1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
ATE4152_proof ■ 5 May 2012 ■ 1/9
Applied Thermal Engineering xxx (2012) 1e9
Contents lists available at SciVerse ScienceDirect
Applied Thermal Engineering
journal homepage: www.elsevier.com/locate/apthermeng
A study on a ventilation stack integrated with a light pipe
Q1
Thanyalak Taengchum
m a, Surapong Chirarattananon
n a, b, *, Robert H.B. Exelll a, b, Kuskana Kubaha
a c,
a, b
Pipat Chaiwiwatworakull
a
Joint Graduate School of Energy and Environment, King Mongkut’s University of Technology Thonburi, Bangkok, Thailand
Science and Technology Postgraduate Education and Research Development Office, Ministry of Education, Thailand
c
School of Energy Environment and Materials, King Mongkut’s University of Technology Thonburi, Bangkok, Thailand
b
h i g h l i g h t s
< An experimental and theoretical study of solar heated stack-light pipe is reported.
< Solar heated water exchanges heat with air to create a stack flow.
< Wind, stack, and heat transfer effects are simultaneously coupled.
< The volume of air flow is sufficient for ventilation and passive cooling.
< The light pipe transmits sufficient natural daylight for general illumination.
a r t i c l e i n f o
a b s t r a c t
Article history:
Received 11 November 2011
Accepted 19 April 2012
Available online xxx
A theoretical and experimental study has been conducted on the performance of a vertical light pipe that
also functions as an air flow stack for night ventilation. The rectangular light pipe of height 3 m and
cross-section area 0.0625 m2 surrounded by an air duct of total cross-section area 0.23 m2 is situated
above a room of height 3.8 m and floor area 9 m2. Heat transfer from the hot water in the wraparound
hot water jacket to the air in the duct is assisted by stainless steel fins. The ventilation of the room, due
partly to the buoyancy of the air in the duct and partly to the wind effect, amounted to nearly 10 air
changes per hour which is sufficient for passive cooling during cooler night periods. The light pipe has
specular reflecting walls. It was found that the transmission of daylight through the light pipe in the
middle of a partly cloudy day was sufficient for illuminating the room to general illumination level.
Ó 2012 Published by Elsevier Ltd.
Keywords:
Natural ventilation
Daylighting
Thermal buoyancy
Light pipe
Counter flow heat exchanger
Solar water heater
1. Introduction
The climate of Thailand is hot and humid. Air-conditioning to
provide cooling for thermal comfort has been increasingly used in
consonant with the increase in disposable income. Air-conditioning
load accounts for over 70% of total electric load in a small household. However, night time air is cool and it is possible to use natural
ventilation to achieve thermal comfort in detached houses in
suburban areas for most nights of a year.
A report of the National Statistical Office of Thailand on the
appliance ownership in Thailand, [1], shows that 14.3% and 12.8% of
all households own air-conditioners and electric hot water heaters
* Corresponding author. Joint Graduate School of Energy and Environment, King
Mongkut’s University of Technology Thonburi, Bangkok, Thailand. Tel.: þ66 (2)
4708309.
E-mail addresses:
[email protected] (T. Taengchum), surapong@jgsee.
kmutt.ac.th (S. Chirarattananon),
[email protected] (R.H.B. Exell), kuskana.
[email protected] (K. Kubaha),
[email protected] (P. Chaiwiwatworakul).
(used for personal hygiene-bathing) in 2008. Among all households, more than 40% of middle and high income households own
both air-conditioners and electric hot water heaters. It seems that
ownerships of air-conditioners and electric hot water heaters
correlate strongly and both are increasing steeply. The authors
perceive that warm water (at 40e50 C) produced by heat pump
air-conditioner while running as room air-conditioner, or by solar
hot water heater, could be used to produce and store warm water to
drive stack air flow for night ventilation. In the latter case, cooling
and ventilation are completely passive.
The device in this paper integrates a light pipe and a ventilation
stack in the same unit that will reduce construction cost. The whole
unit is expected to be situated in a large space at the middle of
a house. Daylight transmitted through the light pipe will provide
general lighting for the space during daytime while stack air flow
y
will provide night ventilation. In this paper, raytracing
is used for
calculation of both daylight from sun and that from sky. A wellknown sky luminance distribution model is used with measured
1359-4311/$ e see front matter Ó 2012 Published by Elsevier Ltd.
doi:10.1016/j.applthermaleng.2012.04.045
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
ATE4152_proof ■ 5 May 2012 ■ 2/9
2
T. Taengchum et al. / Applied Thermal Engineering xxx (2012) 1e9
Nomenclature1
DPstack
g
ra
hs
hNL
Ts
Ta
V_ sin
V_ sout
As
CDi
DPsin
DPsout
ns
Pwi
Cpi
vi
stack pressure at the stack inlet or outlet
constant of gravity, 9.81
density of air at inlet
stack height
neutral height
temperature of air at stack outlet
temperature of air at stack inlet
rate of volumetric flow of air at stack inlet
rate of volumetric flow of air at stack outlet
cross-sectional area of stack
discharge coefficient of air flow through an opening
stack pressure inlet
stack pressure outlet
exponent of stack pressure
wind pressure at wall i
local pressure coefficient at wall i
speed of wind into wall i
daylight illuminance data obtained from a nearby station on the
same campus. A heat exchange model is integrated with a stack air
flow model to predict the rate of air flow in the stack. However, the
actual air flow is disturbed by wind and the model is modified to
account for the effect of wind. The integrated model is used to
calculate air flow under the situation of the experiment.
Zhai and Previtali, [2], in a review of vernacular architecture,
identify local climate and cultural heritage as the main influences
on ancient architecture of a location. The authors use vernacular
houses in two locations in Indonesia where the houses are constructed on raised floor with open windows and doors for natural
ventilation for illustration. Natural ventilation and daylighting are
two methods that can help reduce energy needs in modern
buildings. Normally, they are separate and independent operations.
However, in a project supported by the European Union and
participated by five European institutions in five countries called
‘TripleSave’, [3], it was demonstrated that a light pipe can be integrated with a ventilation stack and used with passive or active
heating or cooling system to serve three functions of daylighting,
ventilation, and heating or cooling of buildings. A number of
publications by participating institutions illustrate theoretically
and experimentally the effectiveness of light transmission of light
pipes fitted with different light entry ports and surface material,
[4e6], and the effectiveness of air flow through different ventilation terminals that are subjected to wind from different directions,
[7,8]. Air flow by natural means is due to pressure differences
caused by wind and thermal buoyancy. In the case of buoyancy air
flow in a solar chimney, a number of studies have been reported,
such as those in Refs. [9e11], where heat transfer from solar radiation to air creates buoyancy force to drive air flow through stack,
[12,13]. Studies of wind effect on air flow into buildings have also
been conducted, [14e16]. The methods used in Refs. [9e16] have
not been directly applied to the case of simultaneous heat transfer
to air in a stack when the air flow is subjected to the influence of
wind at the stack outlet. Superposition method with simplified
model has been employed for the mixed wind and stack driven
flow in some studies, [17,18]. However, computational fluid
dynamics (CFD) instead has been reportedly used to study stack air
flow that is simultaneously subjected to the force of wind, [19], and
also to solar heating, [20].
1
Listed in order of appearance.
V_ wi
Awi
nw
dp
3
N
Ma
Mw
R
U
UAa
DT
rs
Pf
f
Dh
Cps
rate of volumetric flow of air due to wind at wall i
area of wall i
exponent of wind pressure
internal counter balancing pressure against wind
pressure
effectiveness of (stack) heat exchanger
number of transfer units
heat capacity flow rate of air
heat capacity flow rate of water
ratio of heat capacity flow rate
overall heat transfer coefficient
air-side heat transfer parameter
log mean temperature difference (LMTD)
density of air at stack outlet
pressure loss due to friction
friction factor
hydraulic diameter
wind pressure coefficient at stack outlet
Light pipes are hollow light guidance systems with highly
reflective interior surfaces that are used to transfer natural daylight
from both the sun and the sky from the exterior of a building into its
interior spaces. Light pipes comprising circular cross sections (or
cylindrical shape) are more commonly used than those comprising
y
rectangular cross sections. Raytracing
and flux transfer have been
applied successfully to the study of façade-mounted rectangular
pipes by Hien and Chirarattananon, [21]. Dutton and Shao, [22], use
long thin rectangular sections to form approximate circular shaped
pipes and simulate light pipe transmission by the use of Photopia,
a computer program. Swift et al., [23], develop theoretical model of
transmission of rectangular light pipe for collimated rays and
report that results from the model agree well with experimental
results.
2. Thermal environment and vernacular architecture
Traditional practice of housing construction is influenced by and
reflects the climate of the location and cultural heritage, [2]. Prior to
the advent of air-conditioning, buildings in Thailand were designed
for natural ventilation.
Dry-bulb temperature of the central region of Thailand
varies from 25 to 35 C over a daily range of about 10 C for
every day except those in the cooler period of November to
e
For most
January. Daily range of relative humidity is 40e80%.
nights, air temperature in suburban and less densely populated
area surrounding a detached house is sufficiently cool for night
ventilation. Table 1 shows the percentage number of hours in
a year between 10 PM and 7 AM that ambient temperature falls
below the given value. Among the middle income people who own
air-conditioners, the present practice is to turn the air-conditioners
in the bedrooms on to sleep at night. The configuration of the stack
proposed in this paper will enable utilization of cool natural air for
ventilation for the same purpose.
Table 1
Number of hours between 10 PM and 7 AM in a year that the ambient temperature
falls within the given value.
Temperature, C
30
29
28
27
26
25
Number of hours
% of number of hours
between 10 PM and 7 AM
3286
100
3256
99
3095
94
2664
81
1925
59
1099
33
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
ATE4152_proof ■ 5 May 2012 ■ 3/9
3
T. Taengchum et al. / Applied Thermal Engineering xxx (2012) 1e9
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
Fig. 1 shows monthly average hourly temperatures. Hourly
temperatures of the four months of November to February exhibitt
distinct pattern of the cooler season where the values are lower
than those of all other months during the night to the early
morning period. If the acceptable temperature is 27 C, the air is
sufficiently cool for over 80% of the night time period in a year, as
seen from Table 1.
3. Experimental set up
The configuration of the light pipe and solar-heated ventilation
stack is shown in Fig. 2, and a cross-section of the stack interior, which
has five concentric layers, is shown in Fig. 3. The fins, which transfer
heat from the water to the air in the duct, are of stainless steel 1.2 mm
thick. The volume of hot water to be contained by the jacket is
0.286 m3. The insulation layers are of fiberglass 12.5 mm thick.
Fig. 4 shows a vertical side view of the stack, which is 3 m high
and is situated above the ceiling of the experimental room. Thermally insulated half-inch copper pipes were used between the solar
water heater tank and the stack water jacket. Hot water from the
solar collector tank was pumped downwards through the water
jacket causing the air inside the stack to rise in counter flow. The
stack water jacket and the air duct act as a counter flow heat
exchanger. Typical values of thermal conductivities of copper and
stainless steel are used for calculation of heat transfer parameters.
The water side heat transfer area is 6.6 m2 while that for the air-side
is 22.5 m2. The estimated value of the overall heat transfer
parameter (UA value) is 56 W K1.
The light pipe transmits daylight to the interior space, which has
four doors, as shown in Fig. 5. A chamber of 1.1 m height at the top
of the stack has downward-pointing black-painted slats to allow air
to escape and keep out rain. The glass cover at the top of the pipe
has transmittance 88%. The walls of the light pipe are covered with
specularly reflecting plastic film having reflectance 99%. The
bottom of the light pipe is covered with a translucent plastic plate
used to diffuse the light.
The size of the light pipe was chosen so that there was sufficient
light flux to illuminate the room. The size of air duct was chosen to
allow sufficient air flow for ventilation. The height of the stack of
3.0 m was determined to create sufficient stack pressure and flow.
A daylight measurement station has been set up on top of
a nearby 7-storey building on the seaside campus of the university.
Beam normal illuminance and irradiance are measured directly by
a suntracker. The tracker also holds two shading balls to shade out
sunlight and sun irradiance from an illuminance sensor and an
Fig. 1. Monthly average hourly temperature.
Fig. 2. Light pipe and solar heated ventilation stack.
irradiance sensor to give values of diffuse sky illuminance and
diffuse irradiance. Global illuminance and global irradiance as well
as total illuminance and total irradiance in each cardinal direction
are measured by individual sensors. Measured data of sun and sky
illuminance from the station were used in the calculation described
in the followings.
4. Mathematical models
The stack with hot water that flows through its jacket performs
as a water to air heat exchanger. The heated air flows up through
the stack by buoyancy force. The room where the stack is situated
has four openings (door and windows) that are subjected to the
force of wind. The mechanisms of heat transfer and air flows in the
three connected components can be described by three coupled
mathematical models as follows.
4.1. Air flow through stack
The pressure difference that drives airflow through a stack due
to buoyancy force can be determined by the following relationship,
[12,13],
g ra ðhs hNL ÞðTs Ta Þ
;
Ts
DPstack ¼
(1)
where DPstack is the pressure difference at the stack inlet (when
hs ¼ 0) or the stack outlet (when hs ¼ stack height), g is the gravity
constant, ra is the density of air at the inlet, hNL is the neutral height,
Fig. 3. Horizontal cross-section of stack. Air duct is divided into 12 square channels by
stainless steel fins. Layers of thermal insulation are shaded.
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
ATE4152_proof ■ 5 May 2012 ■ 4/9
4
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
T. Taengchum et al. / Applied Thermal Engineering xxx (2012) 1e9
Fig. 4. The three system components.
Ts is the temperature of the air at the stack outlet, and Ta is the
temperature of the air at the stack inlet.
The neutral height hNL is an unknown. For a simple stack where
the stack dimension and air temperatures are known, equation of
balance of air flows can be set up from which the neutral height can
be obtained.
The volumetric rates of air flow V_ sin into and V_ sout out of the
stack are determined by
V_ sin ¼ As CDi
DPsin
jDPsin j
1ns
and V_ sout ¼ As CDi
DPsout
jDPsout j1ns
(2)
where As is the cross-sectional area of the stack, CDi is a discharge
coefficient, and ns is an exponent. In this research the inlet area
equals the outlet area.
When wind is present, the wind pressure on each external
facade of a room superimposes a pressure to the air at a given
location. The pressure difference Pwi between the wind pressure on
the wall i and the (static) local outdoor air pressure at the same
location is given by Ref. [16] as
1
C r v2
2 pi a i
(3)
where Cpi is a local pressure coefficient the value of which is
dependent on the direction of the wind on the facade, and vi is the
wind speed. References [14,15] give average value of local wind
pressure coefficient on a wall in a given direction.
The volume flow rate V_ wi of air into the room through an
opening of area Awi in the wall is given by the formula, [16],
A CDi Pwi
nw
¼ wi 1nw
V_ wi ¼ Awi CDi Pwi
jPwi j
Pwi ¼
1
C r v2 dp
2 pi a i
(5)
4.3. Heat transfer in the stack
4.2. Air flow due to wind
Pwi ¼
where CDi is a discharge coefficient, and nw is an exponent
between 0.4 for large openings and 1.0 for small openings. The
second equality in Equation (4) is used to preserve the sign of the
volumetric flow V_ wi which can be negative. In a contiguous room
with openings, the sum of air flows into the room must balance to
zero for all wind velocity and for any room configuration. This
implies that there is a counter-balancing pressure from the interior
of the room to enable the flows of air into and out of the room to
balance out. Let this counter balancing pressure in the room in
Fig. 5 be dp. Then for opening i, the net wind pressure on the
opening is given as
(4)
The temperature of the air entering the stack at the bottom is
assumed to be the ambient air temperature Ta in the room. Let Twi
be the temperature of the water flowing into the top of the water
jacket around the stack from the solar water tank. Then the
temperature Ts, which is the temperature that air emerges from the
stack is raised to, is given by Ref. [24] as
Ts ¼ Ta þ 3 ðTwi Ta Þ
(6)
where 3 is the effectiveness of the heat exchange process in the
stack. This value is obtained from
3
¼
1 exp½Nð1 RÞ
1 R exp½Nð1 RÞ
(7)
where N is the number of heat transfer units, and R is ratio of the
heat capacity flow rates of air Ma and water Mw. The quantity N is
related to heat capacity flow rates and the heat exchanger
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
ATE4152_proof ■ 5 May 2012 ■ 5/9
5
T. Taengchum et al. / Applied Thermal Engineering xxx (2012) 1e9
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
Fig. 5. The experimental room and stack (sloping roof not shown).
parameter UAa, where U is the overall heat transfer coefficient and
Aa is the heat transfer area (air-side) of the heat exchanger. The
value of UAa (The same UA value as that in Section 3) is related to the
heat transfer rate Q by the equation,
(8)
Q ¼ UAa DT;
where DT is the log mean temperature difference (LMTD) across the
heat exchanger, see Ref. [21]. In Equation (6), Ts (and Two as well) is
dependent on 3 , which is in turn dependent on the rate of heat
capacity flow of air, Ma or the volumetric flow rate of air through
the stack, V_ sin or V_ sout in Equation (2).
where rout is the density of air at the outlet of the stack. The counter
balancing pressure dp for this experimental room also exerts on the
inlet (bottom) of the stack, thus modifying the pressure at the inlet.
The wind pressure also exerts at the top of the stack, thus modifying the pressure at the stack outlet. The roughness of the interior
surface of the stack can act to reduce the flow of air through the
stack. The pressure loss due to this friction force is given by the
y
equation, [21], as
DarcyeWeisbach
Pf ¼ f
h v2in
r
Dh a 2
where f is the friction factor and Dh is the hydraulic diameter. The
resultant mass balance equation at the stack then becomes
4.4. Combined equations
When wind exerts pressure onto the experimental room with
the stack-light
pipe in Fig. 5, air can flow through all four openings
and through the outlet on top of the stack. The mass balance
equation for air flowing through the room is written as
"
X
i ¼ 1e4
#
ra V_ wi þ rs V_ sout ¼ 0; or
3
1
Cpi ra v2i dp
7
6 X
ra Awi CDi 2
4
1nw 5 þ rs V_ sout ¼ 0
i ¼ 1e4
1Cpi r v2 dp
a i
2
2
(9)
ra V_ sin þ rs V_ sout ¼ 0; or
where,
ra DPsin
jDPsin j1ns
þ
rs DPsout
jDPsout j1ns
¼ 0
DPsin ¼ ðgra ðhNL ÞðTs Ta Þ=Ts Þ þ dp Pf
DPsout ¼ ðgra ðhs hNL ÞðTs Ta Þ=Ts Þ þ 1=2Cps ra v2i .
(10)
and
Here, Cps is the wind pressure coefficient at the stack outlet. It is
clear that dp and hNL are the two unknowns in Equations (9) and
(10). Section 4.3 also identifies Ma as another unknown variable.
Equations (6), (9) and (10) form 3 simultaneous nonlinear equations that can be used to solve for the problem of air flow through
the heated stack that is subjected to the force of wind. The approach
taken differs from those in Refs. [17,18]. Here, all phenomena are
dealt with explicitly without any simplifying assumption and the
equations are obtained from application of heat and mass balances.
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
ATE4152_proof ■ 5 May 2012 ■ 6/9
6
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
T. Taengchum et al. / Applied Thermal Engineering xxx (2012) 1e9
4.5. Transmission of daylight through light pipe
Hien and Chirarattananon
n [21], use raytracing principle in
calculating transmission of light rays through rectangular light
pipes. The configuration of each flat section that together with
other sections forms a rectangular light pipe is defined using plane
geometry and each of its corner point is referenced to a Cartesian
coordinate. When light rays traveling along a given direction
incident on an internal surface, the rays are specularly reflected
onto another surface. Daylight from the sun is considered to
comprise collimated rays and raytracing method is used to trace its
travel. However, for diffuse light from the sky, the method of flux
transfer is used to calculate its transmission through a pipe. The
authors in Ref. [21] encode the raytracing and flux transfer
methods in a computer program called BESim. In this paper, the
ASRC-CIE sky luminance model is used to model diffuse daylight,
[25], and use raytracing
y
to trace light rays from each of the standard 145 sky zones. The ASRC-CIE model uses four CIE sky models,
clear, intermediate, overcast, and a high turbidity clear sky model.
Perez’s clearness index and brightness index in Ref. [25], calculated
from values of measured beam irradiance and diffuse irradiance,
are used to identify sky condition and to weigh contribution from
each of the four CIE sky models. The model references zenith
luminance.
5. Results and discussion
5.1. Ventilation
5.1.1. Design calculations for the ventilation stack
For ventilating the experimental room, the preliminary target
was to have an air flow of 0.1 m3 s1, or about 10 air changes per
hour in this experimental room. Assuming ventilation for 8 h per
night and a rise in temperature of the air passing through the stack
of 5 C, the amount of heat required on the air-side
was about
4.0 kW h per day.
Average solar insolation per day at the location of experiment is
18.2 MJ m2 or 5 kW h m2. Assuming an average efficiency of
a solar collector of 50%, the required collector area is 1.6 m2. The
collector available in the market, chosen and used in the experiments had an area of 2.16 m2 and a water storage tank with
a capacity 160 l.
The capacity of a small water pump available and used was 280 l
per hour, or 0.078 l s1. The temperature drop of the hot water
through the stack jacket was expected to be 1.5 C.
5.1.2. Experiments on ventilation
Experiments were conducted mainly during daytime to determine the amount of ventilation produced by the stack with solar
heated water pumped through the water jacket. Measurements
were made of the water flow rate, the temperature Twi of the water
entering the top of the stack, the temperature Two of the water from
the bottom of the stack, the temperature Ts of the air emerging from
the top of the stack and the air speed vin into the bottom of the
stack. Type K thermocouples were used for the temperature
measurements, and hot wire anemometers were used for
measuring the air speed into the stack. Measurements were also
made of the wind speed and direction, the ambient air temperature
Ta, and the ambient relative humidity outside the building.
The measured temperatures Ta, Twi, Two, and Ts for an experiment conducted on a day in June 2010, when solar insolation was
high and wind speed was low, are shown in Fig. 6. Fig. 7 shows the
measured volumetric airflow rate V_ sout through the stack in the
same experiment together with the calculated total airflow rate
V_ sin . The distinctive patterns of the temperatures of the inlet Twi
Fig. 6. Measured temperatures in the stack.
and that of the outlet Two hot water between 10.07 and
d 10.59 in
Fig. 6 require a detailed examination. As is described subsequently,
there are 3 distinct periods of the temperature patterns: 10.07 to
10.59, 10.59 to 12.00, and beyond 12.00.
Period 1: 10.07 to 10.59. At the start of the experiment, the
water in the stack jacket was all at 32.5 C. The solar collector had
accumulated hot water in its own tank during the previous day to
stratify the water in the tank to different temperature levels.
Fig. 8 together with Fig. 6 help illustrate the situation. Part of the
water from the lowest stratification at the bottom of the tank,
with temperature 45 C, had flowed by natural thermosyphon
through the solar collector in the morning that resulted in raising
the temperature of water in the top stratum to 62 C when the
pump operated to supply hot water to the jacket. Fig. 8a illustrates the situation at the start of the experiment at 10.07 h. Fig. 9
shows graphs of global solar irradiance, and of solar illuminance
for the day, the two graphs at the top. The temperature of the
water that flowed subsequently from the remainder of the solar
Fig. 7. Comparison between experimental and calculated volumetric airflow rates.
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
696
697
698
699
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717
718
719
720
721
722
723
724
725
726
727
728
729
730
731
732
733
734
735
736
737
738
739
740
741
742
743
744
745
746
747
748
749
750
751
752
753
754
755
756
757
758
759
760
761
762
763
764
765
766
767
768
769
770
771
772
773
774
775
776
777
778
779
780
781
782
783
784
785
786
787
788
789
790
791
792
793
794
795
796
797
798
799
800
801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
ATE4152_proof ■ 5 May 2012 ■ 7/9
7
T. Taengchum et al. / Applied Thermal Engineering xxx (2012) 1e9
Fig. 8. Illustration of the water temperatures during the two periods.
Fig. 9. Irradiance and illuminance on the day of experiment.
hot water tank into the stack jacket was lower while the
temperature of the leaving water from the jacket, Two, remained
at 32 C. By 10.59 all water from the stack jacket had emptied into
the solar collector tank and the mixture of water from the head of
the jacket at 10.07, with temperature 48 C, had reached the
bottom of the jacket. During this period, heat from only the upper
part of the jacket was transferred to air to drive the stack flow
since the temperature of water at the lower part remained the
same as that of the air in the stack. Effective height of the part of
the stack that drove air flow started from 0 m at the beginning to
reach 3 m at the end of the period. Stack driven air flow was
lowest during this period.
Period 2: 10.59 to 12.00. Fig. 8b illustrates the situation at the
start of this period. The water in stack jacket had totally replaced
the water in the solar water tank and this water had been heated by
the solar collector to 45 C. The temperature of the water in the
jacket had reached 45 C. Stack driven air flow had increased from
the first period.
Period 3: from 12.00 onward. Solar radiation from a relatively
clear sky had increased its intensity and the temperature at the top
of the collector tank increased beyond 45 C at the beginning of this
period. The temperature of water flowing into the stack exceeded
48 C near the end of the period. Stack driven air flow became
highest in this period.
Summary of results. Table 2 shows average temperatures, wind
speed, air flow, heat transfers and other quantities from the
experiment for the 3 periods. The average inlet water temperature
in Period 1 is higher than those of the other two periods. In period
2, the average outlet water temperature is higher than that at the
inlet, thus straight forward calculation of heat transfer from hot
water would give misleading results for Period 1 and 2. The values
of log-mean temperature difference LMTD and heat transfer to air
Q_ a in Period 3 are used in Equation (6) to obtain the air-side heat
transfer parameter UAa a value of 47.9 W K1. This value is used in
the calculation of air flow through the stack to be described next.
5.1.3. Calculation of stack air flow
In applying Equations (1)e(10) for calculation of stack air flow,
first the coefficients, exponents, and areas where air flows through
of Equations (2)e(4) are set to values appropriate for the problem.
Table 3 shows the given values, where the discharge coefficients,
wind pressure coefficients and exponents assume values typically
recommended
d [13e16]. Note that the wind was from the southwest
direction. Next, the values of heat transfer parameters in Equations
(7) and (8) are given as Mw ¼ 325.7 W K1 (for the pump flow of
280 l per minute) and UAa ¼ 47.9 W K1.
In the experiment, the physical dimensions of the room and the
stack are already known. From the experiment, the temperatures of
entering water and of air into the stack are also known. In the
absence of wind, there is no wind pressure at the openings into the
room, and the air flows through the stack due to buoyancy force of
the difference of air temperatures at the entry and exit of stack. The
air temperature difference is due to heat transfer by water to air. In
this case, the temperature of air at stack exit and the rate of air flow
are two unknown variables in the heat transfer equation (6) or (7)
and the stack flow equation (10). When wind exerts pressure at the
openings it causes a counter balancing pressure dp. This same
pressure adds to the buoyancy pressure at the bottom of the stack.
The number of unknowns becomes 3.
The problem of calculation of stack air flow now is reduced to
the following problem statement: Given a set of values of condition
of air at stack inlet (Ta and relative humidity), inlet water temperature, and wind velocity, find a set of values for va, stack air velocity,
dp, counter pressure to wind, hNL, neutral height of air flow in the
stack, that satisfy the flow balance and heat transfer equations (6),
Table 2
Experimental average temperature, air flow, and heat transfer values.
Period
Wind speed, m s1
Twi C
Two C
Ta C
Ts C
V_ sin m3 s1
Q_ a W
Q_ w W
LMTD
UAa W K1
1
2
3
0.71
0.92
1.05
51.9
44.6
47.9
32.6
46.3
45.7
32.8
33.1
33.8
39.8
40.7
39.0
0.025
0.055
0.089
152
428
496
NA
NA
703
NA
7.67
10.34
NA
NA
47.9
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
826
827
828
829
830
831
832
833
834
835
836
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
871
872
873
874
875
876
877
878
879
880
881
882
883
884
885
886
887
888
889
890
891
892
893
894
895
896
897
898
899
900
901
902
903
904
905
906
907
908
909
910
911
912
913
914
915
916
917
918
919
920
921
922
923
924
925
926
927
928
929
930
931
932
933
934
935
936
937
938
939
940
941
942
943
944
945
946
947
948
949
950
951
952
953
954
955
ATE4152_proof ■ 5 May 2012 ■ 8/9
8
T. Taengchum et al. / Applied Thermal Engineering xxx (2012) 1e9
Table 3
Values of coefficients and exponents for Equations (2)e(4).
Air flow opening
North
East
South
West
Stack
Area (m2)
Wind pressure coefficient
Discharge coefficient
Exponent in (2) and (4)
0.1
0.231
0.65
0.65
0.1
0.231
0.65
0.65
0.1
0.213
0.65
0.65
0.1
0.213
0.65
0.65
0.237
0.297
0.5
0.65
(9) and (10). The solution to the three simultaneous nonlinear
equations was obtained by the use of multiple-variable Newton
Raphson numerical method. The first step in the calculation was to
assume a value each for va, dp, and hNL. With given value of va, the
heat capacity flow rate Ma and consequently the temperature Ta
were calculated. These values were then used to calculate the left
hand side functions in Equations (9) and (10). Numerical Jacobian
(matrix of difference approximation to partial derivatives of functions) were then obtained and the calculation step continued.
In the experiment, all data were recorded on 1-min
n interval, but
the measured input values were averaged as 5-min values for use in
the calculation. The calculated volumetric stack air flow obtained is
shown in the graph of Fig. 7, together with graphs of experimental
values, and of wind speed.
For the first period, the effective stack height used in the
calculation was varied linearly from 0 m at the beginning of the
period to 3 m at the end of the period. The effective stack height for
the other two periods was set at 3 m. The resulting graph of
volumetric air flow appears to match reasonably well with that
from experiment. However, since 5-min average values of inlet
water temperature and wind speed were used in the calculation,
the resulting graph appears smoother than that from experiment.
The calculated volumetric flow rates of air through the stack for the
3 periods are obtained respectively as: 0.052, 0.071, and
0.093 m3 s1. These values are slightly larger than the corresponding values in Table 2. The corresponding RMSD (root of mean
square difference between measured and calculated) values for
each of the three periods and for the whole experiment are 0.034,
0.021, 0.056, and 0.027 m3 s1.
The fact that the method employed enable calculated results to
match reasonable well with experimental results illustrates that
this method of directly couple the three equations of wind pressure
flow, stack pressure flow, and heat exchange through mass and heat
balances is applicable. However, it is noted here that values of
discharge coefficients are also highly relevant to the outcomes. The
resultant volumetric air flow through the stack obtained corresponds to the value of discharge coefficient of 0.5 used.
5.2. Daylighting through light pipe
5.2.1. Experiment on the light pipe
During daytime the stack functions as a light pipe to transmit
daylight into the building interior, as shown in Fig. 3. Measurements were made of the beam, diffuse and global illuminance using
sensors in the daylight measurement station and the results are
shown in Fig. 9. Measurements were also made of the total daylight
illuminance at the top of the light pipe under the glass cover and
the illuminance under the diffuser plate at the exit of the light pipe
and the results are shown in Fig. 10. The very low illuminances
before 10:20 and after 14:10 are caused by shading of the entrance
to the light pipe by the slatted cover (see Fig. 4). At noon the illuminance at the entrance was 59 klux and the illuminance at the exit
was 33 klux, giving a transmission of 56%, but at 12:40 the transmission was 84%. The sky of the day was relatively clear and beam
illuminance featured prominently. The smaller angle between the
beam rays and the pipe during noon led to the observed results. The
Fig. 10. Comparison between experimental and calculated daylight illuminances.
total flux of transmitted diffuse daylight was 2.5 kilo lumens
(40 klux from Fig. 10 multiplied by 0.0635 m2 of aperture area),
which is about the same as the volume of light flux from a common
long fluorescent lamp. This is sufficient for general illumination in
the room.
5.2.2. Calculation of daylight transmission through the light pipe
The calculation of the daylight transmission through the light
pipe was aided by the use of a modified version of BESim, where
y
raytracing
is now used for both daylight from sun and that from
sky. There is fairly good agreement between the experimental and
calculated values. The graphs in Fig. 10 include calculated daylight
illuminance at light pipe entry to show that BESim could also
handle shading from obstruction. The calculated results correspond to a light pipe transmission of 75%, similar to that from
experiment.
6. Conclusion
The results from the experiment described in this paper
demonstrate that a solar heated stack surrounding a light pipe can
performs both function of providing cool natural ventilation air
during night time and bringing daylight to the center of a large
space in a house for general illumination during daytime. The
specific configuration in this research differs from that described in
Ref. [3] in that here there is a separate channel for ventilation air to
flow, the light pipe itself is not used for air flow, and that hot water
is used to transfer heat to air directly in the stack to create buoyancy
force.
The results presented in this paper demonstrate that the
simple method of calculation used is applicable. The significance
of this result is that it is possible to utilize the method to design
a system to achieve a rate of ventilation desired, to transmit given
volume of light flux, and to evaluate the cost effectiveness of
a configuration.
The specific experimental results illustrate that designed
ventilation rate of 0.1 m3 s1 or 100 l s1 was achieved. However, it
seems that the capacity of hot water tank used was not sufficient.
Acknowledgements
This work was jointly funded by the National Science and
Technology Development Agency of the Ministry of Science and
Technology and the National Research University Programme of the
Commission for Higher Education of the Ministry of Education of
Thailand.
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
956
957
958
959
960
961
962
963
964
965
966
967
968
969
970
971
972
973
974
975
976
977
978
979
980
981
982
983
984
985
986
987
988
989
990
991
992
993
994
995
996
997
998
999
1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
1011
1012
1013
1014
1015
1016
1017
1018
1019
1020
1021
1022
1023
1024
1025
1026
1027
1028
1029
1030
1031
1032
1033
1034
1035
1036
1037
1038
1039
1040
1041
1042
1043
1044
1045
1046
1047
ATE4152_proof ■ 5 May 2012 ■ 9/9
T. Taengchum et al. / Applied Thermal Engineering xxx (2012) 1e9
References
[1] Economic and Social Statistic Bureau, National Statistical Office of Thailand,
Statistics on household appliance ownerships. Available at: <http://www.nso.
go.th/keystat/keystatDB>.
[2] Z. Zhai, J.M. Previtali, Ancient vernacular architecture: characteristics categorization and energy performance evaluation, Energy and Buildings 42
(2010) 357e365.
[3] K. Siren, T. Helenius, L. Shao, S. Smith, B. Ford, C. Diaz, A. Oliveira, S. Varga, J.
Borth, E. Zaccheddu, Combining light pipe and stack ventilation, in: World
Renewable Energy Congress VI, Brighton, 1e7 July 2000, pp. 395e400.
[4] A.A. Elmualim, S. Smith, S.B. Riffat, L. Shao, Evaluation of dichroic material for
enhancing light pipe/natural ventilation and daylighting in an integrated
system, Applied Energy 62 (1999) 253e266.
[5] G Oakley, S.J. Smith, L. Shao, S.B. Riffat, TripleSave e the investigation and
monitoring of a combined natural daylighting and stack ventilation system.
CIBSE Conference Papers. Dublin, 2000.
[6] L. Shao, S.B. Riffat, Daylighting using light pipes and its integration with solar
heating and natural ventilation, Lighting Research and Technology 32 (2000)
133e139.
[7] S. Varga, A.C. Oliveira, Ventilation terminals for use with light pipes in
buildings: a CFD study, Applied Thermal Engineering 20 (2000) 1743e1752.
[8] A.C. Oliveira, A.R. Silva, C.F. Afonso, S. Varga, Applied Thermal Engineering 21
(2001) 1925e1936.
[9] K.S. Ong, A mathematical model of a solar chimney, Renewable Energy 28
(2003) 1047e1060.
[10] K.S. Ong, C.C. Chow, Performance of a solar chimney, Solar Energy 74 (2003)
1e17.
[11] D. Ryan, S.A.M. Burek, Experimental study of the influence of collector height
on the steady state performance of a passive solar air heater, Solar Energy 84
(2010) 1676e1684.
[12] K.T. Anderson, Theoretical considerations on natural ventilation by thermal
buoyancy, ASHRAE Transactions 101 (2) (1995) 1103e1117.
9
[13] D. Etheridge, M. Sandberg, Building Ventilation: Theory and Measurement,
John Wiley and Son, Essex, 1996.
[14] M.V. Swami, S. Chandra, Correlation for pressure distribution on buildings and
calculation of natural ventilation air flow, ASHRAE Transactions 93 (1) (1987)
243e265.
[15] M.V. Swami, S. Chandra, Procedure for Calculating Natural Ventilation Air
Flow Rates in Buildings, final report FSEC-CR-163-86 (1987), Florida Solar
Energy Center, Cape Carnaveral, Fl.
[16] M.W. Liddament, A Guide to Energy Efficient Ventilation, AIVC, Coventry, UK,
1996.
[17] M.H. Sherman, Superposition in infiltration modeling, Indoor Air 2 (1992)
101e114.
[18] I.S. Walker, D.J. Wilson, Evaluating models for superposition of wind and
stack effects in air infiltration, Building and Environment 28 (1993)
201e210.
[19] H.F. Nouanegue, L.R. Alandji, E. Bilgen, Numerical study of solar-wind
tower systems for ventilation of dwellings, Renewable Energy 33 (2008)
434e443.
[20] B. Zamora, A.S. Kaiser, Numerical study on mixed buoyancy-wind driving
induced flow in a solar chimney for building ventilation, Renewable Energy 35
(2010) 2080e2088.
[21] V.D. Hien, S. Chirarattananon, An experimental study of a façade mounted
light pipe, Lighting Research and Technology 41 (2009) 123e142.
[22] S. Dutton, L. Shao, Raytracing simulation for predicting light pipe transmittance, International Journal of Low Carbon Technologies 2 (2008)
339e358.
[23] P.D. Swift, R. Lawlor, G.B. Smith, A. Gentle, Rectangular-section mirror light
pipes, Solar Energy Materials and Solar Cells 92 (2008) 969e975.
[24] J.F. Kreider, P.S. Curtis, A. Rabl, Heating and Cooling of Building: Design for
Efficiency, second ed. McGraw-Hill, Inc, Singapore, 2005.
[25] R. Perez, P. Ineichen, R. Seals, J. Mechaels, R. Stewart, Modeling daylight
availability and irradiance components from direct and global irradiance,
Solar Energy 44 (1990) 271e289.
Please cite this article in press as: T. Taengchum, et al., A study on a ventilation stack integrated with a light pipe, Applied Thermal Engineering
(2012), doi:10.1016/j.applthermaleng.2012.04.045
1048
1049
1050
1051
1052
1053
1054
1055
1056
1057
1058
1059
1060
1061
1062
1063
1064
1065
1066
1067
1068
1069
1070
1071
1072
1073
1074