UC Berkeley
Controls and Information Technology
Title
Cooling airflow design calculations for UFAD
Permalink
https://escholarship.org/uc/item/5j20s07v
Authors
Bauman, Fred
Webster, Tom
Benedek, Corinne
Publication Date
2007-10-01
Peer reviewed
eScholarship.org
Powered by the California Digital Library
University of California
©2007, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal,
Vol. 49, Oct. 2007. This posting is by permission of ASHRAE. Additional reproduction, distribution, or transmission in either print or digital
form is not permitted without ASHRAE’s prior written permission.
Cooling Airflow Design
Calculations for UFAD
By Fred Bauman, P.E., Member ASHRAE; Tom Webster, P.E., Member ASHRAE, and Corinne Benedek, Student Member ASHRAE
D
uring the past ten years as underfloor air distribution (UFAD)
CFM=
has begun to demonstrate significant growth in new commer-
cial office building construction in North America, design engineers
have often cited methods for airside design sizing as one of the most
important unanswered questions regarding UFAD system design.
The challenge in this regard has been how to accurately account for
differences between a stratified UFAD environment and the familiar
well-mixed environment produced by a conventional overhead (OH)
variable air volume (VAV) air-distribution system.
In this article, we present new guidance
from a recently developed practical and
simplified design procedure to determine
cooling airflow design requirements for
interior occupied spaces of a building with
a UFAD system. Preliminary design guidance for perimeter zones is also provided.
36
ASHRAE Journal
For decades engineers designing OH
air-distribution systems have routinely
calculated the amount of cooling airflow needed to remove sensible heat
loads from a building space by using
the following simple steady-state heat
balance equation.
ashrae.org
Q × (hr · cfm · °F)
1.1 × Btu × DT
(1)
Where:
CFM = total room airflow (cfm)
Q
= total heat gains to room
(Btu/h)
DT = temperature difference
between return temperature
(equal to room setpoint
temperature) and the supply
air temperature (°F)
The validity of this equation relies on
two assumptions: (1) the room is fully
mixed (i.e., uniform temperature disAbout the Authors
Fred Bauman, P.E., and Tom Webster, P.E., are
research specialists, and Corinne Benedek is a
graduate student researcher with the Center for
the Built Environment (CBE) at the University of
California, Berkeley.
October 2007
tribution) and (2) 100% of the net heat gain is removed from
the space by airflow through the room. However, there are
two key aspects of the design and cooling operation of UFAD
systems that invalidate the assumptions of Equation 1 and have
important implications for the determination of UFAD cooling airflow quantities. These issues are room air stratification
and the existence of a cool underfloor air supply plenum, as
discussed further below.
Room Air Stratification
Properly controlled UFAD systems produce temperature
stratification in the conditioned space resulting in higher temperatures at the ceiling level that change the dynamics of heat
transfer within a room, as well as between floors of a multistory
building. Under these conditions, the temperature at the ceiling can no longer be assumed to be equal to the room setpoint
temperature. Figure 1 shows an example room air temperature
profile for an interior zone for purposes of identifying key
features in a stratified profile.1 Previously, most concepts of
UFAD cooling airflow design sizing followed guidelines developed for stratified displacement ventilation (DV) systems, as
described by Chen and Glicksman.2 This procedure attempted
to account for stratification by determining the contribution of
each load component to the occupied zone (the region below
67 in. [1.7 m] for standing and 42 in. [1.1 m] for seated occupants) and then assigning a design temperature difference to
determine the airflow requirements (see discussions for UFAD
systems3,4). However, as will be described later, although this
load-assignment methodology works for traditional DV system
designs, it does not fully characterize the thermal performance
of any stratified system (UFAD or DV) that uses an underfloor
air supply plenum. Furthermore, since stratified conditions of
various magnitudes can exist in the occupied zone, the concept
of determining the airflow quantity required to maintain the
temperature at a 4 ft (1.2 m) high thermostat, which is assumed
to represent a uniform well-mixed occupied zone temperature,
is no longer valid. For purposes of allowing a comparison between cooling airflow quantities used by UFAD vs. well-mixed
OH systems, we have defined an equivalent acceptable comfort
condition for standing occupants in a stratified room as follows
(refer to Figure 1):
• The average occupied zone temperature (Toz,avg), calculated
as the average of the measured temperature profile from
ankle level (4 in. [0.1 m]) to head level (67 in. [1.7 m]), is
equal to the desired setpoint temperature (as measured in a
well-mixed OH system).
• The occupied zone temperature difference (DToz), calculated
as the head-ankle temperature difference, does not exceed the
maximum limit of 5°F (3°C), as specified by ANSI/ASHRAE
Standard 55-2004, Thermal Environmental Conditions for
Human Occupancy.
Underfloor Air Supply Plenums
A distinguishing feature of any UFAD system is the use
of an underfloor plenum to deliver supply air through floor
October 2007
diffusers into the conditioned space. Cool supply air flowing
through the underfloor plenum is exposed to heat gain from
both the concrete slab (in a multistory building) and the raised
floor panels. The magnitude of this heat gain can be quite high,
resulting in undesirable temperature gain to the supply air in
the plenum (sometimes referred to as thermal decay). While the
amount of heat entering the underfloor plenum will not change
the magnitude of the cooling load that must be removed at the
system level, it does directly influence the required cooling
airflow quantity by reducing the amount of heat gain to the room
that must be removed by room air extraction, defined as heat
gain removed by airflow through the room. A recent modeling
study found that for a range of typical operating conditions,
this supply plenum heat gain can amount to 30% to 40% of the
total system heat gain (including 100% of overhead lights). This
results in a reduction in the amount of heat load needing to be
accounted for by the room air extraction rate.5 More recently,
full-scale laboratory experiments have verified the magnitude
of this plenum heat gain.6
Figure 2 is a diagram that summarizes the results of an
ongoing modeling study (using both a whole-building energy
model and a first-law model6,7 that includes a more detailed heat
transfer analysis of the return plenum than was previously done.
As indicated, the model is representative of a middle floor of a
multistory building with UFAD and a hung ceiling.
The figure shows the calculated distribution of total system
heat gain for the room, supply plenum and return plenum. For
a hung ceiling, some portion of the system heat gain will be
removed via airflow through the room where this airflow gains
heat, and after exiting through the ceiling return grille, will lose
heat to the slab in the return plenum. (It may be helpful here to
recall that heat gain to the airflow represents positive extraction
and heat loss, negative extraction.) In addition, although not
shown explicitly, radiation plays an important role in the energy
balance of the system. The results indicate that the room cooling
load ratio, RCLR (defined as the room air extraction divided by
the total system heat gain) is estimated to be 60% to 70%.
Figure 2 also illustrates how warmer temperatures at the
ceiling and in the return plenum drive conductive heat transfer
through the slab into the supply plenum for the floor above, as
well as radiative heat transfer from the ceiling to the floor (and
subsequently conduction through the raised floor into the supply
plenum). Not indicated, but equally important, is the radiant
contribution of the room loads. The calculated net heat gain to
the supply plenum is 35% to 45% and net heat loss from the
return plenum is 10% to 15%. This diagram depicts a typical
interior zone configuration in which a common underfloor
plenum serves both interior and perimeter spaces. Although
the load distribution will remain about the same, the magnitude
of the average temperature gain in the supply plenum will be
based on the total airflow within the plenum. However, this
airflow is governed by the demands of the room to control its
temperature.
The results presented below are based on a preliminary design tool developed as part of a larger research effort focusing
ASHRAE Journal
37
RAT
Height
Ceiling
DTroom
Head
(67 in.)
Toz,avg
Temperature at
Head Height
Tstat
Tstat
(48 in.)
SAT
Occupied
Zone (OZ)
Temperature Near
the Floor
DToz
Ankle
(4 in.)
Temperature
Figure 1: Example room air temperature profile in stratified UFAD system: SAT = room supply
air temperature (diffuser discharge temperature); RAT = return air temperature at ceiling.
Heat Gain into (Loss From) Return Plenum – (10% to 15%)
To
From
Total System
Heat Gain
100%
Perimeter
Zone
Room Air
Extraction
60% to 70%
Ceiling-Floor
Radiation
Through
Slab
65°F
Advertisement formerly in this space.
Ceiling-Slab
Radiation
Through
Ceiling
AHU
Through
Floor
From
To
Heat Gain into Supply Plenum 35% to 45%
Figure 2: Predicted distribution of room cooling load in multistory building with UFAD:
interior zone, total system heat gain = 2.8 W/ft2 (31 W/m2), room airflow = 0.6 – 0.7 cfm/ft2,
(3.1 – 3.6 L/s·m2), diffuser discharge temperature = 65°F (18°C).
on developing energy simulation models
for UFAD systems.6 The design tool accounts for the key issues described previously: (1) room air stratification alters
the assumption of well-mixed conditions,
(2) the conventionally calculated room
cooling load must be reduced by the net
amount of system heat gain transferred to
both the supply and return plenums and
(3) the supply temperature to the room
is greater than that for conventional OH
design and depends on heat gain to the
plenum.
Description of Design Tool
A design tool has been developed as
a spreadsheet-based calculation procedure that in its final form will be easy
to use by practicing design engineers.
The tool is intended to allow the user
to apply various commercially available
38
ASHRAE Journal
ashrae.org
cooling load calculation methods for
conventional overhead systems, including the ASHRAE radiant time series
(RTS) procedure. Figure 3 shows a flow
diagram of the anticipated process for using the design tool. In addition to the load
calculation, users will input several other
parameters that define the design and
desired operation of the UFAD system.
Before proceeding to the main modeling
engine, the calculated total system heat
gain is modified based on an estimated
room cooling load ratio, RCLR, defined
as the percentage of the total system heat
gain (including 100% of lighting) that is
to be assigned to the room in the UFAD
airflow calculation. To date, most of the
design tool development has focused
on interior zone configurations. In this
article, we will highlight recommendations for interior zone cooling airflow
October 2007
120
Standard
Overhead
Load Calculation
Room
Cooling Load
Ratio
Lookup
Modeling
Engine
(Empirical
Correlations)
Example Outputs
Airflow
Occupied Zone DT
Thermostat Setting
Plenum Inlet Temp.
Equivalent OH Airflow
80
Height (in.)
Example
UFAD User
Inputs
Diffuser Type
Diffuser Supply
Temp.
Desired Toz,avg
40
calculations and will also provide preliminary guidance for
perimeter zones. Research is ongoing to complete the design
tool, including perimeter zone airflow calculations.7
The design tool uses a combination of a room energy balance
and empirical correlations based on experimental data from
a full-scale laboratory6 to simulate a simplified temperature
profile constructed of two line segments as shown in Figure 4.
This assumes, for design purposes, that a controlled temperature
profile passes through the thermostat setpoint. It also reflects
the observation that most experimentally measured temperature
profiles exhibit a change in slope between the lower and upper regions of the room. Beginning with the assumed diffuser
discharge temperature (e.g., 65°F [18°C]) and an assumed
airflow rate, the model calculates the air temperature at the
ceiling using a heat balance equation based on the modified
cooling load assigned to the room. The current design tool assumes a constant value of 0.7 for RCLR (i.e., 70% of the total
system heat gain must be removed by room air extraction).
Temperatures at the 4 in. (0.1 m) and 67 in. (1.7 m) heights are
determined through empirical correlations. Using the simple
profile, the tool derives the two comfort parameters, Toz,avg and
DToz, and then determines the airflow that matches most closely
the design conditions.
20
Comparison to Test Data
The experiments used to develop the design tool were conducted in a full-scale test chamber set up to represent an open
plan office with realistic workstations and internal loads.6
The applicability of the design calculations to real buildings
is not currently known but is the subject of ongoing research.
We do not expect that the profile correlations will be affected
significantly by changes in system characteristics. RCLR
correlations still need to be determined for different system
configurations, but the model can easily accommodate changes
in this parameter.
The accuracy of the empirical temperature profile was
verified by comparison with the full-scale test data. This was
done for interior zone loads and two types of diffusers, as
described below.
Swirl (SW) diffuser: These round floor diffusers are one
of the most commonly installed diffusers in UFAD systems;
more models are commercially available than any other design.
The swirl diffuser used in our tests is representative of typical UFAD applications, providing a design airflow of 80 cfm
67 in.
60
Figure 3: Design tool flow diagram.
October 2007
Return at Ceiling
100
Tsetpoint at 48 in.
Measured
Modeled
4 in.
0
70
71
72
73
74
Temperature (°F)
75
76
77
Figure 4: Simplified temperature profile vs. measured data: Swirl
diffusers, cooling load = 3.1 W/ft2 (33 W/m2), SAT = 65.6°F (18.7°C),
Tsetpoint = 74.8°F (23.8°C), airflow = 0.60 cfm/ft2 (3.1 L/s·m2).
SW
VA
Number of Tests
18
8
Toz,avg Average Error (°F)
0.01
0.18
Toz,avg Standard Deviation (°F)
0.32
0.37
DToz Average Error (°F)
0.02
0.02
DToz Standard Deviation (°F)
0.52
0.24
Table 1: Comparison to test data.
(38 L/s) at a plenum pressure of 0.05 in. H2O (12.5 Pa). Since
the stratification performance of swirl diffusers can change at
different airflow rates, the concept of a diffuser design ratio
(DDR) is introduced. DDR is defined as the ratio of actual
airflow to design airflow (80 cfm [38 L/s]). As discussed below,
for design calculations the use of DDR = 1.0 assumes that all
diffusers are operating at their design airflow.
Variable-area (VA) diffuser: This square diffuser is designed
for variable-air-volume operation. The unit we tested used an
automatic internal damper to adjust the active area of the diffuser to maintain a nearly constant discharge velocity, even
at reduced air volumes. The adjustable grilles were set in the
manufacturer’s recommended “spread” position for all tests. The
VA diffuser provides a maximum design airflow of 150 cfm (71
L/s) at a plenum pressure of 0.05 in. H2O (12.5 Pa).
Table 1 shows the calculated errors when comparing the design tool calculations of the two key comfort parameters (Toz,avg,
DToz) with the full-scale experimental data. The model predictions were based on the measured airflow rate. The range of test
conditions covered were the following: 1.9 W/ft2 (20 W/m2)
≤cooling load ≤3.4 W/ft2 (37 W/m2); 0.30 cfm/ft2 (1.5 L/s·m2)
≤room airflow ≤0.85 cfm/ft2 (4.3 L/s·m2); 60.8°F (16.0°C)
≤room SAT ≤68.2°F (20.1°C); 72°F (22.2°C) ≤Tsetpoint ≤76°F
(24.4°C); 0.3 ≤DDR ≤2.0. Figure 4 shows a representative
comparison between the predicted and measured temperature
profiles for one specific swirl diffuser test.
ASHRAE Journal
39
UFAD
UFAD
or OH
Diffuser
Discharge
Temp. (°F)
Cooling
Load*
(W/ft2)
Toz,avg‡ = 75°F
Tsetpoint†† = 73°F
Tsetpoint†† = 75°F
Airflow (cfm/ft2)
Airflow (cfm/ft2)
0.39
0.35
0.59
0.53
0.79
0.70
0.39
0.35
0.59
0.53
0.79
0.70
DToz**
(°F)
Airflow§
(cfm/ft2)
DToz**
(°F)
1.0
0.43
2.7
0.38
3.1
0.34
3.6
0.5
0.40
4.5
0.36
5.2
0.32
5.8
1.0
0.65
2.6
0.58
3.0
0.52
3.4
0.5
0.61
4.4
0.54
5.0
0.48
5.6
1.0
0.87
2.5
0.77
2.9
0.69
3.3
0.5
0.81
4.3
0.72
5.0
0.64
5.6
1.0
0.58
1.9
0.49
2.3
0.43
2.7
0.5
0.54
3.3
0.46
3.9
0.40
4.5
1.0
0.87
1.8
0.75
2.2
0.65
2.6
0.5
0.81
3.2
0.69
3.8
0.61
4.4
1.0
1.17
1.7
1.00
2.1
0.87
2.5
0.5
1.09
3.2
0.93
3.7
0.81
4.3
2.0
1.0
0.46
1.8
0.40
2.0
0.36
2.2
0.39
0.35
3.0
1.0
0.70
1.9
0.62
2.1
0.55
2.3
0.59
0.53
4.0
1.0
0.94
2.0
0.83
2.2
0.75
2.4
0.79
0.70
2.0
1.0
0.62
1.5
0.53
1.6
0.46
1.8
0.39
0.35
3.0
1.0
0.93
1.5
0.80
1.7
0.70
1.9
0.59
0.53
4.0
1.0
1.25
1.6
1.07
1.8
0.94
2.0
0.79
0.70
3.0
3.0
4.0
VA
67°F
Toz,avg‡ = 74°F
Airflow§
(cfm/ft2)
2.0
VA
65°F
Toz,avg‡ = 73°F
DToz**
(°F)
4.0
Swirl
67°F
Diffuser
Design
Ratio†
OH with SAT = 57°F
Airflow§
(cfm/ft2)
2.0
Swirl
65°F
UFAD
*Total cooling load (system heat gain), including 100% of overhead lighting, as used for sizing conventional overhead (OH) systems.
†Diffuser design ratio (DDR) = (actual diffuser airflow)/(diffuser design airflow).
‡Toz,avg = average temperature in occupied zone (between head height, 67 in. [1.7 m], and ankle height, 4 in. [0.1 m]).
§Airflow = Total room airflow, including Category 2 leakage from supply plenum to room.
**DToz = temperature difference between head height, 67 in. (1.7 m), and ankle height, 4 in. (0.1 m).
††Tsetpoint = setpoint temperature measured at 4 ft (1.2 m) height.
Table 2: Design cooling airflow performance for UFAD and OH systems: Interior zones.
Design Tool Results: Interior Zones
Table 2 presents design tool predictions
of UFAD cooling airflow rates and associated occupied zone temperature differences (DToz) for a range of typical interior
zone design conditions. Also shown for
comparison are predicted airflow rates
for a conventional overhead (OH) system
with a supply air temperature (SAT) of
57°F (14°C) and setpoint temperatures
of 73°F (23°C) and 75°F (24°C).
To use the table, select the following
design conditions: diffuser type and discharge temperature, cooling load, room
setpoint temperature (for UFAD systems,
this is equal to Toz,avg) and DDR equal to
1.0. Table 2 also includes information for
swirl diffusers with DDR = 0.5, represent40
ASHRAE Journal
ing a design case where the airflow through
each diffuser is 50% of design airflow (80
cfm [38 L/s]). Since the VA diffuser automatically maintains a consistent throw
height, and a similar room temperature
profile (if there is no significant Category 2
leakage [see below]), VA results are shown
only for DDR = 1.0. The user should exercise care when extrapolating the airflow
data in the table to other design conditions.
It is recommended that the table not be
used for airflow calculations outside of the
following ranges of design conditions in
interior zones: cooling load, up to 4 W/ft2
(43 W/m2); room 4 ft (1.2 m) setpoint temperature, 73°F to 76°F (22.8°C to 24.4°C);
and diffuser discharge temperature, 63°F
to 68°F (17°C to 20°C).
ashrae.org
Air Leakage
Supply plenum leakage is one of the
most important issues facing the UFAD
industry. Experience in the field has
shown that Category 2 leakage (from
the plenum into the room) can often be
in the range of 10% to 20% of design
airflow. To account for leakage in design
calculations, the predicted airflow from
Table 2 should include the estimated
(or measured) air leakage rate at design
conditions. Although the results of Table
2 were developed assuming no leakage,
additional full-scale experiments were
conducted to investigate the impact of
leakage on stratification.6 These experiments demonstrated that for swirl and
VA diffusers with DDR close to 1.0, the
October 2007
increase in DToz and decrease in Toz,avg
will be minimal. These guidelines are
applicable for Category 2 design air
leakage rates up to about 20%. Category
2 leakage rates above 20% may impact
the amount of stratification in the occupied zone, as well as the system’s ability
to control room temperature. Note that
while Category 1 leakage (from the plenum to the outside or other zones in the
building) will not impact room air temperature profiles, it will directly impact
the airflow (and, therefore, energy use)
of the air handler.
less than VA (7% less at room SAT =
65°F [18°C], load = 4 W/ft2 [13 W/m2],
Toz,avg = 74°F [23°C]). VA diffusers,
with their variable air volume control,
produce consistent stratification (DToz),
although approximately 1°F (0.5°C) less
than that for swirls, over all load levels
for the same room SAT and Toz,avg. Swirl
diffusers exhibit higher stratification
under part load conditions (DDR = 0.5),
although nearly all predicted values for
DToz are less than or equal to 5°F (3°C)
(maximum limit specified by Standard
55-2004), except at room SAT = 65°F
(18°C) and Toz,avg = 75°F (24°C).
Comparison to Overhead (OH) System
For standard room operating conditions (UFAD Toz,avg = OH Tsetpoint =
74°F [23.3°C]; UFAD SAT = 65°F) at
all load levels, Table 2 shows that airflow
quantities for swirl and VA diffusers are
predicted to range from 0% to 10% higher
than OH airflows. At the higher room
SAT of 67°F (19.4°C), UFAD airflows
range from 32% to 43% higher than OH
(using 57°F [14°C] SAT). The maximum
predicted DToz for all design conditions
shown in the table for swirl (DDR = 1.0)
and VA diffusers is 3.6°F (2.0°C), indicating that excessive stratification will not
be a problem at design load. The impact
of increasing stratification (produced by
raising the room setpoint for a given room
SAT) on reducing airflow rates is demonstrated by the values for a higher design
setpoint temperature of 75°F (24°C). At
this setpoint and with room SAT = 65°F
(18°C), predicted UFAD airflow rates
are equal for swirl diffusers and slightly
higher (7%) for VA diffusers, compared
to OH airflow rates at all load levels.
Example Design Tool Calculation
Figure 5 presents design tool results
from Table 2 for swirl diffusers supplying 65°F (18°C) air with DDR = 1.0 in
an interior zone with a cooling load of
3 W/ft2 (32 W/m2) and an RCLR = 0.7.
The figure plots predicted cooling airflow rates and DToz as a function of Toz,avg
over the range of 72°F to 76°F (22.2°C
to 24.4°C). Calculations are highlighted
for two design conditions that cover the
range of Toz,avg between 73°F (23°C)
and 75°F (24°C). At each setpoint temperature (read on the left-hand y-axis),
the first step is to read the airflow rate
on the x-axis, and then for the same airflow the second step is to read the DToz
on the right-hand y-axis, as shown. The
results indicate that to design the system
to maintain the average occupied zone
temperature in the range of 74 ±1°F, the
system must be designed for an airflow
in the range of 0.52 to 0.65 cfm/ft2 (2.6
to 3.3 L/s·m2), resulting in an occupied
zone temperature difference in the range
of 2.6°F to 3.4°F (1.4°C to 1.9°C).
Advertisement formerly in this space.
Diffuser Type
The design tool results allow a comparison between the two types of diffusers. VA diffusers, with their higher
vertical throw were previously thought
to require higher airflow rates due to reduced stratification, while swirl diffusers
with throws that vary with airflow were
thought to provide excessive stratification
at low load conditions. The design tool
shows that under design flow conditions
(swirl DDR = 1.0), airflow quantities are
quite similar, with swirl airflows slightly
October 2007
Thermostat Setting
In conventional overhead systems that
aim to maintain a uniform well-mixed
environment, the assumption is made
by building operators that the 4 ft (1.2
m) thermostat setpoint is the same as the
average temperature experienced in the
occupied zone. However, as indicated in
Figure 1, depending on the amount of
stratification that produces cooler temperatures near the floor, the average temperature in the occupied zone (Toz,avg)
ASHRAE Journal
41
Toz,avg
4.0
3.5
75
3.0
74
2.5
DToz (°F)
Toz,avg (°F)
76
DToz
73
2.0
72
71
0.40
1.5
68
66
Plenum Inlet Temperature (°F)
77
64
Average Diffuser
Discharge = 67°F
62
60
Average Diffuser
Discharge = 65°F
58
56
54
52
0.50
0.60
Airflow (cfm/ft2)
0.70
1.0
0.80
Figure 5: Example design cooling airflow performance: interior
zone, cooling load = 3.0 W/ft2 (32 W/m2), swirl diffusers with DDR
= 1.0, diffuser discharge temperature = 65°F (18°C).
will be lower than the single point thermostat temperature. To
maintain equivalent comfort conditions in a stratified environment (e.g., UFAD Toz,avg = OH Tsetpoint), it is recommended to
raise the 4 ft (1.2 m) thermostat setpoint by 1°F (0.5°C) for DToz
values around 3°F (2°C) and by 0.5°F (0.3°C) for DToz values
around 2°F (1°C). For example, to maintain an average occupied
zone temperature of 74°F (23.3°C) for swirl diffusers (DDR =
1.0) supplying 65°F (18°C) air to the space at any load level,
the 4 ft (1.2 m) thermostat should be set at 75°F (24°C). When
the final design tool is released, it will include an automatic
calculation for the 4 ft (1.2 m) thermostat setting.
50
0.0
0.5
1.0
1.5
2.0
2.5
3.0
Airflow (cfm/ft2)
Figure 6: Predicted plenum inlet temperature vs. total plenum airflow
for different average diffuser discharge temperatures: Cooling load
= 3.0 W/ft2 (32 W/m2).
performance in the field may vary, but the trends are very clear. The
results show that plenum thermal decay can be a problem at lower
plenum airflow rates. If coil leaving temperatures in the air handling
unit (AHU) have to be reduced to maintain room supply temperatures, potential economizer energy savings (in suitable climates)
may be eroded. As illustrated in Figure 2, an underfloor plenum
serving an interior zone is typically configured as a larger open
plenum that also serves perimeter spaces, thus increasing the total
airflow through the plenum and reducing the temperature gain. The
above considerations point to the importance of ongoing research
to develop improved plenum design guidelines and to assess the
energy impact of thermal decay on economizer performance.
Plenum Inlet Temperature
Figure 6 shows the predicted plenum inlet temperature as a
function of total plenum airflow for two different average diffuser
discharge temperatures (65°F, 67°F [18.3°C, 19.4°C]) for a cooling
load of 3.0 W/ft2 (32 W/m2). The predictions are based on a simple
steady state energy balance assuming that 40% of the cooling load
enters the supply plenum. Note that while results are shown for an
average room supply temperature, measured diffuser discharge
temperatures across the floor plate will be both higher and lower,
depending on the airflow distribution within the plenum.6,8 Actual
Advertisement formerly in this space.
42
ASHRAE Journal
Perimeter Zones
Perimeter zones differ from interior zones due to the type and
magnitude of the heat sources. In cooling mode, the dominant
heat source creates a large thermal plume that rises vertically
at the window and under peak load conditions the perimeter
heat gain is several times that of total internal gains. Research
is ongoing to complete the development of a perimeter zone
cooling airflow design tool that will be modeled after the interior
zone tool described earlier.6,7 Interim guidance is discussed
briefly below.
Figure 7 presents the results of three
full-scale laboratory experiments investigating room air stratification in a
perimeter zone. The 26 ft (7.9 m) square
test room was configured to simulate an
open plan office containing six workstations with linear bar grilles next to
the perimeter window/wall and swirl
diffusers elsewhere. A solar simulator
in a weather chamber provided direct
solar gain through windows on one wall
with a window to wall ratio of 0.74. The
simulated perimeter zone load for all
tests in Figure 7, including an interior
load level of 3.5 W/ft2 (38 W/m2), was
ashrae.org
October 2007
Room Temperature (°C)
21.1
22.2
23.3
24.4
25.6
26.7
27.8
28.9
3.0
Peak Solar Load
9
2.7
8
2.4
Blinds Open,
8 Linear Bar Grilles
Vanes at 90°
2.4 cfm/ft2
Height (ft)
7
6
2.1
5
4
3
1.5
1.2
0.9
Blinds Open,
10 Linear Bar Grilles
Vanes at 53°
1.9 cfm/ft2
2
1
0
68
1.8
Blinds Closed,
8 Linear Bar Grilles
Vanes at 90°
1.4 cfm/ft2
Height (m)
10
20.0
0.6
0.3
0.0
70
72
74
76
78
Room Temperature (°F)
80
82
84
Figure 7: Room air stratification temperature profiles for perimeter zones at constant
perimeter zone load of 14.8 W/ft2 (159 W/m2), supply temperature of 65°F (18°C), and control
setpoint of 76°F (24.4°C) at 4 ft (1.2 m).
14.8 W/ft2 (159 W/m2), based on the 15 ft
(4.6 m) wide floor area near the window.
These test conditions are representative of
a west-facing zone in 40° north latitude on
July 21 with a window with solar heat gain
coefficient (SHGC) = 0.37. All tests used a
diffuser supply temperature of 65°F (18°C)
and were controlled to a 4 ft (1.2 m) thermostat setpoint of 76°F (24.4°C), meaning
that average occupied zone temperatures
were 75°F (24°C) or below. Key findings
are summarized below.
• The test producing the least amount
of stratification required the highest
airflow rate: 2.4 cfm/ft2 (12.2 L/s·m2),
based on the 15 ft (4.6 m) wide perimeter zone. This test used 8 bar grilles
with vertical vanes, producing the
highest throw and mixing.
• When the number of bar grilles was
increased to 10 and the vanes were
inclined to 53°, thereby reducing the
throw and mixing of the diffusers,
stratification increased and the required
airflow decreased to 1.9 cfm/ft2 (9.7
L/s·m2). This demonstrates the potential
benefits of using lower-throw diffusers,
although care must be taken to maintain
acceptable comfort conditions.
• The lowest airflow requirements were
obtained for the test when window blinds
were closed, producing the highest stratification with an airflow rate of only 1.4
cfm/ft2 (7.1 L/s·m2). This reduction in
October 2007
•
airflow rate is the result of several factors,
including attenuation of the incident solar
radiation entering the space, formation
of a stronger thermal plume around
the blinds, and changes in the radiant
energy distribution (more diffuse). The
use of blinds at peak load has profound
implications for design although considerable difference of opinion exists about
whether to assume blinds open or closed
for design calculations.
For comparison, an overhead system
supplying 55°F (12.8°C) air and maintaining a setpoint temperature of 75°F
(24°C) would require 2.3 cfm/ft2 (11.7
L/s·m2) for this same load condition. If
UFAD supply air temperatures increase
above 65°F (18°C) due to thermal
decay in the plenum, required UFAD
airflow rates would also increase.
Advertisement formerly in this space.
Summary
In this article we have presented new
design guidance for UFAD cooling airflow
calculations in interior zones based on a
recently developed design tool. The design
tool predicts required cooling airflow rates
and the amount of stratification in the occupied zone for a range of design conditions.
Results are shown for swirl and variablearea diffusers, two of the most frequently
installed diffusers in interior zones. The
design tool also compares UFAD airflows
with conventional overhead (OH) airflows
ASHRAE Journal
43
for equivalent design and comfort conditions. The design tool
accounts for heat transfer to the underfloor supply plenum, which
can be a significant portion of the total cooling load. This allows
the calculation of the plenum inlet temperature (air handler leaving
temperature) to maintain a desired diffuser supply temperature.
Preliminary guidance for perimeter zones is presented based
on full-scale testing results. Ongoing research is scheduled to
complete the development of the cooling airflow design software tool in 2008. In particular, the research will investigate the
development of improved models for predicting RCLR and the
effects of air leakage. The completed design tool will include a
perimeter zone model, user interface and further validation.
Acknowledgments
This work was supported by the California Energy Commission (CEC) Public Interest Energy Research (PIER) Buildings
Program under Contract 500-01-035. Partial funding was also
provided by the Center for the Built Environment, University of
California, Berkeley (www.cbe.berkeley.edu). We would like to
thank Norman Bourassa of the CEC PIER Buildings Program,
who served as our Commission Project Manager. We would also
like to express our sincere appreciation to Paul Linden and Anna
Liu of the Department of Mechanical and Aerospace Engineering, University of California, San Diego, who provided valuable
contributions on the model formulation and calculation methods.
We also thank other members of our research team for their
technical advice and insights: Allan Daly of Taylor Engineering
and Hui Jin of University of California, Berkeley.
References
1. Webster, T., and F. Bauman. 2006. “Design guidelines for
stratification in underfloor air distribution (UFAD) systems.” HPAC
Engineering (6).
2. Chen, Q., and L. Glicksman. 2003. System Performance Evaluation
and Design Guidelines for Displacement Ventilation. Atlanta: ASHRAE.
3. Loudermilk, K. 1999. “Underfloor air distribution solutions for
open office applications.” ASHRAE Transactions 105(1):605–613.
4. Bauman, F. 2003. Underfloor Air Distribution (UFAD) Design
Guide. Atlanta: ASHRAE.
5. Bauman, F., H. Jin, and T. Webster. 2006. “Heat transfer pathways
in underfloor air distribution (UFAD) systems.” ASHRAE Transactions
112(2):567–580.
6. Bauman, F., T. Webster, et al. 2007. “Energy Performance of UFAD
Systems.” Final Report to CEC PIER Program. CEC Contract No.
500-01-035. Center for the Built Environment, University of California,
Berkeley. www.cbe.berkeley.edu/research/briefs-ufadmodel.htm.
7. CBE. 2007. “Improvement and Refinement of EnergyPlus/UFAD
and Design Tool.” Center for the Built Environment, University of California, Berkeley. www.cbe.berkeley.edu/research/ufad_designtool.htm.
8. Jin, H., F. Bauman, and T. Webster. 2006. “Testing and modeling of
underfloor air supply plenums.” ASHRAE Transactions (112)2:581–591.
Advertisement formerly in this space.
44
ASHRAE Journal
ashrae.org
October 2007