice showing the different zones and the flow of the brine.
The ground structure beneath the ice rink is represented in
Fig. 1 and comprises horizontal layers of ice (50 mm), concrete
(150 mm), thermal insulation (100 mm), sand (200 mm) and,
finally, soil. The total depth of this structure included in the
calculation domain is 4 m.
The secondary coolant used to maintain the ice at the desired
temperature is calcium chloride brine. It is supplied from a
header located at the west end of the ice sheet and circulates in
the concrete slab at a depth 57.5 mm below the ice surface
within 74 uniformly distributed, four-pass polyethylene tubes
(25 mm ID). The spacing between tubes is 87.5 mm. The main
collector has an internal diameter of 150 mm. The flow rate of
the pump is 28.5 L/s.
An electrical heater of 8 kW is activated in the sand layer when
the ground temperature at a depth of 4 m is below 4 8C to prevent
freezing under the concrete slab which can cause damage to the
underground structure and ice.
2.2. Model of air movement and heat exchanges above the ice (AIM)
The air movement and heat exchanges occurring in the rink
above the ice surface are simulated using a 3D transient model
with 64 zones [9–11]. It consists of six coupled submodels solved
with the ‘‘onion’’ method. The first submodel is the energy model
which uses the Multizone Building Model (type 56) of TRNSYS [12].
It is based on two relations. The first one expresses energy
conservation inside each thermal zone i:
ðM C p Þi
X
dT i
ṁ j ! i C p T j
¼ ðqcv AÞi þ
dt
j
(1)
while the second expresses energy conservation for each internal
surface in contact with the air in the building:
qcd ¼ qcv þ qrd þ qcond þ qrs
(2)
The conductive flux through the wall is evaluated using the
transfer functions method while the convection flux between the
wall surface and the air inside the building is calculated using a
constant heat transfer coefficient (3 W/m2 K). The radiation flux
between internal surfaces of the building is provided by a
submodel (radiative transfer submodel) based on the Gebhart
method [13]. The condensation flux is attributed to the ice surface
when its temperature is below the dew point of the air above it. It is
provided by a submodel (humidity transport submodel) which
calculates the absolute humidity of the air in every thermal zone
inside the building using the following conservation equation:
M air;i
dvi X
¼
ṁi; j ðv j vi Þ þ Ẇg;i
dt
i; j
(3)
Finally, qrs corresponds to the heat flux occurring when the
resurfacing operation deposits approximately 0.5 m3 of water at
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
503
Fig. 3. Schematic representation of the ventilation system.
60 8C on the ice surface. It is calculated using the equation
recommended by ASHRAE [14].
The airflow mi,j between thermal zones used in Eq. (1) is
provided by the zonal airflow submodel. The formulation used
expresses the mass flow crossing the common surface between
two zones i and j in terms of their pressure difference. Thus, in the
case of a vertical interface
ṁi; j ¼ ei; j C d
pffiffiffiffiffiffiffiffi
2ri Ai; j jP j P i j1=2
(4)
While in the case of a horizontal interface
ṁi; j ¼ ei; j C d
1=2
pffiffiffiffiffiffiffiffi
1
2ri Ai; j P j P i ðri ghi þ r j gh j Þ
2
(5)
The coefficient eij is equal to +1 when flow is from zone i to zone
j and equal to 1 for flow from zone j to zone i.
A new submodel not described in our previous publications
[9,10] is used to simulate the behaviour of the ventilation
system. It consists of two units (see Fig. 3). The first one is used
for cooling, dehumidifying and reheating the external air when
its temperature is above 23 8C while the second unit is for
heating and humidifying it when its temperature is below 15 8C.
When the temperature of the entering air is between 23 8C and
15 8C none of the units is in operation unless the humidity level
is too high or too low. The humidity controls are such that the
relative humidity of the air entering the ice rink is maintained
between 20% and 33%. The equations modeling the operation of
these two units are the mass and energy conservation equations
for a gas–vapour mixture in a steady state, steady flow process.
It should be noted that the results presented here assume that
only outdoor air is handled by the ventilation system (no
recirculation).
The final submodel evaluates the ventilation effectiveness by
calculating the age of the air in every zone of the ice rink.
The data exchange between these six submodels is represented
in Fig. 4. It takes place several times at every timestep until the
outputs of each submodel vary by less than 103.
2.3. Below ice modeling (BIM)
The modeling of the ice rink ground structure shown in Figs. 1
and 2 is of a substantial nature. Indeed, the concrete slab is one of
the most important parts of an ice rink. It forms and maintains the
ice by removing heat from it, using a secondary coolant (brine)
circulating in the embedded network of pipes.
The BIM is based on the transient one-dimensional conduction
equation and the electrical circuit analogy. For that, the ice surface
is divided in eight equal square surfaces (one to eight) shown in
Fig. 2, which correspond to those used by the zonal submodel of the
AIM. Each of these surfaces is subdivided into two parts (A and B).
The brine flows from west to east under part A of the eight surfaces
and in the opposite direction under part B (see Fig. 2). Thus, the
brine enters at 1A or 2A with a constant temperature Tb,in and exits
at 1B or 2B with a temperature Tb,out which is not the same for the
North and South brine loops.
Heat transfer between the tubes is neglected since the brine
temperature increases by less than 2 8C between inlet and outlet.
This justifies the hypothesis of one-dimensional vertical heat
transfer between the different layers of the ground structure.
However, the BIM takes into consideration heat exchanges
between the horizontal layers and the outdoor or the indoor
appropriate ground surface as explained below. Therefore, it takes
into account three-dimensional phenomena.
Fig. 5 shows the equivalent electrical circuit under one-half of the
ice. At each of the 16 subdivisions of the ice surface shown in Fig. 2
the heat flux calculated by AIM enters the ice at node 1. The electrical
heating in the sand layer is added to nodes 5 and 6. The temperature
of node 7 is considered as given by the following correlation based on
the deep soil (4 m) temperature data for Montreal [15]
T 7 ¼ 3:34 4:78 103 t 1:97 107 t 2 þ 1:15 109 t 3
2:66 1013 t 4 þ 2:15 1017 t 5 5:91 1022 t 6
þ 273:15
(6)
where t is in h and T7 in K.
The heat exchanges between the horizontal layers and the
outdoor or indoor ground surface are added at nodes 2–6. They are
evaluated using the ASHRAE method [16] and are divided in two
halves attributed to the circuits under parts A and B. This method
uses the formula:
Q node ¼ U node Snode ðT o T node Þ
where the below-grade average U-factor is given by:
2ksoil
2k R
2k R
U node ¼
ln z1 þ soil
ln z2 þ soil
pðz2 z1 Þ
p
p
(7)
(8)
For nodes 4, 5 and 6 on the north, east and west sides of the ice
rink To is the temperature of the ground surface outside the ice
rink. It is calculated at each time step by the following correlation
based on the surface soil temperature data for Montreal [15]
T gr ¼ 2:56 1:31 102 t 6:88 106 t 2 1:79
1010 t 3 2:02 1013 t 4 þ 2:42 1017 t 5 7:93
1022 t 6 þ 273:15
Fig. 4. Information flow in the above-ice model (AIM).
where t is in h and Tgr in K.
(9)
504
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
Fig. 5. Thermal circuit model for below ice structure (1A, 1B. . . etc. identify zones in Fig. 2).
On the south side To is taken as constant (equal to the
temperature in the changing rooms). On the three other sides, for
nodes 2, 3 and 4, To is taken as the temperature of the concrete
surface in the corridors surrounding the ice surface which is
calculated by the AIM.
The brine enters each subdivision and absorbs the heat coming
from nodes 2 and 4. Its temperature therefore increases and it
enters the next subdivision where the process is repeated. Each of
the 16 subdivisions (parts A and B of surfaces 1–8 in Fig. 2) is
modeled in the same manner and only the entering brine
temperature and the lateral heat exchanges calculated by Eq. (7)
vary from one to another. Thus there are 7 unknown temperatures
under each of the 16 subdivisions (at nodes 1–6 and at the brine
outlet) or 118 unknown temperatures altogether.
The implicit discretisation of the transient energy balance for
each node under each subdivision leads to a system of linear
equations which can be represented by the matrix equation
AT ¼ B
(10)
where T is the vector of the seven unknown temperatures. The
expressions of the 7 7 matrix A and of the vector B are given in
the appendix.
This system of linear equations is solved by inversing matrix A
since this direct method is suitable for small-size systems. The
solution starts under surface 1A and then continues to 3A, 5A, etc.
following the direction of flow. The temperature of all the nodes is
thus obtained for each of the 16 subdivisions. Then, the
temperature of each level below the ice is obtained by averaging
the 16 corresponding node temperatures. The final outlet
temperature of the brine is calculated by assuming that the two
streams from 1B and 2B are mixed adiabatically. The heat rates
from the ice to the brine and from the soil to the brine are also
evaluated and therefore the total refrigeration load is calculated. A
FORTRAN subroutine of this model was incorporated as a new type
in TRNSYS [12].
2.4. Coupling of the AIM and BIM
The coupling of the BIM with the AIM was realised using the
‘‘Onion’’ method. Fig. 6 shows a schematic representation of the
coupling method. During one time step, the BIM calculates the
temperature T2 between the ice and the concrete for each of the
eight zones. It provides them as inputs to the AIM in which they are
used as boundary conditions. This model calculates the eight total
heat fluxes towards the ice and returns them as inputs to the BIM.
Several such data exchanges take place until outputs of each model
vary by less than 103. Then time is incremented and this
procedure is repeated.
For the simulations performed in the present project hourly
average weather data for a typical meteorological year (temperatures of the air and the ground at 0 m and 4 m depth as well as solar
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
Fig. 6. Schematic representation of the onion coupling between AIM and BIM.
radiation [15]) is used. In order to ensure the periodicity of the
results (values at the end of the 365th day must be identical to
those at the beginning of the first one) we carried out simulations
over 17 months by repeating the meteorological data for January to
May and did not consider the results of the initial 5 months to be
sure that the effects of the arbitrary initial values are eliminated.
The choice of time step is based on four considerations. The first
is that TRNSYS accepts only time steps of the form 1/N where N is
an integer. The second is the duration of resurfacing (12 min)
which means that the time step should not exceed 0.2 h. The third
is the need to minimize the time required for the calculation of the
results over the 17-month period which implies that the time step
must be large. Finally, a small time step is necessary to capture
more transient details. As a compromise between these considerations we have opted for a time step equal to 0.1 h. With this
choice the entire yearly simulation requires about 80 h on a
personal computer (with an Intel Core 2 Duo 6400 2.13 GHz
processor and 2 Go of RAM). This is a considerable improvement
over an equivalent CFD two-dimensional simulation which
requires 24 h to calculate the results for a single day [7].
2.5. Model validation
The AIM was successfully validated in previous studies [9–11].
The predictions of the more complete numerical model presented
here are validated by comparison with measurements recorded in
the Camilien Houde ice rink over relatively short periods in 2005
and 2006 [8]. Table 1 presents such a comparison of the measured
and calculated brine outlet temperature and ice surface temperature. Measured values are the averages of recorded temperatures
while calculated values are monthly averages for the typical
meteorological year. Although these conditions are not identical,
the small seasonal variation of these results makes this comparison
acceptable. The agreement between measured and calculated
values of these temperatures shows that the proposed model
predicts satisfactorily these values. The maximum relative
difference is less than 10%, which is acceptable since the
simulations did not take into account the refrigeration system
which regulates the inlet brine temperature. This difference is
principally due to the boundary condition used for the simulation
(constant brine inlet temperature Tb,in = 9 8C) and to imprecision
of the measurements.
Similar agreement has also been established between the
measured and calculated values of the heat flux into the ice. The
former was obtained by integrating the readings of four heat flux
sensors installed under the ice sheet. The corresponding daily
mean values for 1 October 2005 are: 94.9 W/m2, 56.6 W/m2,
90.6 W/m2 and 113.0 W/m2 [8]. Disregarding the second sensor
which gives significantly lower values than the other three, the
mean value of the experimentally measured heat flux is 99.5 W/
m2. On the other hand, the model predicts an average total heat
flux of 108 W/m2 for October which is about 8% higher than the
measurements. In view of the fact that these values do not
correspond to identical climate conditions, their agreement is
judged to be acceptable.
In view of these results we consider that the proposed model
can be used with confidence for the calculation of typical yearly
refrigeration loads and for parametric studies which aim to
establish the effect of design and operation conditions on these
loads.
3. Parametric analysis
The analysis in this section starts from a ‘‘base case scenario’’
which corresponds to meteorological conditions for a typical year
in Montreal (latitude N 458470 , longitude W 738750 ), a constant
brine inlet temperature to the slab equal to 9 8C, an ice thickness
of 5.08 cm, an under slab insulation thickness equal to 10 cm, a
setpoint of 15 8C with a nocturnal set back of 7 8C and an hysteresis
of 0.2 8C for the electronic thermostat, while the underground
heating (8 kW) is in operation when the ground temperature at a
depth of a 4 m is below 4 8C. The results of this transient simulation
are compared with corresponding results obtained by varying the
parameters defining the base case scenario one at a time.
3.1. Effects of the climate
Results have been calculated for typical meteorological years
for the cities of Edmonton (latitude N 538310 , longitude W 114850 ),
Houston (latitude N 298580 , longitude W 958220 ) and Pittsburgh
(latitude N 408300 , longitude W 808130 ) for which correlations
similar to those for Montreal (Eqs. (6) and (9)) have been obtained
from the meteorological data [15]. These results are compared
with those for the base case at Montreal. As indicated by the values
in Table 2 these climatic conditions vary from very warm and
humid during the summer in Houston to very cold and dry in
winter in Edmonton.
Figs. 7 and 8 illustrate the effects of the climate on the average
daily energy consumption of the ventilation system which, as
mentioned before, is constituted of two units (cf. Fig. 3). In
particular, Fig. 7 shows that the energy consumption of the first
unit, which dehumidifies the ventilation air by cooling and
reheating it, is greatest for Houston where it is significant
throughout the year. On the other hand, for the other three cities
this quantity is essentially zero during the winter months but
becomes important during the summer. The seasonal variation of
this quantity as well as its relative magnitude between the four
cities under consideration is consistent with the meteorological
data of Table 2. The same is true for the results in Fig. 8 which
shows the energy consumption of the second unit of the
ventilation system. This one heats and humidifies the incoming
ventilation air and is therefore high in winter and essentially zero
in summer, largest for Edmonton and lowest for Houston. It is
Table 2
Comparison of climatic conditions in the cities under consideration.
Table 1
Comparison between measured and calculated temperatures.
Return brine temperature (8C)
Ice surface temperature (8C)
Measured
Calculated
7.3
From 5.5 to 6.3
From 7.8 to 8.0
From 5.2 to 6.0
505
Edmonton
Houston
Montreal
Pittsburgh
Heating dry
bulb (99%)
Cooling dry
bulb (2%)
Mean coincident
wet bulb
30.5 8C
0.4 8C
21.8 8C
14.1 8C
24.0 8C
33.5 8C
25.8 8C
28.7 8C
15.7 8C
24.9 8C
19.5 8C
20.6 8C
506
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
Fig. 7. Effect of the climate on the cooling and reheating energy consumption of the
ventilation system.
Fig. 8. Effect of the climate on the heating and humidification energy consumption
of the ventilation system.
interesting to note that the peak energy consumption for cooling–
reheating is for every city higher than the one for heating–
humidification.
The predicted total annual energy consumption of the
ventilation system for Edmonton, Houston, Montreal and Pittsburgh is 1278 MWh, 4033 MWh, 1435 MWh and 2228 MWh,
respectively. The distribution of this total among the four
processes is shown in Fig. 9. Cooling uses the largest part in
Houston, Pittsburgh and, surprisingly, Montreal while in Edmonton the largest part is used for heating. Humidification requires a
very small part of the total energy consumption in all cases.
The impact of the climate on the temperature of the ice surface
is quite small (1 8C) since this variable is essentially determined
by the temperature of the brine which for these simulations is the
same throughout the year for all four cities. Therefore the values of
IST are not presented here. However, it should be noted that these
values are somewhat influenced by the temperature of the air
above the ice which depends on whether the radiant heating is on
and whether the ventilation air is heated or cooled. Thus the IST for
all cities is slightly higher in winter, when heating is required, than
in summer, when the ventilation air requires cooling. Similarly, the
IST during the summer is a little bit higher in Edmonton than in
Houston since the former city requires much less cooling of the
ventilation air and necessitates heating of the stands as shown in
Fig. 10. This last figure also shows that the radiant heating of the
stands exhibits the expected seasonal behaviour, that it is
significantly smaller in Houston and quite important in Edmonton
even during the summer. It should be noted that the daily energy
consumption of the radiant heaters is for all cities significantly
lower than the corresponding values of the ventilation system
(sum of consumption shown in Figs. 7 and 8).
Fig. 11 shows the influence of the climate on the refrigeration
load, i.e. on the sum of the heat reaching the brine from the ice and
from the ground. This quantity is greatest for Houston where the
seasonal variation is also the least pronounced. This result is
consistent with the climatic conditions which signify that the
Fig. 9. Effect of the climate on the annual energy consumption of the ventilation system.
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
507
Fig. 10. Effect of the climate on the energy consumption of the radiant heating.
Fig. 11. Effect of the climate on the refrigeration load.
envelope and indoor air are warmer in Houston and that, therefore,
heat fluxes towards the ice by both radiation and convection are
also higher in this city. Furthermore, because the humidity is
higher in Houston the corresponding heat flux due to condensation
of water vapour on the ice is also higher in this city. The
combination of all these effects explains the results shown in this
figure.
Table 3 compares the annual refrigeration load and the
corresponding energy consumption of the different systems for
each city. It confirms the fact that the refrigeration load is greatest
for Houston and shows that this quantity is always smaller than
the energy consumption by the ventilation system. It is important
to note that the refrigeration load does not vary significantly (less
than 7.5% of the average value) between these four locations
despite their very different climates. This is attributed to the fact
that the indoor conditions are quite similar due to the controls on
the ventilation system and the radiant heaters. However, it is
expected that the energy consumption of the refrigeration system
will be higher in locations with warm climates since the
condensation temperature and pressure will be higher than in
locations with cold climates.
Table 3 also shows that the energy consumed by the lights and
the brine pump does not depend on the climate in accordance with
the modeling assumptions. Lighting consumes more energy than
the radiant heaters for each of the four locations under
consideration while the same is true for the energy used by the
brine pump in three of the four cities. The greatest and smallest
contributors to the total energy consumption are the ventilation
system and the underground heater respectively for each of the
four cities under consideration. Finally, the total annual energy
consumption is highest, by a considerable margin, in Houston
(where summer operation requires considerable quantities of
energy for cooling and dehumidification) and lowest in Edmonton.
Table 4 shows the energy consumption by the underground
heater which is activated to avoid freezing and heaving of the
ground under the concrete slab. Its operation is not at all necessary
in the case of the warmer climates (Houston and Pittsburgh) while
in Edmonton and Montreal it is in operation for approximately 7
and 5 months, respectively.
3.2. Effects of the hysteresis of the thermostat
The influence of this parameter is established by comparing the
results for an electronic thermostat with a hysteresis of 0.2 8C
with those for a conventional bimetallic thermostat with a hysteresis
of 1.5 8C. The set point is 15 8C in both cases.
Fig. 12 shows that the refrigeration load is always higher in the
case of the electronic thermostat. The difference varies from
Table 3
Annual energy consumption of different systems and annual refrigeration load for each city (MWh).
Annual refrigeration load
Edmonton
Houston
Montreal
Pittsburgh
1023
1110
979
1018
Annual energy consumption of different systems
Ventilation system
Radiant heating
Underground heating
Lighting
Brine pump
Total
1278
4033
1435
2228
133
30
86
74
40.5
0
30.1
0
148.7
148.7
148.7
148.7
98.1
98.1
98.1
98.1
1698.3
4309.8
1797.9
2548.8
Table 4
Monthly underground electrical heating for each city (MWh).
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
508
Fig. 12. Effect of the thermostat hysteresis on the refrigeration load.
Fig. 14. Effect of the brine inlet temperature on the refrigeration load.
approximately 125 kWh/day in summer to 200 kWh/day in winter.
This result can be explained by the fact that the radiant heating is
turned on more frequently with an electronic thermostat in order
to maintain the temperature in the zone occupied by the spectators
at (15 0.2) 8C; therefore the corresponding average air and
envelope temperatures are slightly higher and result in increased
convective and radiative fluxes towards the ice. However, the energy
savings associated with the conventional thermostat are achieved at
the expense of the spectators comfort since in that case the air
temperature above the stands oscillates between 13.5 8C and 16.5 8C.
The smaller difference in summer energy consumption between the
two cases under consideration is due to the fact that the radiant
heating load is greatly reduced during these warm months.
It should also be noted that the type of thermostat influences
the ice temperature, i.e. its quality. Thus the temperature of the ice
surface is higher for the base case (electronic thermostat) by
approximately 0.25 8C in winter and 0.15 8C in summer.
elements is set to 15 8C during the day and 7 8C during the
unoccupied night hours, while in second case the thermostat is set
to 15 8C throughout the day.
Fig. 13 shows that the use of a thermostat with nocturnal set
back (base case) reduces the refrigeration load. However, this
reduction is very small (it varies from 25 kWh/day during the
winter to 50 kWh/day during the summer). It is due to the decrease
of the operation time of the radiant heating elements and the
corresponding reduction of the air and envelope temperatures
which in turn lower the convective and radiative fluxes towards
the ice. The corresponding effect on the IST is insignificant
(reduction of 0.1 8C when nocturnal set back is used) since these
flux reductions are small compared to their respective values.
Finally, it is important to note that the heat flux from the ground to
the brine is totally unaffected by the use, or not, of the nocturnal set
back since the conditions below the concrete slab are independent
of those prevailing within the ice rink.
3.3. Effect of the nocturnal set back
3.4. Effect of the brine inlet temperature
Two cases are compared in this section. The first one is the base
case in which the thermostat controlling the radiant heating
Three different constant brine inlet temperature were used for
this study (Tb,in = 8 8C, 9 8C and 10 8C). Fig. 14 shows that the
Fig. 13. Effect of the nocturnal set back on the refrigeration load.
Fig. 15. Effect of the ice thickness on the refrigeration load.
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
509
Table 5
Effect of the ice thickness on the January temperatures of the ice and the brine.
Ice thickness (cm)
2.54
5.08
7.62
Temperatures (8C) (January)
Ice surface
Brine (inlet)
Difference
6.20
5.97
5.74
9.0
9.0
9.0
2.8
3.03
3.26
Table 6
Effect of the ice thickness on the July temperatures of the ice and the brine.
Ice thickness (cm)
2.54
5.08
7.62
Temperatures (8C) (July)
Ice surface
Brine (inlet)
Difference
5.46
5.13
4.83
9.0
9.0
9.0
3.54
3.87
4.17
refrigeration load increases when the inlet brine temperature
decreases. The increase is about 100 kWh/day for each decrease of
Tb,in by 1 8C. This behaviour is qualitatively logical since the brine
acts as a heat sink while the conditions of the heat sources above
and below the concrete slab remain the same for these three
simulations.
A 1 8C increase or decrease of the inlet brine temperature causes,
respectively, an augmentation or diminution of 0.8 8C of the ice
surface temperature, for all months of the year. An analogous
observation can be made for the outlet brine temperature which
increases or decreases by the same amount as the inlet brine
temperature.
Fig. 16. Effect of the insulation thickness on the heating rate from the soil.
3.5. Effect of the ice thickness
Fig. 15 shows that the refrigeration load decreases slightly with
the increase of the ice thickness. It is reduced by 8–10% when the ice
thickness triples (from 2.54 cm to 7.62 cm). This is due to the
corresponding increase of the thermal resistance of the ice sheet
which also causes a small increase of the IST. The increase of the
latter is greater in summer due to the augmentation of the
convection and radiation fluxes during this warm season. Furthermore, Tables 5 and 6 show that, when the ice thickness is increased
by 5 cm, the temperature difference between the ice surface and the
brine increases by 14% (from 2.8 8C to 3.26 8C) for the month of
January and by 18% (from 3.54 8C to 4.17 8C) for the month of July.
These results should not be generalised. They have been
calculated by fixing the brine inlet temperature and do not
necessarily apply to other control strategies (such as, for example,
cases where the ice surface temperature is kept constant).
3.6. Effect of the insulation thickness
Fig. 16 shows that an increase of the underground insulation
thickness from 10 cm to 30 cm reduces the heat rate transferred to
the brine pipes from the soil by approximately 25% for all months of
the year. It should also be noted that the change of insulation
thickness has an insignificant effect on the heat rate from the ice to
the brine pipes. However, the effect of this reduction of the heat rate
from the soil on the total refrigeration load is not significant since
the former is less than 10% of the latter (cf. Fig. 15). The most
important impact of added underground insulation is to reduce the
risk of freezing under the concrete slab which can cause heaving
and damage to the ice. Fig. 17 which shows the average temperature
of node 5 situated at the sand–insulation interface clearly illustrates
this effect. Furthermore, as this insulation thickness is increased the
energy consumption of the electrical element in the sand can be
reduced without increasing the danger of freezing.
Fig. 17. Effect of the insulation thickness on the temperature of the insulation–sand
interface.
4. Non-linear correlations of energy loads
This section presents four correlations between the monthly
mean value of the energy consumption (in kWh/day) of the
different processes taking place in the ventilation system and the
corresponding sol-air temperature (in 8C) calculated with the
expression and parameters proposed by ASHRAE [17]. They are
based on numerous simulations carried out at the four selected
cities (Montreal, Edmonton, Houston and Pittsburgh).
Cooling load correlation:
2
Q Cool ¼ 283:96 þ 189:1 T sol-air þ 4:85 Tsol
-air
(14a)
Reheating load correlation:
2
Q Re heat ¼ 8:63 þ 192:58 T sol-air 2:217 Tsol
-air
(14b)
Heating load correlation:
2
Q Heat ¼ 1943:1 140:23 T sol-air þ 1:89 Tsol
-air
(14c)
Humidification load correlation:
2
Q Humid ¼ 44:9 10:95 T sol-air þ 0:79 Tsol
-air
(14d)
Figs. 18 and 19 show that these fairly simple correlations agree
quite well with the calculated values. These results also show that
510
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
The annual refrigeration load does not vary significantly (less
than 7.5% from the mean value) between these four locations
despite their very different climates.
The annual energy consumption by the ventilation system is
significantly influenced by the meteorological conditions; it is
highest in hot and humid locations and is always greater than the
corresponding refrigeration load.
The annual energy consumptions by the radiant heaters and by
the underground electric heater are very small compared to the
refrigeration load even in the coldest of the four cities under
consideration.
The main results of the other parametric studies are the
following:
Fig. 18. Energy consumption of ventilation system (cooling/reheat) vs. sol-air
temperature.
The use of an electronic thermostat with a low hysterisis
(0.2 8C) rather than a bimetallic one with a high hysteresis
(1.5 8C) increases the refrigeration load by more than 10% if the
same set point is used in both cases; however the energy savings
associated with the bimetallic thermostat are achieved at the
expense of the spectator’s comfort.
The use of a thermostat with nocturnal set back results in a small
reduction of the refrigeration load.
A reduction of the brine temperature causes an increase of the
refrigeration load and an almost equal reduction of the ice
surface temperature.
An increase of the ice thickness causes a decrease of both the
refrigeration load and the ice surface temperature.
An increase of the underground insulation thickness causes a
slight decrease of the refrigeration load and reduces significantly
the danger of ground freezing and heaving.
Finally, four correlations expressing the energy consumptions
for heating and humidifying, or cooling and reheating, the
ventilation air in terms of the sol-air temperature have been
proposed.
Acknowledgements
Fig. 19. Energy consumption of the ventilation system (heating/humidification) vs.
sol-air temperature.
the energy consumption by the heating and cooling processes
depend heavily on Tsol-air while those by the reheat and, in
particular, humidification processes are less dependent on this
parameter.
5. Conclusion
A transient model which calculates heat transfer through the
ground towards the brine pipes imbedded in the concrete slab
under the ice of an indoor ice rink has been formulated and coupled
with a previously developed one which calculates heat fluxes in the
building by convection, radiation and phase changes. The resulting
simulation tool has been enriched with subroutines which
calculate the energy consumption for heating and humidifying,
or cooling and reheating, the ventilation air. After validation with
experimental results, this tool was used to evaluate the refrigeration load as well as the energy consumed by the radiant heaters of
the stands, each process of the ventilation system, the lights, the
brine pump and the underground electric heater over a typical year
at four North American locations (Edmonton, Houston, Montreal,
Pittsburgh) with very different meteorological conditions. The
results of this analysis show that:
This study was financed by the Natural Sciences and
Engineering Research Council (NSERC) of Canada through the
Strategic Project Grant STPGP 306792 (Title: Development of
design tools and of operation guidelines for the heating,
ventilation, air conditioning and refrigeration systems of ice
rinks).
Appendix A
The expressions of the 7 T 7 matrix A and of the vectors B and T in
Eq. (10) are:
1
1
0
0
0
0
0
C
B Að1; 1Þ R
Ice
C
B
C
B 1
1
C
B
Að2;
2Þ
0
0
0
0
C
B R
Rc1
B Ice
C
B
C
1
1
B 0
C
Að3;
3Þ
0
0
ṁ
C
B
PB
B
C
R
R
c1
c2
B
C
C
1
1
A¼B
B 0
C
0
Að4; 4Þ
0
0
B
C
R
R
Ins
c2
B
C
B
C
1
1
C
B 0
Að5; 5Þ
0
0
0
C
B
RIns
RSand
C
B
C
B
1
C
B 0
0
0
0
Að6;
6Þ
0
A
@
RSand
0
0
2
0
0
0
1
0
(A.1)
L. Seghouani et al. / Energy and Buildings 41 (2009) 500–511
1
ðM C p Þeq1 p
Q Ice þ
T1
B
C
B
C
Dt
B
C
ðM
C
Þ
p eq2 p
1
B
C
T2
U 2 S2 T gr
B
C
B
C
2
D
t
B
C
ðM
C
Þ
p
1
B
eq3 p C
B ṁB C pB T In U 3 S3 T gr
T3 C
B
C
2
Dt
B
C
ðM C p Þeq4 p
B¼B
C
1
B
C
U
S
T
T
gr
4
4
4
B
C
2
D
t
B
C
ðM C p Þeq5 p
B
C
1
B
C
T5
Q H U 5 S5 T gr
B
C
2
D
t
B
C
B
C
ðM C p Þeq6 p
1
1
B Q U S T gr
T7 C
T6
6 6
H
@
A
2
RSoil
Dt
T in
0
ðM C p Þeq1
Að2; 2Þ ¼
Að3; 3Þ ¼
Að4; 4Þ ¼
Að5; 5Þ ¼
Að6; 6Þ ¼
1
RIce
!
ðM C p Þeq2
1
1
1
þ
þ U 2 S2 þ
RIce Rc1 2
Dt
!
ðM
C
p Þeq3
1
1
1
þ
þ U 3 S3 þ
Rc1 Rc2 2
Dt
!
ðM
C p Þeq4
1
1
1
þ
þ U 4 S4 þ
RIns Rc2 2
Dt
!
ðM C p Þeq5
1
1
1
þ
þ U 5 S5 þ
RSand RIns 2
Dt
!
ðM C p Þeq6
1
1
1
þ
þ U 6 S6 þ
RSoil RSand 2
Dt
Dt
1
1
MIns C PIns þ M Sand C PSand
2
2
(A.5e)
ðM C p Þeq6 ¼
1
1
M
CP
þ M CP
2 Sand Sand 2 Soil Soil
(A.5f)
References
(A.3)
Here the coefficients in Eq. (A.1) are
Að1; 1Þ ¼
ðM C p Þeq5 ¼
(A.2)
and
Pþ1
T ¼ T1pþ1 T2pþ1 T3pþ1 T4pþ1 T5pþ1 T6pþ1 TOut
511
þ
(A.4)
And the equivalent thermal capacity in Eqs. (A.2) and (A.4) is
calculated as follows:
ðM C p Þeq1 ¼
1
M Ice C PIce
2
(A.5a)
ðM C p Þeq2 ¼
1
1
M Ice C PIce þ Mc1 C PC
2
2
(A.5b)
ðM C p Þeq3 ¼
1
M B C PB
2
(A.5c)
ðM C p Þeq4 ¼
1
1
M c2 C PC þ M Ins C PIns
2
2
(A.5d)
[1] M. Lavoie, R. Sunyé, D. Giguére, Potentiel d’économies d’énergie en réfrigération
dans les arénas du Québec, Report prepared by the CANMET Energy Technology
Center, 2000.
[2] P.J. Jones, G.E. Whittle, Computational fluid dynamics for building air flow
prediction—current status and capabilities, Building and Environment 27 (3)
(1992) 321–338.
[3] Z. Jian, Q. Chen, Airflow and air quality in a large enclosure, ASME Journal of Solar
Energy Engineering 117 (2) (1995) 114–122.
[4] C. Yang, P. Demokritou, Q. Chen, J.D. Spengler, A. Parsons, Ventilation and air
quality in indoor ice skating arenas, ASHRAE Transactions 106 (2) (2000) 338–
346.
[5] O. Bellache, M. Ouzzane, N. Galanis, Coupled conduction, convection, radiation
heat transfer with simultaneous mass transfer in ice rinks, Numerical Heat
Transfer Part A 48 (2005) 219–238.
[6] O. Bellache, M. Ouzzane, N. Galanis, Numerical prediction of ventilation and
thermal processes in ice rinks, Building and Environment 40 (3) (2005) 417–
426.
[7] O. Bellache, N. Galanis, M. Ouzzane, R. Sunyé, D. Giguére, Two-dimensional
transient model of airflow and heat transfer in ice rinks (1289-RP), ASHRAE
Transactions 112 (2) (2006) 706–716.
[8] M. Ouzzane, R. Sunyé, R. Zmeureanu, D. Giguére, J. Scott, O. Bellache, Cooling load
and environmental measurements in a Canadian indoor ice rink (1289-RP),
ASHRAE Transactions 112 (2) (2006) 538–545.
[9] A. Daoud, N. Galanis, Calculation of the thermal loads of an ice rink using zonal
model and building energy simulation software, ASHRAE Transactions 112 (2)
(2006) 526–537.
[10] A. Daoud, N. Galanis, O. Bellache, Calculation of refrigeration loads by convection,
radiation and condensation in ice rinks using a transient 3D zonal model, Applied
Thermal Engineering (2007), http://dx.doi.org/10.1016/j.applthermaleng.2007.
11.011.
[11] A. Daoud, Analyse des transferts de chaleur et de masse transitoires dans un aréna
à l’aide de la méthode zonale, Thèse de doctorat en sciences appliquée, Université
de Sherbrooke (Québec), Canada, 2007.
[12] TRNSYS, A transient system simulation program, Software Manual, Solar Energy
Laboratory, University of Wisconsin-Madison, 2000.
[13] B. Gebhart, Heat Transfer, Second edition, McGraw-Hill, 1971.
[14] ASHRAE, Ice Rinks, ASHRAE Handbook-Refrigeration, American Society
of Heating, Refrigeration, and Air-Conditioning Engineers, Inc., Atlanta,
2002.
[15] ENERGYPLUS, http://www.eere.energy.gov/buildings/energyplus/.
[16] ASHRAE, Residential cooling and Heating load Calculations ASHRAE Handbookfundamentals, American Society of Heating, Refrigeration, and Air-Conditioning
Engineers, Inc., Atlanta, 2005, pp. 29.11–29.12.
[17] ASHRAE, Non-residential cooling and Heating load Calculations ASHRAE Handbook-fundamentals, American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc., Atlanta, 2001, pp. 29.14–29.17.