Aquacultural Engineering 41 (2009) 114–121
Contents lists available at ScienceDirect
Aquacultural Engineering
journal homepage: www.elsevier.com/locate/aqua-online
Coldwater RAS in an Arctic charr farm in Northern Norway
Steinar Skybakmoen a,*, Sten Ivar Siikavuopio b, Bjørn-Steinar Sæther b
a
b
OppdrettsTeknologi (Fishfarming Technology), Nordslettveien 177, N-7038 Trondheim, Norway
Nofima Marin, N-9291 Tromsø, Norway
A R T I C L E I N F O
A B S T R A C T
Keywords:
Coldwater
Recirculating
Water quality
Water quality variations
Use of coldwater recirculating aquaculture systems (RAS) are still very rare in Norway, and only two
farms are producing Arctic charr. This project took place in one of these commercial Arctic charr farms;
Villmarksfisk AS in Bardu, Northern Norway.
The farm gets its make-up water from ground water that holds 5 8C year around. Temperature in the
rearing water varies between 7.5 8C (‘‘low’’) to 12 8C (‘‘high’’) through the year. The biological filter in the
RAS seems to work stable at both ‘‘low’’ and ‘‘high’’ temperatures, including after incidents when feeding
has been stopped for a day and started on top again the day after. Such an extreme change in loading was
measured as a 70% increase in TAN concentration, with only minor changes in nitrite levels recorded. The
biofilter also kept the nitrite stable and low in spite of diurnal variation in TAN excretion at normal
feeding regimes (every day in three periods at day-time).
The farming concept is to stock the farm with wild caught juvenile fish for on-growing to market size
fish (0.75–1.00 kg). A drop in growth rate during early autumn has been a main concern for the farm. This
may reflect a seasonal shift in growth potential, sometimes referred to as ‘‘autumn depression’’.
Interestingly, there is little sign of seasonal changes in the growth of hatchery-produced fish tested in the
farm. Sampling of water quality through the seasons in tanks holding fish undergoing such growth
depressions indicate that TAN excretion is much higher per kg feed used in the wintertime than in the
springtime. This observation corresponds with the lack of weight gain during wintertime despite that the
fish is feeding. Thus, feed conversion calculations indicate that feed utilization also varies with season
reaching its nadir during this period.
Both challenges concerning RAS in cold water and strongly reduced growth in autumn and winter
time, have been investigated from 2005 to 2007 in a project financed by the Norwegian research council
and the partners in the agricultural framework agreement.
ß 2009 Elsevier B.V. All rights reserved.
1. Introduction
Arctic charr (Salvelinus alpinus L.) is the northernmost
distributed freshwater fish and is considered the most coldadapted species within the salmonid family (Johnson, 1980). The
growth of Arctic charr populations is variable under natural
conditions (Johnson, 1980; Sæther et al., 1996). Arctic charr
tolerate high-density culture conditions, have an excellent fillet
yield, are amenable to niche marketing, and are suitable for
production within super-intensive recirculating systems (Jobling,
1987; Johnston, 2002; Summerfelt et al., 2004a,b).
The company Villmarksfisk AS in Northern Norway (Bardu
community in Troms county) operate an on growing (grow out)
farm based on wild caught Arctic charr from lake Altevatn situated
approximately 40 km from the farm (Siikavuopio et al., 2009a). The
* Corresponding author. Tel.: +47 4804 7204.
E-mail address:
[email protected] (S. Skybakmoen).
0144-8609/$ – see front matter ß 2009 Elsevier B.V. All rights reserved.
doi:10.1016/j.aquaeng.2009.06.007
farm consists of a fully insulated building with two separate
compartments each of 200 m3 rearing volume (four tanks each
50 m3; 45 m3 effective). Each compartment has their own
recirculation system and both utilize the same source for makeup water; ground water from a borehole close to the building.
Effluent water is discharged back to the ground in an infiltration
system.
A flow chart for the farm is shown in Figs. 1–3 show a simplified
sketch of the farm and a picture inside the farm. The fish rearing
installation and recirculation system were in place in 2002 and in
operation from 2003. First regular year of operation was 2004.
2. Technical installations
The rearing tanks are constructed as octagonal tanks where
four tanks are put together in a square to share the inner walls. The
walls are being built of vertical aluminium profiles on a concrete
bottom. The inside of the tank walls are covered with fibre glass
sheets which are glued together in the corners by sheets of
S. Skybakmoen et al. / Aquacultural Engineering 41 (2009) 114–121
115
Fig. 1. Process flow chart for Arctic charr farm in Northern Norway. This flow sheet represents one of two identical production systems (Compartment A and B).
polypropylene with a back-side of polyester. Each tank has a
particle trap at the centre of the tank bottom with a sludge
collector outside the tank that also allows inspection of the sludge
production and feed loss (EcoTrap 250 with 70 L sludge collector;
main outlet pipe dimension and outlet screen is Ø250 mm reduced
to pipe Ø200 just after the trap; particle hose to the sludge collector
is Ø50 mm). The water then passes through a mechanical filter
with 60 mm openings (Hydrotech HDF 1202-1H, 0.37 kW). From
the mechanical filter, water flows into a common sump for
aeration, trickling biofilter and sump for both pumps lifting water
to the top of the trickling biofilter and for the pumps lifting water
back to the tanks. This sump is made of polyethylene plates welded
together by extruder to a rectangular unit with a length of 9 m,
water depth of 0.8 m and width of 1.4 m, total water volume of
10 m3.
At the bottom of the common sump a number of 60 diffusors
provide aeration/CO2-removal (Nopon MKP 600 Tube diffuser,
Finland). These are fed by a blower (Venture HPB-200-XX-500T,
5.5 kW, Sweden). Gas to water ratio is 5:1 and the degassed CO2 is
removed from the compartment through an outer wall ventilation
channel of 0.1 m2 situated at floor level. Two pumps (Grunfos NB
80-160/177, 3 kW, Denmark) lift the water to the biofilter,
installed for parallel operation and with stationary frequency
(constant rpm). The trickling biofilter consist of 84 blocks each
0.55 m 0.55 m 0.55 m size (Bio-blok 200 from Exponet, Denmark). There are seven modules of blocks, in three layers and 2 by 2
Fig. 2. Simplified sketch of the farm, Villmarksfisk AS.
116
S. Skybakmoen et al. / Aquacultural Engineering 41 (2009) 114–121
Fig. 4. Flow chart for the spreadsheet. Make-up water is actually not introduced
direct to the rearing tank, but in the common sump under the biofilter where CO2removal takes place.
Fig. 3. From inside one of the departments.
in each layer. The water is distributed from the top of the biofilter
via seven rotating pipes, one for each module. These pipes turn
around as water hits the top of the biofilter. When both pumps are
working (normal operation), the hydraulic surface load is 472 L/
min/m2.
The two recirculation pumps (Grunfos NB 100-200/100, 5.5 kW,
Denmark) that lift the water back to the tanks, are installed at far
end to the water inlet from the mechanical filter in the common
sump. One of these pumps has a frequency controller, the other
have stationary frequency. To this time, it has not been necessary
to operate both pumps simultaneously. Before reaching the tanks,
the water passes oxygen saturator units, one at each tank (Inline
Down Flow Bubble Contactor, AquaOptima, Norway). Water is
distributed into the tanks through vertical pipes (Ø160, located
25 cm from the tank wall) via 25 Ø18 mm holes. This provides a
unidirectional circular water movement in the tanks enabling
some control of the water velocity and thereby the fish’s
swimming speed.
Collected sludge from mechanical filters and sludge collectors is
stored during winter time in two insulated under ground fibre
glass tanks (35 m3 each). The sludge is utilized as fertiliser/soil
improvement on grass fields during the summer season.
as low as possible, and it is crucial that personnel operating this
attend to keep it clean and effective. To this point the biofilter has
been operationally very stable without any clogging problems.
The diffusors at the bottom of the common sump has been in
operation continuously without any cleaning and they still seems
to work properly. Although there is a tendency for higher CO2-level
which may be partly explained by clogged diffusors.
4. Biological experiences
The farm’s production is based on wild caught fish from a
nearby lake. Capture normally takes place from February until
March–April, or as long as the ice is strong enough to support a safe
operation. Some catching also takes place by boat during the
summer. Reduced growth in late summer and during most of the
autumn and winter has been a major problem. High mortality has
also been experienced (Siikavuopio et al., 2009b). The most severe
growth problem was experienced in a small scale highly controlled
trial at the farm in 2005–2006. Specific growth rate declined
dramatically during the period from July until late October. From
November till January the growth increase, but is still lower than
what can be expected for hatchery-produced fish (Sæther et al.,
1996; Siikavuopio et al., 2009a). It has also been observed fish that
apparently thrives well, based on appetite, still show poor growth
rates combined with high mortality.
3. Technical experiences
5. Investigation plan 2005–2007
The main water flow through pumps (recirculation pumps) are
dimensioned for 1000 L/min per tank. This flow is too high for the
particle trap main outlet screen, creating a very high swirl velocity
in the tank surface centre and standing waves in the tank. Normal
main flow has been 350–550 L/min depending on loading. The
particle trap system restrain only approximately 50% of feed loss
and faeces from the fish, however, this is sufficient to get an
impression of the appetite of the fish. The main problem with the
particle trap is the fouling inside the trap and in the small hoses
between the trap and the sludge collector. The mechanical filter
plays a key role for controlling organic matter and keeping the BOD
The recirculating systems at the farm showed good performance from the very beginning. A concern, however, was that
there was lack of practical experience on water quality and water
treatment efficiency in such systems with relatively cold water and
high variation in organic loading from fish with un-known feeding
capacity and excretion. It was also a concern that water quality
calculations were complicated for people with mainly technical
background and no comprehensive skills in water chemistry. In
order to make some progress in this field, the project investigation
plan was set up by a combination of:
Table 1
Day and night measurements series; date and general situation at the time.
Date/period
Department
Water
temperature (8C)
Feeding
(kg/24 h)
Light/darkness
(h)
Make-up
water (L/min)
Tank volume
(m3)
Total flow
through (L/min)
2005 April 20–21a
2006 November 15–16
2007 September 17–18
Hall A
Hall B
Hall B
10.6
7.5
11.6
57.6
16.0
70.4
L/D 24/0
L/D 24/0
L/D 24/0
133
190
120
4 45
3 45
4 45
1800
1500
1800
a
In 2005, the measurement was done the day after a complete feeding stop. In November 2006 and in September 2007 feeding was regular at day-time (3 or 4 feeding
periods of 1–2 h duration).
117
S. Skybakmoen et al. / Aquacultural Engineering 41 (2009) 114–121
Table 2
Measured pH and alkalinity, both measured and calculated the CO2-content and calculated difference between calculated and measured CO2.
Date
2006
2007
2007
2007
a
b
c
d
e
f
November 15
August 22
September 18
September 18
Water type
Measured
CO2 (mg/L)
Measured
pH
Measured
alkalinity
(mg/L CaCO3)
Calculated
CO2 (mg/L)
Groundwater
Effluent water
Groundwater
Effluent water
13a
18b
13b
22b
7.48c
7.29d
7.42d
7.06d
180e
155e
165e
130e
11.9f
15.9f
12.5f
22.6f
Difference between
calculated and
measured CO2
(% of measured value)
8.5
11.7
3.9
+2.7
Method: Oxyguard CO2 analyser.
Method: LaMotte carbon dioxide test kit, model PCO-DR, code 7297-DR.
Method: Oxyguard pH Manta.
Method: Hanna instrument pH/ORP Meter HI 98150, sensor HI 1618D.
Method: Merck alkalinity test 1.11109.0001.
Formula: CO2 = alkalinity 10(6.3 pH).
Technical system input (as correct as possible by measurements
and registrations).
Water quality measurements (as correct as possible with field
test kits and methods).
Water quality calculations (as correct mass balances as possible
for TAN and CO2 combined with simplified formulas for the
carbonate system).
All relevant information was summarized and controlled by
means of a spreadsheet based on a flow chart (Fig. 4). The general
idea was to use it as a calculation control system at the same time
as the water quality measurement was done; establish an
understanding of the importance of measured water quality
parameters. Table 1 shows an overview of the intensive day and
night measurements series performed at the farm. In April 2005,
the measurement was done the day after a complete feeding stop.
In November 2006 and in September 2007 feeding was regular at
day-time (three or four feeding periods of 1–2 h duration).
somewhat different: 06:00–08:00, 12:00–13:00 and 17:00–
18:00, see Fig. 6.
In order to examine the TAN excretion, several calculations have
been done based on measuring TAN, nitrite, nitrate, feeding and
make-up water use. Not surprising, there are periods when TAN
excretion is much higher than the theoretical medium value.
Reasons for this can be feed loss or that the fish is not able to utilize
the feed as expected. More surprising is the measurement from
2007, when the TAN excretion was much below 3.25% (2.74%).
However, this can be related to the fact that the measurement was
taken early autumn and that the fish still utilized the feed very well.
Later in the autumn, e.g. as in November 2006, the TAN excretion
recording was much higher (8.1%) than the expected value of 3.25%.
It is only the measurement in springtime 2005 that indicate a TAN
excretion close to the expected medium value of 3.25%.
In order to decide CO2-excretion in a recirculation system,
excretion from the bacterial activity in the biofilter should also be
included. However, in a trickling filter the CO2-excretion in the
6. Water quality considerations and calculations
In April 2005 the ground water was evaluated for total gas
pressure (oxygen, CO2 and nitrogen). The water had very low
oxygen saturation (47%), high content of CO2 (2200%) and was
supersaturated with nitrogen (110%). The total gas pressure (97%)
was close to barometric pressure. In February 2004 oxygen
saturation was 57% and pH 7.24. Alkalinity was considered to be
stable at 3.5 mmol/L (175 mg/L CaCO3) and CO2 was expected to be
high, around 20 mg/L. Other measurements taken are set up in
Table 2. From these measurements it was considered to be
acceptable to use the simplified formula CO2 (mg/L) = alkalinity
(mg/L CaCO3) 10(6.3 pH) for (Summerfelt, 1996) further calculations of the relationship between pH, alkalinity and CO2.
7. Ammonium and CO2-excretion
As a starting point, it was assumed 32.5 g TAN excretion per kg
feed (3.25%) for the feed used (Nutra Parr, protein content 50%,
Skretting). Further, it was assumed that this excretion is a medium
value over 24 h. More conservative estimations say 4.6% in TAN
excretion (NRAC 2002), approximately 40% higher than the
present start point. Our measurements in 2007 shows that the
TAN content in the water was 37% higher at night-time as
compared to day-time when feeding took place at day-time. Fig. 5
shows the variation in TAN content in treated water. The feeding
periods were 07:00–08:00, 13:00–14:00, 16:00–17:00 and
19:00–20:00. From the measurement in 2005 the TAN content
was 42% higher in the night than the medium level; however, it is
important to recognise that at that day the feeding had been
stopped the day before. The regular feeding times were also
Fig. 5. Variation in TAN content in treated water through 24 h; from 2007.
Fig. 6. Variation in TAN content in treated water through 24 h; from 2005.
118
S. Skybakmoen et al. / Aquacultural Engineering 41 (2009) 114–121
biofilter is likely to be released very quickly. For the purpose of
calculations, the CO2-excretion is set to 1.3 g/g O2-consumed and
the O2-consumption set to 0.35 kg oxygen per kg feed offered to
the fish.
8. Water quality simulation
The main reason for assessing water quality in a recirculation
system is to assure that the most important water chemical
parameters stays within acceptable levels, not compromising
animal welfare (Colt, 2006). Also, it is important to use the
measurements to supervise the functionality of the system
enabling farmers to take correct action if one or more parameters
have to be adjusted (Losordo et al., 2000; Losordo and Hobbs, 2000;
Summerfelt, 2002; Summerfelt et al., 1993). By means of a simple
spreadsheet it is possible to simulate the water quality in the
rearing tank volume and in the treated water. For the actual farm,
treated water is similar to the effluent water (see flow charts,
Figs. 1 and 4). The accuracy of this simulation depends on
knowledge of the following parameters:
Main water flow (L/min).
Make-up water flow (L/min).
TAN excretion (% per kg feed, etc.).
Removing efficiency of the water treatment processes.
Make-up water quality (alkalinity, pH and CO2).
Interactions between removing efficiency and water temperature.
All parameters involved in and influencing the carbonate system.
Fig. 8. Nitrification rate (TAN-removal rate) related to ammonium content in tank
effluent water at Villmarksfisk AS for 2005, 2006 and 2007-series (dots). The curve
in the diagram is a constructed line for preliminary dimensioning purposes.
the water. At Villmarksfisk the TAN-removal rate is calculated by
means of the earlier mentioned spreadsheet made for simulation of
the systems functionality and water quality. Fig. 7 shows the TANremoval rate relative to temperature for the three investigation
series performed in 2005, 2006 and 2007. Fig. 8 shows the TANremoval rate related to the TAN content in the outlet water from the
tanks, i.e. before the biofilter. The TAN-removal rate is generally as
expected, except for the series from September 2007, with the
removal rate being less than expected. This may be due to high CO2
levels, but it can also be other reasons not yet examined or
understood. For further information on biofilter and water quality
factors affecting nitrification rate, see Chen et al. (2006).
Examples:
By increasing main flow through, all excretion product concentration will be reduced as more water flow, e.g. to the CO2stripping unit hence more CO2 are being removed. This brings the
pH up.
Reduced make-up water will reduce the alkalinity import to the
system, and this will bring the pH down.
9. TAN-removal rate
In a biological filter, bacteria convert ammonia (TAN) to nitrite
(NO2) and nitrite is further converted to nitrate (NO3) (Timmons
et al., 2002; Eding et al., 2006). The second step work faster than the
first step and this is convenient because the acceptable limit of
nitrite is much lower than for nitrate (Timmons et al., 2002). Looking
at the TAN conversion separately, the TAN-removal rate is
influenced strongly by the temperature and the TAN content of
Fig. 7. Nitrification rate (TAN-removal rate) related to water temperature at
Villmarksfisk AS for 2005, 2006 and 2007-series (dots). The lines in the diagram are
a summary from different papers (Bovendeur, 1989; Eikebrokk, 1988; Rusten,
1986; Speece, 1973), see Gebauer et al. (2005) (textbook in Norwegian).
10. Operation and documentation from April 2005
Average water temperature was 10.6 8C and the feeding rate
was approximately 60 kg per 24 h in compartment A where day
and night measurements were performed. The purpose of the
measurements was to examine how the biofilter reacts to variation
in TAN excretion over a period of 24 h. In addition these
measurement series should also reflect the biofilter reaction to
the feeding stop the day before. The most important parameter in a
recirculation system is the level of nitrite. Some have experienced
sudden peaks in nitrite (e.g. in a pilot-scale farm at Villmarksfisk
using submerged biofilter) resulting in instant and high mortality.
The commercial scale system operating now does not give the
same surprises (Fig. 9), despite sudden increases in organic load.
Over a period of 12 h (3–15 h after start of feeding) the TAN content
in the system increased 200%, whereas the nitrite increased only by
12%. The nitrate-producing bacteria in the biofilter had no problem
to handle the increased production of nitrite as the nitrate content
Fig. 9. Ammonia content strongly increased in treated water, but not the nitrite
content.
S. Skybakmoen et al. / Aquacultural Engineering 41 (2009) 114–121
Fig. 10. Approximately 24% increase in nitrate content the first 12 h period, next
12 h period a 15% slow down.
119
Fig. 11. Normal variation in TAN content in treated water, very little variation in
nitrite.
increased with 24% over the same 12 h period (Fig. 10). In the next
period of 12 h (15–27 h after feeding start), the TAN content still
increased but at a slower rate (67%); the nitrite content increased
only 3%, and the nitrate content started to fall (15% reduction).
11. Operation and documentation from November 2006
During this period the farm struggled with very high mortality
due to saprolegnia (fungal infection). Water temperature was
dropped to 7.5 8C and feeding reduced. Fig. 11 shows the TAN
variation during a 24 h period of the measurement series. Feeding
time was 06:00–08:00, 12:00–13:00 and 17:00–18:00. The nitrite
content was low and stable and apparently the biofilter handled
the diurnal variation also at this low temperature. The content of
nitrate in the outlet water from the tanks where on average only 6%
higher than in the treated water. This indicate that the nitrification
(TAN-removal) mainly occurs in the biofilter and also that there is
very little suspended biofilm in the system (passive nitrification is
Fig. 12. Weak increase in CO2 level in effluent water from the tanks in the afternoon,
decreasing from midnight.
Fig. 13. Spreadsheet for water quality simulation; situation from 2007-series. All bold figures are input/assumed values, all other figures are calculated. The assumed values
for removal rates are adjusted in order to make the calculated values correspond with the measured values for TAN, CO2, alkalinity and pH.
120
S. Skybakmoen et al. / Aquacultural Engineering 41 (2009) 114–121
Fig. 17. CO2 variation day/night.
Fig. 14. TAN variation day/night in effluent water from the tanks.
Fig. 15. Alkalinity variation day/night.
Fig. 18. TAN and nitrite variation day/night in treated water.
as 0.3. On the contrary, during spring 2005 the CO2 removal rate
was 0.71 and the nitrification rate was 0.64. Another reason for low
nitrification rate can be high content of organic matter (BOD). This
was not measured, only calculated, and can therefore be underestimated. Compartment B operates as the fish entrance area. This
part of the farm has the most severe problems with fungus and
periodically very low feed utilization. This situation can result in
high organic load on the biofilter and, thus, reduced nitrification
rate.
Figs. 14–17 show the dynamics of TAN, alkalinity, pH and CO2.
The CO2 level was calculated whereas the other parameters are
measured. Despite some variation, the nitrification process is very
stable, as indicated in Fig. 18. The nitrite content was under 0.5 mg/
L-N, which is considered to be acceptable.
Fig. 16. pH variation day/night.
low). The CO2 content varies over 24 h in the effluent water from
the tanks (Fig. 12). The same picture appeared also in treated
water, however, with less variation, indicating difficulties with
removing CO2 when the CO2 content is low.
12. Operation and documentation from September 2007
During the autumn 2007, growth rates were good and
mortalities low as compared to the previous year. The fish were
treated with formaldehyde (1:3000) in order to reduce the
saprolegnia spp. infection, and this is likely to have contributed
to the improved performance. The previously mentioned simulation shows that CO2-level was high and this was attributed to
reduced efficiency of the diffusors (Fig. 13). This can affect the
nitrification rate in a negative way, which at this point was as low
13. Summary
The biofilters at Villmarksfisk AS are traditional trickling filters;
very robust filters that handle large variations in load. However,
compared with other filter media trickling filters are sometimes
considered as old fashioned and too space demanding. Because of
the very short water retention time in the filter, a trickling filter
needs a very high hydraulic flow through to maintain nitrification
stability. Biomedia that is submerged all the time usually have a
longer water retention time (contact time), and for these
applications it is easier to obtain a lower TAN and nitrite content
than in trickling filters. There are concerns, however, on how
submerged biofilters responds to large variability in nutrition load,
e.g. following a period with low load. Available literature dealing
with, e.g. moving bed biofilters points to sudden increase in TAN
load as critical events for these filters to handle (Rusten et al.,
2006). The trickling biofilter at Villmarksfisk seems to react fast
S. Skybakmoen et al. / Aquacultural Engineering 41 (2009) 114–121
enough at a relative high increase in TAN load, for instance such as
represented by feeding stop, and the nitrification rate is
satisfactory and stable at low temperature.
Acknowledgements
This paper is based upon work supported by the Norwegian
research council, the partners in the agricultural framework
agreement and Villmarksfisk AS. We want to thank Espen
Haugland at Norwegian Institute for Agricultural and Environmental Research (Bioforsk Nord), Tromsø, who acted as project
manager and his colleges Hallvard Jensen and Christian Uhlig.
Special thanks to Dagfinn Lysne and Nils Steien at Villmarksfisk AS
for all assistance and advice during the full duration of the project
period.
References
Chen, S., Ling, J., Blancheton, J.-P., 2006. Nitrification kinetics of biofilm as affected
by water quality factors. Aquaculture Engineering 34, 179–197 (Special Issue).
Colt, J., 2006. Water quality requirements for reuse systems. Aquaculture Engineering 34, 143–156 (Special Issue).
Eding, E.H., Kamstra, A., Verreth, J.A.J., Huisman, E.A., Klapwijk, A., 2006. Design and
operation of nitrifying trickling filters in recirculating aquaculture: a review.
Aquaculture Engineering 34, 234–260 (Special Issue).
Gebauer, R., et al., 2005. Oppdrettsteknologi. Vannkvalitet og Vannbehandling i
Lukkede Oppdretts-anlegg, 2nd edition. Tapir forlag, Trondheim, Norway, In
Norwegian (Translated title: Fish farming Technology. Water quality and water
treatment in closed fish farming systems).
Jobling, M., 1987. Growth of Arctic charr (Salvelinus alpinus L.) under conditions of
constant light and temperature. Aquaculture 60, 243–249.
Johnson, L., 1980. The Arctic charr, Salvelinus alpinus. In: Balon, E.K. (Ed.), Charrs,
Salmonid Fishes of the Genus Salvelinus. W. Junk, The Hague, Netherlands, 87 pp.
Johnston, G., 2002. Arctic Charr Aquaculture. Blackwell Publishing, 272 pp.
121
Losordo, T.M., Hobbs, A.O., DeLong, D.P., 2000. The design and operational characteristics of the CP&L/EPRI fish barn: a demonstration of recirculating aquaculture technology. Aquaculture Engineering 22, 3–16.
Losordo, T.M., Hobbs, A.O., 2000. Using computer spreadsheets for water flow and
biofilter sizing in recirculating aquaculture production systems. Aquaculture
Engineering 23, 95–102.
Rusten, B., Eikebrokk, B., Ulgenes, Y., Lygren, E., 2006. Design and operation of the
Kaldnes Moving Bed Biofilm Reactors. Aquaculture Engineering 34, 322–331
(Special Issue).
Summerfelt, S.T., Wilton, G., Roberts, D., Rimmer, T., Fonkalsrud, K., 2004a. Developments in recirculating systems for Arctic char in North America. Aquaculture
Engineering 30, 31–71.
Summerfelt, S.T., Davidson, J.W., Waldrop, T.B., Tsukuda, S.M., Bebak-Williams, J.,
2004b. A partial-reuse system for coldwater aquaculture. Aquaculture Engineering 31, 157–181.
Summerfelt, S.T., 2002. Final Project Report for USDA/ARS Grant No. 59-1930-8-038,
Technologies. Procedures and Economics of Cold-Water Fish Production and
Effluent Treatment in Intensive Recycling Systems. The Conservation Fund’s
Freshwater Institute, Shepherdstown, WV.
Summerfelt, S.T., 1996. Engineering design of a water reuse system. In: Summerfelt,
R.C. (Ed.), Walleye Culture Manual. NCRAC Culture Series 101. North Central
Regional Aquaculture Center Publications Office, Iowa State University, Ames,
pp. 277–309.
Summerfelt, S.T., Hankins, J.A., Summerfelt, S.R., 1993. Modeling continuous culture
with periodic stocking and selective harvesting to measure the effect on
productivity and biomass capacity of fish culture systems. In: Wang, J.K.
(Ed.), Techniques for Modern Aquaculture. American Society of Agricultural
Engineers, Siant Joseph, Michigan, pp. 581–595.
Siikavuopio, S.I., Sæther, B.-S., Skybakmoen, S., Uhlig, C., Haugland, E., 2009a. Effects
of a simulated short winter period on growth in wild caught Arctic charr
(Salvelinus alpinus L.) held in culture. Aquaculture 28, 431–434.
Siikavuopio, S.I., Skybakmoen, S., Sæther, B.-S., 2009b. Comparative growth study of
wild- and hatchery produced Arctic charr (Salvelinus alpinus L) in a coldwater
recirculation system. Aquaculture Engineering 41, 122–126.
Sæther, B.-S., Johnsen, H.K., Jobling, M., 1996. Seasonal changes in food consumption
and growth of Arctic charr exposed to either simulated natural or a 12:12 LD
Photoperiod at constant water temperatures. Journal of Fish Biology 48 (6),
1113–1122.
Timmons, M.B., Ebling, J.M., Wheaton, F.W., Summerfelt, S.T., Vinci, B.J., 2002.
Recirculating aquaculture systems, 2nd edition. NRAC Publication No.01-002.